Move your pointer over the image to zoom in
Complete Product Overview
U clamp for connecting conductor to earth rod and reinforcing bar
Last updated:
The U clamp from KALOT Group, known in the trade as a "U-bolt clamp" or "U-type clamp", connects copper earth conductor to an earth rod or reinforcing bar. The U-bolt loops around the earth rod or reinforcing bar, and the conductor passes between the two brass jaws, in line with or at right angles to the earth rod. Tightening the two nuts presses the conductor between the jaws and seats the earth rod firmly in the jaw facing it: a bolted connection you can open for inspection and measurement, then close again.
We made this clamp for places where the earth conductor must fasten to the top of an earth rod inside an earth inspection pit, or to a reinforcing bar, whether inside the foundation reinforcement cage before concreting or at a connection point that stays accessible. Because the U-bolt does not rely on a thread, it also fastens onto an unthreaded earth rod, an earth rod whose top was damaged during driving, and ribbed reinforcing bar. The body is brass, and the U-bolt and nuts are stainless steel. Six codes, from UBDV 0906 to UBDV 2012, cover earth rods or reinforcing bars from 9.5 to 20 mm and copper conductor from 6 to 300 mm². If your sizes fall between two codes, our specialists will recommend the right one.
U clamp for copper conductor, earth rod and reinforcing bar
To choose a code, you need just two sizes: the diameter of the earth rod or reinforcing bar and the conductor cross-section.
- Copper conductor to earth rod and reinforcing bar
- Conductor in line or at right angles, through-run or terminating
- Brass body, stainless steel U-bolt
- Conductor from 6 to 300 mm² in six codes
Conductor in line with or at right angles to the earth rod
You fasten the conductor between the two jaws, in line with or at right angles to the earth rod. In the clamp shown in the images and drawings on this page, the middle hole takes an in-line conductor and the cross hole, below the legs of the U-bolt, takes a perpendicular one. The conductor can pass through the clamp and on to the next earth rod, or end in this clamp.
Conductor clamp for reinforcing bar
The U-bolt needs no thread and also fastens around ribbed reinforcing bar. Use it to bond copper earth conductor to the foundation reinforcement before concreting, or to the structural reinforcement at an accessible point.
Material: brass and stainless steel
Body chemical composition test report (PDF)Website membership required · Sign in or joinThe two-jaw body is cast brass, and the U-bolt, nuts and washers are stainless steel.
Six UBDV codes
U clamp datasheet (PDF)You will find the table of codes UBDV 0906 to UBDV 2012 on the technical specifications tab and in the U clamp datasheet.
Advice from KALOT Group specialists
When you enquire, send us the diameter and material of the earth rod or reinforcing bar, the conductor cross-section, the conductor direction (in line or at right angles) and the quantity you need, and our specialists will recommend the right code. For ribbed reinforcing bar, give its nominal diameter.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | Two-jaw U clamp for connecting a conductor to an earth rod or reinforcing bar |
Body (two jaws) | Cast brass |
U-bolt and nuts | Stainless steel |
Fastening parts | U-bolt, two nuts and two flat washers |
Conductor type | Stranded copper conductor |
Earth rod or reinforcing bar diameter | 9.5 to 20 mm (depending on the code) |
Conductor cross-section | 6 to 300 mm² (depending on the code) |
Conductor route | In line with or at right angles to the earth rod; through-run or terminating |
Matching earth rod | Copper, copper-bonded or stainless steel, threaded or unthreaded |
Connection type | Bolted, can be opened and refastened |
Typical installation location | Earth inspection pit; foundation reinforcement before concreting; accessible connection point on structural reinforcement |
Codes | UBDV 0906 to UBDV 2012 (six codes) |
U clamp codes (UBDV)
Code | Earth rod or reinforcing bar diameter (mm) | Conductor cross-section (mm²) |
|---|---|---|
UBDV 0906 | 9.5-12.5 | 6-35 |
UBDV 1406 | 14 | 6-35 |
UBDV 1416 | 14-16 | 16-70 |
UBDV 1435 | 14-20 | 35-150 |
UBDV 2070 | 20 | 70-185 |
UBDV 2012 | 20 | 120-300 |
Diameter is in millimetres and cross-section in square millimetres. Our products improve continuously and the dimensions of some may be updated, so please check the final dimensions with our specialists before you buy.
U clamp dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Two holes for the conductor
In the clamp shown in the image below, the middle hole takes a conductor in line with the earth rod and the cross hole takes one at right angles to it. In this side view, the conductor has passed through the middle hole, and the opening of the cross hole is visible between the two jaws.
Click to view enlarged
U clamp applications
- Connecting bare copper conductor to the top of a copper-bonded earth rod inside a concrete or polyethylene earth inspection pit, where the connection stays accessible for inspection and measurement
- Connecting a conductor to a copper or stainless steel earth rod, an unthreaded earth rod, or an earth rod whose top was damaged during driving
- Bonding foundation reinforcement with copper earth conductor before concreting, or a reinforcing bar at a connection point that stays accessible, for bonding the structure to the earthing system
- Connecting the copper down conductor of a lightning protection system to an earth rod
- Fastening one continuous conductor to several earth rods or reinforcing bars in a row, passing it through each clamp without cutting it
Bonding foundation reinforcement with copper earth conductor using a brass U clamp, before concreting.
