KALOT Group
This translation is an AI-assisted draft pending human review. It is not indexed for search yet.Read the reviewed Persian original
Earthing and bonding clamps

Complete Product Overview

U clamp for connecting conductor to earth rod and reinforcing bar

Last updated:

The U clamp from KALOT Group, known in the trade as a "U-bolt clamp" or "U-type clamp", connects copper earth conductor to an earth rod or reinforcing bar. The U-bolt loops around the earth rod or reinforcing bar, and the conductor passes between the two brass jaws, in line with or at right angles to the earth rod. Tightening the two nuts presses the conductor between the jaws and seats the earth rod firmly in the jaw facing it: a bolted connection you can open for inspection and measurement, then close again.

We made this clamp for places where the earth conductor must fasten to the top of an earth rod inside an earth inspection pit, or to a reinforcing bar, whether inside the foundation reinforcement cage before concreting or at a connection point that stays accessible. Because the U-bolt does not rely on a thread, it also fastens onto an unthreaded earth rod, an earth rod whose top was damaged during driving, and ribbed reinforcing bar. The body is brass, and the U-bolt and nuts are stainless steel. Six codes, from UBDV 0906 to UBDV 2012, cover earth rods or reinforcing bars from 9.5 to 20 mm and copper conductor from 6 to 300 mm². If your sizes fall between two codes, our specialists will recommend the right one.

U clamp for copper conductor, earth rod and reinforcing bar

To choose a code, you need just two sizes: the diameter of the earth rod or reinforcing bar and the conductor cross-section.

  • Copper conductor to earth rod and reinforcing bar
  • Conductor in line or at right angles, through-run or terminating
  • Brass body, stainless steel U-bolt
  • Conductor from 6 to 300 mm² in six codes
  • Conductor in line with or at right angles to the earth rod

    You fasten the conductor between the two jaws, in line with or at right angles to the earth rod. In the clamp shown in the images and drawings on this page, the middle hole takes an in-line conductor and the cross hole, below the legs of the U-bolt, takes a perpendicular one. The conductor can pass through the clamp and on to the next earth rod, or end in this clamp.

  • Conductor clamp for reinforcing bar

    The U-bolt needs no thread and also fastens around ribbed reinforcing bar. Use it to bond copper earth conductor to the foundation reinforcement before concreting, or to the structural reinforcement at an accessible point.

  • Material: brass and stainless steel

    The two-jaw body is cast brass, and the U-bolt, nuts and washers are stainless steel.

    Body chemical composition test report (PDF)Website membership required · Sign in or join
  • Six UBDV codes

    You will find the table of codes UBDV 0906 to UBDV 2012 on the technical specifications tab and in the U clamp datasheet.

    U clamp datasheet (PDF)
  • Advice from KALOT Group specialists

    When you enquire, send us the diameter and material of the earth rod or reinforcing bar, the conductor cross-section, the conductor direction (in line or at right angles) and the quantity you need, and our specialists will recommend the right code. For ribbed reinforcing bar, give its nominal diameter.

Technical Product Information

Click to view enlarged

Feature

Value

Type

Two-jaw U clamp for connecting a conductor to an earth rod or reinforcing bar

Body (two jaws)

Cast brass

U-bolt and nuts

Stainless steel

Fastening parts

U-bolt, two nuts and two flat washers

Conductor type

Stranded copper conductor

Earth rod or reinforcing bar diameter

9.5 to 20 mm (depending on the code)

Conductor cross-section

6 to 300 mm² (depending on the code)

Conductor route

In line with or at right angles to the earth rod; through-run or terminating

Matching earth rod

Copper, copper-bonded or stainless steel, threaded or unthreaded

Connection type

Bolted, can be opened and refastened

Typical installation location

Earth inspection pit; foundation reinforcement before concreting; accessible connection point on structural reinforcement

Codes

UBDV 0906 to UBDV 2012 (six codes)

U clamp codes (UBDV)

Code

Earth rod or reinforcing bar diameter (mm)

Conductor cross-section (mm²)

