Move your pointer over the image to zoom in
Complete Product Overview
Galvanised U clamp for connecting conductor to earth rod or reinforcing bar
Last updated:
The KALOT Group galvanised U clamp, also known in the trade as a galvanised U-clamp, connects a galvanised steel conductor to an earth rod or reinforcing bar. The U-bolt loops around the earth rod or reinforcing bar, and the conductor sits in line with it in the channel of the outer plate. As the two nuts tighten, the conductor is pressed between the channel and the flat plate, and the earth rod or reinforcing bar bears firmly against the flat plate: a bolted connection that can be opened for inspection and measurement and closed again.
The main use of this clamp is in foundation earthing and foundation bonding: with it you connect reinforcing bars to each other and to the earthing system using galvanised round wire or tape. It also works with stainless steel conductors, both wire and tape. The connector material must match the conductor material, and this clamp should not be used next to copper, because contact between zinc and copper destroys the galvanised coating; for copper conductors, we recommend our brass U clamp. The plates are pressed from 2 mm galvanised steel sheet, and the U-bolt and its two nuts are galvanised steel too. Code UBCG 1450 fixes a 50 to 95 mm² conductor onto an earth rod or reinforcing bar of 14 to 34 mm; our specialists are with you for selection and enquiries.
Galvanised U clamp for foundation earthing and reinforcement bonding
To choose this clamp, check three things: the conductor material (galvanised or stainless steel, never copper), its cross-section, and the diameter of the reinforcing bar or earth rod.
- Foundation earthing and bonding
- Galvanised or stainless steel round wire or tape
- Conductor 50 to 95 mm²; reinforcing bar 14 to 34 mm
- Pressed galvanised steel, U-bolt and M6 nuts
Galvanised conductor in line with the earth rod
The galvanised round conductor sits in the channel of the outer plate, in line with the earth rod or reinforcing bar, and the flat plate lies between the conductor and the earth rod. The conductor can run through the clamp to the next earth rod or reinforcing bar, or end in this clamp.
Foundation reinforcement bonding clamp
The U-bolt needs no thread or smooth surface and closes around the reinforcing bar; in foundation earthing, you bond the reinforcing bars to each other and to the earthing system with galvanised round wire or tape.
Material: galvanised steel, matching the conductor
The flat plate and channel plate are pressed from 2 mm galvanised steel sheet, and the U-bolt and two nuts are galvanised steel too. The clamp matches a galvanised conductor, also works with a stainless steel conductor, and must not be placed next to copper.
Code UBCG 1450 and drawings
Galvanised U clamp datasheet (PDF)You will find the dimensions of code UBCG 1450 in the technical specifications tab, on the dimensional drawing and technical drawing, and in the galvanised U clamp datasheet.
Advice from KALOT Group specialists
When you enquire, send us the conductor material (galvanised or stainless steel) and its size (round wire diameter, stranded conductor cross-section or tape dimensions), the diameter and material of the earth rod or reinforcing bar, the connection location and the quantity needed, and our specialists will confirm the right clamp and the price.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | Pressed U clamp for connecting a galvanised conductor to an earth rod or reinforcing bar |
Material | Galvanised steel (plates, U-bolt and nuts) |
Flat plate | 2 mm steel sheet, 60 × 25 mm, with two 8 mm holes |
Channel plate | Pressed 2 mm steel sheet, 60 × 25 mm, with two 8 mm holes, round channel and engraved KALOT |
U-bolt | 6 mm diameter, M6 thread 40 mm long, 35 mm inside diameter, 63.5 mm long |
Nuts | Two M6 hexagon nuts |
Weight | 78 g (complete set) |
Suitable conductor | Galvanised steel round wire (conductor) or tape; stainless steel conductor (wire or tape) |
Do not use with | Copper conductor or copper earth rod |
Round conductor cross-section | 50 to 95 mm² (round wire 8 to 11 mm) |
Suitable tape | Maximum width 30 mm; such as 25 × 3, 30 × 3 and 30 × 3.5 mm |
Earth rod or reinforcing bar diameter | 14 to 34 mm; for ribbed reinforcing bar, the diameter over the ribs (roughly sizes 14 to 28) |
Conductor route | In line with the earth rod or reinforcing bar, in the plate channel; through-run or end connection |
Connection type | Bolted, can be opened and refastened |
Main application | Foundation earthing and bonding, on reinforcing bar |
Other locations | Top of a steel earth rod inside an earth inspection pit |
Code | UBCG 1450 |
Code and dimensions (UBCG)
Code | Earth rod or reinforcing bar diameter (mm) | Conductor cross-section (mm²) | Plate length (mm) | Plate width (mm) | Overall length (mm) |
|---|---|---|---|---|---|
UBCG 1450 | 14-34 | 50-95 | 60 | 25 | 63.5 |
Diameters and dimensions are in millimetres and cross-sections in square millimetres; overall length is the distance from the curve of the U-bolt to the thread ends. Our products are continually improved and some dimensions may be updated; please confirm final dimensions with our specialists before purchase.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Conductor channel
The middle of the outer plate is pressed into a round channel; the channel's outer radius is 9 mm and it stands 7 mm proud of the plate surface. The channel runs across the full width of the plate, and the round conductor sits in it, in line with the earth rod or reinforcing bar; the KALOT name is engraved on this part.