Before concreting, tighten the nuts of each clamp firmly and make sure the conductor and reinforcing bar are fully seated in the clamp. If your design calls for covering the connection point, do this before the concrete is poured. After concreting, these connections are no longer accessible.
Installation schematic
Download the execution schematic (PDF)
Connection modes
Download connection modes (PDF)
Conductor in line with the earth rod, through the middle hole:
Conductor at right angles to the earth rod, through the cross hole:
U clamp installation steps
- Choose the clamp code from the code table using the diameter of the earth rod or reinforcing bar and the conductor cross-section; both sizes must fall within the range of the same code.
- Before installation, clean paint, rust, mud and any non-conductive layer from the contact surfaces of the earth rod or reinforcing bar and the conductor.
- Undo the nuts and put the U-bolt around the earth rod or reinforcing bar so that it sits in the shallow seat of the jaw facing it.
- Place the conductor, in line with or at right angles to the earth rod, in the matching hole between the two jaws, and first tighten the nuts by hand.
- Tighten the nuts with a spanner, following the manufacturer's instructions, until the conductor is fully pressed between the two jaws and the clamp sits firmly on the earth rod or reinforcing bar.
- Check that the conductor is seated all the way into the hole and that the clamp has not damaged the earth rod, reinforcing bar or conductor.
Download the installation steps (PDF)
Installation tools
For installation, one spanner that fits the nuts is enough; this connection needs no heat, electricity or mould.
Inspection and measurement
During periodic inspections, look at the condition of the clamp, U-bolt and conductor inside the earth inspection pit and check for corrosion, movement and looseness. If the connection has come loose, corroded or been damaged, open it, clean the contact surface and fasten it again following the manufacturer's instructions, or replace the clamp. To measure earth termination resistance, open the connection with a spanner so that the earth rod separates from the conductor, then fasten it again after measuring.
Choosing the size and asking for a U clamp price
When you enquire, send us the diameter and material of the earth rod or reinforcing bar, the conductor cross-section, the conductor direction (in line or at right angles) and the quantity you need, and our specialists will recommend the right code. For ribbed reinforcing bar, give its nominal diameter.
Click to view enlarged
Choose this clamp when copper conductor must fasten to an earth rod or reinforcing bar that may not have a thread or a sound end. Examples are ribbed reinforcing bar, an unthreaded earth rod, or an earth rod whose top was damaged during driving. The U-bolt loops around the earth rod or reinforcing bar and does not rely on a thread, so it fastens anywhere along its length, not just at the top of the earth rod. Our brass U clamp is for copper conductor and fastens onto copper, copper-bonded or stainless steel earth rods and onto reinforcing bar. For galvanised conductor or reinforcing bar, we recommend the galvanised U clamp.
Advantages of the brass U clamp
- On ribbed reinforcing bar and unthreaded earth rods: the U-bolt fastens around the earth rod or reinforcing bar and needs no thread or flat end; neither the earth rod nor the conductor is drilled.
- One clamp, several connection modes: conductor in line with or at right angles to the earth rod, through-run or terminating; the conductor's route sets the direction.
- Conductor up to 300 mm²: six codes, for conductor from 6 to 300 mm² and earth rods or reinforcing bars from 9.5 to 20 mm.
- Can be opened and refastened: for inspection, resistance measurement or a change of conductor route, you undo the nuts and fasten them again.
- Stainless steel U-bolt and nuts: we make the body from brass and the U-bolt and nuts from stainless steel; alongside copper and copper alloys, stainless steel is a common material for earthing components.
U clamp or G-type clamp?
Feature | U clamp | G-type clamp |
|---|---|---|
What it connects | Conductor to earth rod or reinforcing bar | Conductor to top of earth rod |
Fastening point | Anywhere along the earth rod or reinforcing bar | Top of the earth rod |
Earth rod diameter (millimetres) | 9.5 to 20 | 14 to 20 |
Conductor cross-section (square millimetres) | 6 to 300 | 16 to 120 |
Fixing method | U-bolt, two jaws, two nuts | One bolt |
Disconnecting the conductor for measurement | By undoing the nuts | By undoing the bolt |
Both clamps make a connection that can be opened and refastened, and they belong at accessible points such as an earth inspection pit. For connections buried in soil, we recommend exothermic welding.
