Complete Product Overview
Galvanised cross clamp for conductor-to-conductor connections (round wire to round wire)
Last updated:
The KALOT Group galvanised cross clamp, also called a "galvanised four-way clamp" or "cross clamp", joins two galvanised steel round wires or galvanised conductors where they cross, in an X shape. It is made of two identical pressed plates, each with a diagonal round groove. The plates fit together with their grooves at right angles, each conductor sits in the groove of one plate, and two M6 bolts press the conductors together at the crossing point.
Its main use is in foundation earthing: it joins the crossings and branches of the galvanised round wire in a foundation earth electrode with a firm bolted connection before the concrete is poured. For carrying lightning current, this connection replaces tying with reinforcement tie wire. It is also used at the crossings of roof air termination networks built with galvanised round wire. The clamp is the same material as galvanised conductors and is not used next to copper; for copper conductors we recommend our four-way conductor-to-conductor clamp. Code GLSC 5095 clamps round conductors from 50 to 95 mm², and our specialists are at your side for selection and enquiries.
Galvanised cross clamp for foundation earthing round wire crossings
To choose this clamp, check three things: the material of both conductors (galvanised, never copper), their cross-section or diameter, and the joint type (four-way or three-way).
- Foundation earth electrode crossings and branches
- Two round galvanised conductors, 50 to 95 mm²
- Four-way or three-way joint, at 90 degrees
- Two pressed galvanised steel plates, two M6 bolts
Two diagonal grooves, 90-degree crossing
Each plate has a round groove running across its width at 45 degrees. The two plates close over the crossing with their grooves at right angles, and each conductor sits in its own groove, so the two conductors are pressed together at the centre of the clamp.
Connecting foundation earthing crossings
In a foundation earth electrode, galvanised round wire runs as a closed ring and mesh through the building's footing. This clamp connects its crossings and branches before the concrete is poured.
Material: galvanised steel, matching the round wire
The two plates are pressed from 2 mm galvanised steel sheet, and the bolts and nuts are also galvanised steel. The clamp is the same material as galvanised round wire and conductors, and must not be placed next to copper.
Code GLSC 5095 and drawings
Galvanised cross clamp datasheet (PDF)You will find the dimensions of code GLSC 5095 in the technical specifications tab, in the dimensional drawing, technical drawing and exploded view, and in the galvanised cross clamp datasheet.
Advice from KALOT Group specialists
When you enquire, send us the material and size of both conductors (round wire diameter or stranded conductor cross-section), the joint type (four-way or three-way), the installation location and the quantity needed, and our specialists will confirm the right clamp and the price.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | Two-plate pressed cross clamp for an X connection of two round conductors |
Material | Galvanised steel (plates, bolts and nuts) |
Plates | Two identical plates of 2 mm steel sheet, 80 × 25 mm, rounded corners, with a diagonal round groove and KALOT engraving |
Groove | 45 degrees to the plate length; 9 mm outer radius; projects 7 mm from the plate surface |
Holes | Two 8 mm holes in each plate, 56 mm centre to centre |
Bolts | Two M6 hexagon bolts, 25 mm long |
Nuts | Two M6 hexagon nuts |
Weight | 83 g (complete set) |
Suitable conductor | Galvanised steel round wire or stranded conductor |
Conductor cross-section | 50 to 95 mm² (round wire 8 to 11 mm) |
Joint arrangement | X crossing at 90 degrees; four-way (both conductors run through) or three-way (branch) |
Do not use with | Copper conductor |
Connection type | Bolted |
Main application | Crossings and branches of foundation earth electrodes |
Other locations | Crossings of roof air termination networks and galvanised bonding conductors |
Code | GLSC 5095 |
Code and dimensions (GLSC)
Code | Conductor cross-section (mm²) | Round wire diameter (mm) | Plate length (mm) | Plate width (mm) | Weight (g) |
|---|---|---|---|---|---|
GLSC 5095 | 50-95 | 8-11 | 80 | 25 | 83 |
Diameters and dimensions are in millimetres and cross-sections in square millimetres; the weight is for the complete set (two plates, two bolts and two nuts). Our products are continually improved and some dimensions may be updated, so please confirm final dimensions with our specialists before you buy.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Exploded view
Download the exploded view (PDF)
Conductor grooves
Each plate has a pressed round groove at its centre, running at 45 degrees from one edge of the plate to the other. The groove has a 9 mm outer radius and projects 7 mm from the plate surface. When the two plates are fitted together, the grooves lie at right angles and each conductor sits in one of them. The KALOT name is engraved on the groove.
Click to view enlarged
Applications of the galvanised cross clamp
- Foundation earthing: connecting the galvanised round wire crossings of the foundation earth electrode, in the closed ring and mesh inside the footing, before the concrete is poured
- A three-way branch from the foundation electrode, to bring a conductor to a connection terminal or bonding bar
- Connecting galvanised bonding conductors at crossings, for bonding the structure to the earthing system
- Crossings of roof air termination networks and down conductors built with galvanised steel round wire
- Connecting two round galvanised conductors of different sizes within the 50 to 95 mm² range, such as round wire and stranded conductor
Installation schematic
Download the execution schematic (PDF)
Connection modes
Download connection modes (PDF)
Installation steps for the galvanised cross clamp
- Choose the clamp by the cross-section of both conductors, and make sure both are galvanised and that no copper is involved in this joint.