Click to view enlarged
Applications of the galvanised U clamp
- Bonding reinforcing bars in foundation earthing with galvanised round wire or tape
- Connecting structural reinforcement to the earthing system, for bonding the structure to the earthing system
- Connecting a galvanised or stainless steel conductor to the top of a steel earth rod inside an earth inspection pit (inspection chamber)
- Connecting a galvanised steel down conductor of a lightning protection system to an earth rod
- Fixing one continuous conductor to several reinforcing bars or earth rods in a row, running it through the clamp channel without cutting it
Installation schematic
Download the execution schematic (PDF)
Connection modes
Download connection modes (PDF)
Installation steps for the galvanised U clamp
- Choose the clamp by the conductor cross-section and the diameter of the reinforcing bar or earth rod, and make sure the conductor is galvanised or stainless steel and that there is no copper in the connection.
- Before installation, clean paint, rust, mud and concrete slurry from the contact surface of the earth rod or reinforcing bar and the conductor, and do not scrape the zinc coating of the conductor or clamp.
- Remove the nuts, pass the U-bolt around the earth rod or reinforcing bar, and place the flat plate on the U-bolt legs so that it bears against the earth rod or reinforcing bar.
- Lay the conductor on the flat plate in line with the earth rod or reinforcing bar, fit the channel plate so that the conductor sits in its channel, and tighten the nuts by hand first.
- Tighten the nuts with a spanner, following the manufacturer's instructions, until the conductor is pressed between the two plates and the clamp sits firmly on the earth rod or reinforcing bar.
- Check that the conductor sits in the channel across the full width of the plate, that its end projects slightly beyond the edge of the clamp, and that the clamp has not damaged the conductor, earth rod or reinforcing bar.
- If the connection stays inside foundation concrete, check before pouring that the conductor is fixed with two clamps to two reinforcing bars, and photograph the connections so that their location and workmanship stay documented.
Download the installation steps (PDF)
Installation tools
A single spanner the size of the M6 nuts is all you need for installation; this connection requires no heat, electricity, mould or welding.
Inspection and measurement
During periodic inspections, look at the clamp, U-bolt and conductor and check for loosening, movement, damage to the zinc coating and signs of corrosion, such as a white zinc rust layer or red steel rust. If the connection has loosened, corroded or been damaged, open it, clean the contact surface and close it again following the manufacturer's instructions, or replace the clamp. For measuring earth terminal resistance, open the connection with a spanner to separate the conductor from the earth rod, and close it again after the measurement.
Selecting the galvanised U clamp and requesting a price
When you enquire, send us the conductor material (galvanised or stainless steel) and its size (round wire diameter, stranded conductor cross-section or tape dimensions), the diameter and material of the earth rod or reinforcing bar, the connection location and the quantity needed, and our specialists will confirm the right clamp and the price.
Click to view enlarged
Choose this clamp when your earth conductor or bonding conductor is galvanised or stainless steel; its main use is bonding reinforcement in foundation earthing. Galvanised steel conductors are common in earthing and bonding systems in Iran, and their connector must match their material, because in the presence of moisture, contact between zinc and copper or copper alloys such as brass intensifies galvanic corrosion and the zinc coating wears away sooner. That is why we recommend a galvanised clamp for galvanised conductors, and a brass U clamp for copper conductors on copper or copper-bonded earth rods. The U-bolt loops around the earth rod or reinforcing bar and does not rely on a thread, so it can be fixed anywhere along its length, not only at the top of the earth rod. To compare clamp materials, see Earth clamp materials: brass, copper or galvanised.