⁦UBDV 0906⁩

⁦9.5-12.5⁩

⁦6-35⁩

⁦UBDV 1406⁩

⁦14⁩

⁦6-35⁩

⁦UBDV 1416⁩

⁦14-16⁩

⁦16-70⁩

⁦UBDV 1435⁩

⁦14-20⁩

⁦35-150⁩

⁦UBDV 2070⁩

⁦20⁩

⁦70-185⁩

⁦UBDV 2012⁩

⁦20⁩

⁦120-300⁩

Diameter is in millimetres and cross-section in square millimetres. Our products improve continuously and the dimensions of some may be updated, so please check the final dimensions with our specialists before you buy.

U clamp dimensional drawing

Dimensional drawing of the U clamp with a table of codes.

Download the dimensional drawing (PDF)

Technical drawing

Technical drawing of the U clamp.

Download the technical drawing (PDF)

Two holes for the conductor

In the clamp shown in the image below, the middle hole takes a conductor in line with the earth rod and the cross hole takes one at right angles to it. In this side view, the conductor has passed through the middle hole, and the opening of the cross hole is visible between the two jaws.

Side view; the opening of the cross hole between the two plates is visible.

U clamp for connecting conductor to earth rod and reinforcing bar

Drag to rotate; scroll to zoom.Open full screen

Frequently Asked Questions

What is a U clamp and what does it do?

The U clamp is a brass part with a U-shaped bolt that fastens copper earth conductor to an earth rod or reinforcing bar. The bolt loops around the earth rod, the conductor sits between the two jaws, and two nuts press it tight. The connection can be opened for inspection.

How do we choose the size of a U clamp (UBDV code)?

For a 20 mm earth rod and a 240 mm² conductor, code UBDV 2012 is the right choice. Find the code in the code table using the diameter of the earth rod or reinforcing bar and the conductor cross-section; both sizes must fall within the range of the same code. For sizes at the limit of a range, our specialists will recommend the right code.

Does the U clamp also fasten onto ribbed reinforcing bar?

Yes. The U-bolt loops around the ribbed reinforcing bar, which sits in the seat of the clamp jaw, and the conductor, in line with or at right angles to the bar, is fastened between the two jaws. You can place this connection inside the foundation reinforcement cage before concreting, or at a point that stays accessible for inspection. Choose the code from the code table using the diameter of the reinforcing bar and the conductor cross-section.

Can the conductor pass through the U clamp, or must it end there?

Both are possible. You can run the conductor through the clamp and on to the next earth rod or reinforcing bar, or end it in this clamp. With a through-run conductor, you connect several earth rods with one continuous conductor, without cutting it.

Should we fasten the conductor in line with the earth rod or at right angles to it?

The conductor's route sets the direction, and the U clamp accepts both. In the model shown in the images and drawings on this page, an in-line conductor passes through the middle hole and a perpendicular conductor through the cross hole, below the legs of the U-bolt. The conductor must sit fully in the hole so that tightening the nuts presses it between the two jaws.

What is the U clamp made of?

The two-jaw body is cast brass, and the U-bolt and nuts are stainless steel. In the chemical composition test of the U clamp body by emission spectrometry (DIN EN 15079), copper is the alloy base, with zinc at 4.6, lead at 4.7 and tin at 1.27 per cent. You will find the report of this test under "Documents and downloads" on this page.

What is the difference between a brass U clamp and a galvanised U clamp?

Our brass U clamp is for copper conductor and for copper, copper-bonded or stainless steel earth rods, while the galvanised U clamp is for galvanised conductor and reinforcing bar. The clamp material must be compatible with the conductor and the earth rod, because galvanised steel in contact with copper may suffer galvanic corrosion.

Should the U clamp connection to the earth rod go inside an earth inspection pit or underground?

This clamp belongs at accessible points, such as a concrete or polyethylene earth inspection pit, where you can see it, open it for measurement and fasten it again. It is also fastened inside foundation concrete, before the pour. Make connections that go directly underground permanent with exothermic welding.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.