If these conditions apply to you, see these clamps as well
Clamp | When |
|---|---|
Three-piece U clamp for connecting two conductors to earth rod and reinforcing bar | When you fasten two conductors with one clamp to the same earth rod or reinforcing bar. |
When you fasten a conductor of up to 120 mm² on the top of an earth rod with a single bolt. | |
Galvanised U clamp for connecting conductor to earth rod or reinforcing bar | When the conductor or reinforcing bar is galvanised. |
When the conductor is a tape, not a wire. | |
Reinforcing bar bonding plate with conductor for concrete structures | When the reinforcement of a concrete structure needs a brass connection point for the earthing system. |
Compare all our earthing clamps in the "Which clamp should we choose?" table.
The KALOT Group U clamp is designed and made in line with IEC 62561-1, the standard that sets the requirements for lightning protection system connection components, including clamps.
IEC 60364-5-54 accepts connecting an earth conductor to an earth electrode with a suitable clamp or mechanical connector, alongside exothermic welding and compression joints, provided the clamp is installed following the manufacturer's instructions and does not damage the electrode or conductor.
IEC 62305-3 treats clamping as one of the accepted connection methods in a lightning protection system. It also recommends a test joint where the down conductor meets the earthing system, which can be opened with a tool for measurement and stays closed in normal use.
In Iran, Topic 13 of the National Building Regulations places the top of the earth rod inside a covered pit for a simple earth electrode, and accepts its connection to the earth conductor by a dedicated clamp or by welding. The same part requires the clamp, earth rod and conductor materials to be compatible, and connections to be checked for tightness and corrosion during periodic inspections. At the point where the earth conductor meets the electrode, a connecting piece is also provided that can be opened and separated for testing and measurement. The safety code for earthing systems likewise requires the connection material to be compatible with the electrode and conductor. To learn more, see standards for earthing system design and installation.
U clamp for connecting conductor to earth rod and reinforcing bar
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- U clamp for connecting conductor to earth rod (UBDV) dimensional drawing | Codes and dimensions tableLanguage: Persian (opens in a new tab)
- U clamp for connecting conductor to earth rod (UBDV) technical drawingLanguage: Persian (opens in a new tab)
- U clamp installation schematic | Inspection pit and reinforcing barLanguage: Persian (opens in a new tab)
- U clamp connection modes | Conductor in line or perpendicularLanguage: Persian (opens in a new tab)
- U clamp installation stepsLanguage: Persian (opens in a new tab)
Certificates & test reports
- Chemical composition test report for U clamp (U-Bolt) | 2012Persian · 2012-10-31
Frequently Asked Questions
What is a U clamp and what does it do?
The U clamp is a brass part with a U-shaped bolt that fastens copper earth conductor to an earth rod or reinforcing bar. The bolt loops around the earth rod, the conductor sits between the two jaws, and two nuts press it tight. The connection can be opened for inspection.
How do we choose the size of a U clamp (UBDV code)?
For a 20 mm earth rod and a 240 mm² conductor, code UBDV 2012 is the right choice. Find the code in the code table using the diameter of the earth rod or reinforcing bar and the conductor cross-section; both sizes must fall within the range of the same code. For sizes at the limit of a range, our specialists will recommend the right code.
Does the U clamp also fasten onto ribbed reinforcing bar?
Yes. The U-bolt loops around the ribbed reinforcing bar, which sits in the seat of the clamp jaw, and the conductor, in line with or at right angles to the bar, is fastened between the two jaws. You can place this connection inside the foundation reinforcement cage before concreting, or at a point that stays accessible for inspection. Choose the code from the code table using the diameter of the reinforcing bar and the conductor cross-section.
Can the conductor pass through the U clamp, or must it end there?
Both are possible. You can run the conductor through the clamp and on to the next earth rod or reinforcing bar, or end it in this clamp. With a through-run conductor, you connect several earth rods with one continuous conductor, without cutting it.
Should we fasten the conductor in line with the earth rod or at right angles to it?
The conductor's route sets the direction, and the U clamp accepts both. In the model shown in the images and drawings on this page, an in-line conductor passes through the middle hole and a perpendicular conductor through the cross hole, below the legs of the U-bolt. The conductor must sit fully in the hole so that tightening the nuts presses it between the two jaws.
What is the U clamp made of?
The two-jaw body is cast brass, and the U-bolt and nuts are stainless steel. In the chemical composition test of the U clamp body by emission spectrometry (DIN EN 15079), copper is the alloy base, with zinc at 4.6, lead at 4.7 and tin at 1.27 per cent. You will find the report of this test under "Documents and downloads" on this page.
What is the difference between a brass U clamp and a galvanised U clamp?
Our brass U clamp is for copper conductor and for copper, copper-bonded or stainless steel earth rods, while the galvanised U clamp is for galvanised conductor and reinforcing bar. The clamp material must be compatible with the conductor and the earth rod, because galvanised steel in contact with copper may suffer galvanic corrosion.
Should the U clamp connection to the earth rod go inside an earth inspection pit or underground?
This clamp belongs at accessible points, such as a concrete or polyethylene earth inspection pit, where you can see it, open it for measurement and fasten it again. It is also fastened inside foundation concrete, before the pour. Make connections that go directly underground permanent with exothermic welding.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.