Advantages of the galvanised U clamp
- Matches the galvanised conductor: the plates, U-bolt and nuts are all galvanised steel, so no pairing of galvanised parts with brass or copper arises at the galvanised conductor connection.
- No threading and no drilling: the U-bolt loops around the earth rod or reinforcing bar; it needs no thread, and the earth rod, reinforcing bar and conductor are not drilled.
- Installed with one spanner, no welding: you tighten the two M6 nuts with one spanner; the connection needs no heat, electricity, mould or welding on the reinforcing bar.
- Can be opened and closed: for inspection, earth terminal resistance measurement or rerouting the conductor, you undo the nuts and tighten them again.
- Sized for common steel conductors: the 50 to 95 mm² range starts from the minimum cross-section that electrical installation standards set for a steel earth conductor.
- Complete dimensional drawing: the dimensions of the plates, channel and U-bolt are at your disposal on the dimensional drawing, technical drawing and datasheet on this page, as PDF files.
Galvanised U clamp, brass U clamp or galvanised four-way clamp?
Feature | galvanised U clamp | Brass U clamp | Galvanised four-way clamp |
|---|---|---|---|
Main application | Foundation earthing and bonding | Copper conductor to earth rod and reinforcing bar | Branches and crossings of galvanised conductor |
What it connects | Galvanised or stainless steel round wire or tape to reinforcing bar or earth rod | Copper conductor to earth rod or structural reinforcing bar | Galvanised conductor to galvanised conductor |
Material | Galvanised steel | Brass body, stainless steel U-bolt and nuts | Galvanised steel |
Conductor cross-section (mm²) | 50 to 95 | 6 to 300 | 50 to 95 |
Earth rod or reinforcing bar diameter (mm) | 14 to 34 | 9.5 to 20 | Dedicated to conductor-to-conductor connections |
Conductor route | In line with the earth rod or reinforcing bar | In line with or perpendicular to the earth rod | Three-way or four-way, for branches and crossings |
The galvanised U clamp and brass U clamp both make a bolted connection. The galvanised U clamp is used mostly in foundation earthing and bonding, on structural reinforcing bar, and the brass U clamp is for copper conductors; do not use one in place of the other. For connections buried in soil, we recommend exothermic welding.
If these conditions apply to you, see these clamps as well
Clamp | When |
|---|---|
U clamp for connecting conductor to earth rod and reinforcing bar (brass) | When you fix a copper conductor to a copper or copper-bonded earth rod, or to structural reinforcing bar. |
Galvanised cross clamp for conductor-to-conductor connections | When you connect two or more galvanised conductors at a branch or crossing. |
Galvanised steel round wire for earthing and lightning protection | When you are sourcing the galvanised conductor itself for an earthing system or down conductor. |
When you secure a galvanised round conductor on a wall, facade or parapet. | |
When you bond a conductor to the reinforcement in foundation earthing work, either parallel or crosswise. |
Compare all our earthing clamps in the "Which clamp should we choose?" table.
The KALOT Group galvanised U clamp is designed and manufactured in line with IEC 62561-1, the standard that sets the requirements for connection components of lightning protection systems, including clamps.
Earthing system standards require the connector to be compatible with the material of the conductor and earth electrode, to keep galvanic corrosion to a minimum. IEC 62305-3 counts contact with copper among the factors that destroy galvanised steel, advises avoiding connections between dissimilar metals or protecting the joint, and notes that galvanised steel may corrode in clay or damp soil. The same standard does not consider tying a conductor to reinforcing bar with tie wire suitable for carrying lightning current, prefers a clamped or welded connection, and for connections inside concrete, which cannot be inspected later, recommends two clamps on two reinforcing bars.
IEC 60364-5-54 accepts connecting an earth conductor to an earth electrode with a suitable clamp or mechanical connector, alongside exothermic welding and compression joints, provided the clamp is installed according to the manufacturer's instructions and does not damage the electrode or conductor. In this standard, the minimum cross-section of a steel earth conductor is 50 mm². It also notes that steel, galvanised or not, is well protected against corrosion if it has at least 5 cm of concrete around it, and that a galvanised connection coming out of a foundation earth electrode must not lie in soil.