- Before installation, clean mud, cement slurry, rust and paint from the crossing point of both conductors, without scraping the zinc coating of the conductors or the clamp.
- Pass the bolts through the holes of the lower plate and place the plate under the crossing so the lower conductor sits in its groove.
- Lay the second conductor across the first at right angles, then fit the upper plate on the bolts so its groove sits over the second conductor.
- Tighten the nuts by hand first, then evenly with a spanner according to the manufacturer's instructions, so both conductors are pressed into the grooves and against each other.
- Check that both conductors sit along the full length of the grooves, that the crossing is still at right angles and that the clamp has not damaged the conductors.
- In a foundation, make sure before pouring that at least 5 cm of concrete will surround the clamp and conductors, and photograph the crossings so their location and workmanship stay on record.
Download the installation steps (PDF)
Installation tools
Two size 10 spanners are all you need for installation: one to hold the bolt head and one for the nut. This connection needs no welding, heat or electricity.
Checks and inspection
Crossings that stay in the concrete can no longer be seen once it is poured, so check and document all of them beforehand, and afterwards measure the continuity of the foundation electrode from the terminals that come out of the concrete. At accessible crossings, such as on a roof network, check for looseness, zinc coating damage and signs of corrosion during periodic inspections, and if needed open, clean and retighten the connection according to the manufacturer's instructions. For measuring earth termination resistance, use the measuring points of the earthing system.
Choosing and enquiring about the galvanised cross clamp
When you enquire, send us the material and size of both conductors (round wire diameter or stranded conductor cross-section), the joint type (four-way or three-way), the installation location and the quantity needed, and our specialists will confirm the right clamp and the price.
Click to view enlarged
Choose this clamp when two round galvanised conductors cross or branch from each other; it is used most in foundation earth electrodes. Lightning protection standards do not consider tying conductors with reinforcement tie wire suitable for carrying lightning current and prefer a clamped or welded connection; the cross clamp provides this with no welding or heat next to the reinforcing bars. The connector material must also suit the conductor material, because in the presence of moisture contact between zinc and copper or copper alloys intensifies galvanic corrosion. That is why we recommend the galvanised cross clamp for galvanised round wire, the four-way conductor-to-conductor clamp for copper conductors, and the multi-purpose stainless steel four-way clamp for stainless steel conductors. To compare clamp materials, see Earth clamp materials: brass, copper or galvanised.
Advantages of the galvanised cross clamp
- Same material as galvanised round wire: the plates, bolts and nuts are all galvanised steel, so the crossing does not pair galvanised steel with brass or copper.
- 90-degree crossing: the two diagonal grooves in the plates hold the conductors at right angles, each in its own groove.
- No welding or heat: you tighten the two M6 bolts with a spanner; next to the reinforcing bars there is no need for welding, a mould or electricity.
- Four-way or three-way with one clamp: both conductors can pass through the clamp, or one can end in it; the through-run conductor is not cut.
- Fits common round wire sizes: the 50 to 95 mm² range covers the 8 and 10 mm round wire common in foundation earthing and lightning protection.
- Complete drawings: the dimensions of the plate, groove and components are at hand in the dimensional drawing, technical drawing, exploded view and datasheet on this page, as PDF files.
Galvanised cross clamp, four-way conductor-to-conductor clamp or stainless steel four-way clamp?
Feature | galvanised cross clamp | Four-way conductor-to-conductor clamp | Multi-purpose stainless steel four-way clamp |
|---|---|---|---|
Main application | Foundation earthing round wire crossings | Stranded copper conductor crossings | Conductor and tape crossings with one clamp |
Conductor | Galvanised steel round wire or conductor | Stranded copper conductor | Conductor or tape |
Material | Galvanised steel | Brass body, stainless steel bolts | Stainless steel |
Round conductor cross-section (mm²) | 50 to 95 | 50, 70 or 95 (three models) | 50 and 70 |
Bolts | Two M6 bolts | Four stainless steel bolts | Four M6 bolts |
Arrangement | Four-way or three-way, 90 degrees | Four-way, straight or three-way | Conductor to conductor, tape to tape, conductor to tape |
The galvanised cross clamp and the four-way conductor-to-conductor clamp both join two conductors at a crossing. The first is for galvanised round wire and conductors, the second for copper conductors, and they must not be swapped. To connect a galvanised conductor to a reinforcing bar or earth rod, see the galvanised U clamp, and for connections buried in soil we recommend exothermic welding.