In Iran, Topic 13 of the National Building Regulations requires galvanic corrosion to be taken into account when dissimilar metals are joined in an earthing system, and the clamp, electrode and conductor materials to be compatible. In this part's metal compatibility table for parts joined in soil, galvanised steel is compatible with galvanised steel, but a smaller galvanised part next to copper is not suitable for bonding. The same part places the top of the earth rod inside a covered inspection pit, accepts connecting it to the earth conductor with a dedicated clamp or a weld, and requires this connection to be openable for testing and to be checked for tightness and corrosion during periodic inspections. The earthing system safety code also requires the connection material to be compatible with the electrode and conductor. To learn more, see Standards for the design and installation of earthing systems.
Galvanised U-bolt clamp, round wire to rebar and earth rod
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Galvanised U clamp dimensional drawing (UBCG 1450)Language: Persian (opens in a new tab)
- Galvanised U clamp technical drawing (UBCG 1450)Language: Persian (opens in a new tab)
- Galvanised U clamp installation schematicLanguage: Persian (opens in a new tab)
- Galvanised U clamp connection modesLanguage: Persian (opens in a new tab)
- Installation steps for the galvanised U clampLanguage: Persian (opens in a new tab)
Frequently Asked Questions
What is a galvanised U clamp (U-clamp) and what does it connect?
The galvanised U clamp is a pressed galvanised steel part that fixes a galvanised round conductor in line with an earth rod or reinforcing bar. The U-bolt loops around the earth rod or reinforcing bar, the conductor sits in the channel of the outer plate, and two nuts press it tight; the connection can be opened for inspection and closed again.
Can I fix a galvanised conductor to an earth rod with a brass U clamp?
No. Do not use galvanised parts alongside copper and brass. The clamp material must match the conductor material, and the zinc coating on a galvanised conductor wears away faster in contact with copper and copper alloys such as brass when moisture is present. Use the galvanised U clamp for galvanised conductors and keep the brass U clamp for copper conductors.
Which conductor, tape and reinforcing bar sizes does the galvanised U clamp suit?
Code UBCG 1450 fixes a galvanised round conductor of 50 to 95 mm², that is round wire of 8 to 11 mm, or galvanised tape up to 30 mm wide, such as 25 × 3 and 30 × 3.5, onto an earth rod or reinforcing bar of 14 to 34 mm. For ribbed reinforcing bar, the diameter over the ribs is what counts; this range covers roughly bar sizes 14 to 28. For example, 10 mm round wire on a size 20 reinforcing bar or on a 16 mm earth rod falls within this range. If your sizes sit at the edge of these ranges or your tape is wider, our specialists will recommend the right clamp.
Does the galvanised U clamp fit ribbed reinforcing bar?
Yes, this is its main use. The U-bolt loops around the reinforcing bar and needs no thread or smooth surface. In foundation earthing and bonding, you connect galvanised round wire or tape to the reinforcing bars with this clamp; to carry lightning current, connect the conductor to the reinforcing bar with a clamp or a weld, not with tie wire.
Can the galvanised U clamp also be used with a stainless steel conductor?
Yes, you can also use this clamp with stainless steel wire or tape. The only condition is that there is no copper in the connection.
How does a galvanised conductor or tape sit in this clamp?
The round conductor sits in the round channel of the outer plate, in line with the earth rod or reinforcing bar, and the flat plate lies between the conductor and the earth rod. Position the conductor so it stays inside the channel across the full width of the plate; it can run through the clamp and on to the next earth rod or reinforcing bar. Lay tape flat, in line with the reinforcing bar, between the two plates and between the two legs of the U-bolt; as the nuts tighten, the two plates press the tape between them.
What is the code of the galvanised U clamp, and what details should we send for a price enquiry?
The code of this clamp is UBCG 1450: UBCG stands for galvanised U clamp, 14 is the minimum diameter of the earth rod or reinforcing bar, and 50 is the minimum conductor cross-section. For an enquiry, send us the conductor material and cross-section, the diameter and material of the earth rod or reinforcing bar, the connection location and the quantity needed, and our specialists will confirm the right clamp and the price.
Where should the galvanised U clamp be used: in foundation concrete or underground?
This clamp belongs mainly on reinforcing bar in foundation earthing and bonding, and at accessible points such as the top of an earth rod inside an earth inspection pit. When the connection stays inside foundation concrete, fix the conductor with two clamps on two separate reinforcing bars, because a connection under concrete can no longer be inspected, and let at least 5 cm of concrete surround the clamp and conductor. Do not take a galvanised conductor straight from concrete into soil, and do not place a galvanised connection in soil or at the boundary between concrete and soil; make connections that go underground permanent with exothermic welding. In coastal areas or saline soil and water, consult our specialists before choosing galvanised parts.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.