If these conditions apply to you, see these clamps as well
Clamp | When |
|---|---|
Galvanised U clamp for connecting conductor to earth rod and reinforcing bar | When you connect galvanised round wire to a reinforcing bar or a steel earth rod. |
When you are sourcing the galvanised conductor itself for a foundation electrode or roof network. | |
When you join two stranded copper conductors at a crossing. | |
Multi-purpose stainless steel four-way clamp for connecting conductor and tape | When the conductors are stainless steel, or when you connect conductor and tape. |
When you bond the conductor to the reinforcing bars in foundation earthing work. |
Compare all our earthing clamps in the "Which clamp should we choose?" table.
We design and manufacture the KALOT Group galvanised cross clamp to IEC 62561-1, the standard that sets the requirements for lightning protection connection components, including clamps that join conductors crossing or parallel to each other.
IEC 62305-3 treats the foundation earth electrode and the conductor network as parts of the lightning protection system, does not consider tying conductors with reinforcement tie wire suitable for carrying lightning current, and prefers a clamped or welded connection. The same standard notes that contact with copper destroys galvanised steel, and that an electrode covered by at least 5 cm of concrete is well protected against corrosion.
IEC 60364-5-54 accepts connecting earth electrode sections with a clamp or mechanical connector, alongside exothermic welding and compression joints, and does not consider wire wrapping alone sufficient. In this standard, steel round wire in concrete, bare or galvanised, has a diameter of at least 10 mm, and a galvanised connection coming out of the foundation electrode must not lie in soil.
In Iran, Topic 13 of the National Building Regulations counts the steel reinforcing bars in reinforced concrete among the types of earth electrode, requires connections to be reliable and firm, and requires connector materials to suit conductor materials so that galvanic corrosion is reduced. The Earthing System Safety Code also accepts reinforced foundation concrete as an earth electrode under certain conditions and requires the connection material to be compatible with the electrode and conductor. To learn more, see Standards for the design and installation of earthing systems.
Galvanised cross clamp, round wire to round wire
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Galvanised cross clamp dimensional drawing (GLSC 5095)Language: Persian (opens in a new tab)
- Galvanised cross clamp technical drawing (GLSC 5095)Language: Persian (opens in a new tab)
- Galvanised cross clamp exploded view (GLSC 5095)Language: Persian (opens in a new tab)
- Galvanised cross clamp installation schematicLanguage: Persian (opens in a new tab)
- Galvanised cross clamp connection modesLanguage: Persian (opens in a new tab)
- Installation steps for the galvanised cross clampLanguage: Persian (opens in a new tab)
Frequently Asked Questions
What is a galvanised cross clamp and what is it used for?
A galvanised cross clamp is a pressed galvanised steel part that joins two round galvanised conductors where they cross, in an X shape. Two identical plates with diagonal grooves fit over the crossing, and two M6 bolts press the conductors together. It is used most often at the crossings and branches of galvanised round wire in foundation earthing.
Does a galvanised cross clamp differ from what is sold as a galvanised four-way clamp or a cross clamp?
There is no difference: these are all names for the same part. On the market it is also called a "galvanised four-way clamp", a "cross clamp" or a "round wire to round wire clamp", because it joins two round conductors in a four-way or three-way arrangement.
Which round wire and conductor sizes does the galvanised cross clamp suit?
Code GLSC 5095 clamps round galvanised conductors from 50 to 95 mm²: that means 8 to 11 mm round wire, or 50, 70 and 95 mm² stranded conductor. Both the 10 mm round wire common in foundation electrodes and the 8 mm round wire used on roof networks fall within this range. If your conductor sizes sit at the edge of the range, our specialists will recommend the right clamp.
Can I join two conductors of different sizes with one cross clamp?
Yes, as long as both conductors are round and galvanised and each has a cross-section between 50 and 95 mm²: for example a 10 mm round wire with a 95 mm² stranded conductor. Each conductor sits in the groove of its own plate, and the two plates press them together.
Is the galvanised cross clamp suitable for copper conductors too?
No. Do not use galvanised parts next to copper. In the presence of moisture, contact between zinc and copper uses up the galvanised coating faster. For stranded copper conductors, use our four-way conductor-to-conductor clamp.
Can a galvanised cross clamp be cast inside foundation concrete?
Yes, that is its main use. Before pouring concrete, check all the crossings, photograph them and make sure at least 5 cm of concrete surrounds the clamp and conductors. Do not leave a galvanised connection in soil or at the boundary between concrete and soil; make connections that go underground permanent with exothermic welding. In coastal areas, or with saline soil and water, talk to our specialists before choosing galvanised parts.
Why not tie foundation round wire crossings with reinforcement tie wire?
Reinforcement tie wire is useful for holding the round wire in place, but lightning protection standards do not consider it suitable for carrying lightning current and prefer a clamped or welded connection. The cross clamp makes a firm bolted connection with no welding or heat next to the reinforcing bars.
What is the code of the galvanised cross clamp, and what should we send for a price enquiry?
The code for this clamp is GLSC 5095, and it clamps round conductors from 50 to 95 mm². When you enquire, send us the material and size of both conductors (round wire diameter or stranded conductor cross-section), the joint type (four-way or three-way), the installation location and the quantity needed, and our specialists will confirm the right clamp and the price.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.