Move your pointer over the image to zoom in
Complete Product Overview
Galvanised clamp for connecting tape to earth rod and round wire
Last updated:
The galvanised tape-to-earth rod clamp from KALOT Group fixes galvanised steel tape to a round steel conductor in foundation earthing and bonding, before the pour: galvanised round wire, reinforcing bar or a stainless steel earth rod. The round conductor is held in the saddle of the upper plate and the tape between two flat plates. Both pass between the two bolts, parallel or at a slight angle, and the tape is neither drilled nor cut.
The clamp is the same material as galvanised tape and round wire and also works next to stainless steel conductors, but not next to copper, since contact with copper can destroy the zinc coating. For copper tape on a copper earth rod, we recommend our brass A-type clamp. The clamp with code TRCG 3016 fixes tape up to 30 mm wide to 8 and 10 mm round wire and to reinforcing bar or an earth rod up to 16 mm. Our specialists are with you in choosing the size and requesting a quote.
Connecting galvanised tape to reinforcing bar, round wire and earth rods
To choose this clamp, weigh three things: the material of both conductors (galvanised or stainless steel), the width and thickness of the tape and diameter of the round conductor, and the location of the joint (inside concrete or in air).
- Foundation earthing and bonding, inside concrete
- Tape up to 30 mm to round conductor 8 to 16 mm
- Round wire, reinforcing bar or earth rod; parallel or at a slight angle
- Three galvanised steel plates, two M8 bolts
Tape between flat plates, round conductor in the saddle
Each conductor has its own place: the round conductor is held in the saddle and the tape between two flat plates, while the middle flat plate keeps them apart. You will find the shape and order of the plates in the technical specifications tab.
Connecting tape to round wire and reinforcing bar in foundation earthing
In a foundation earth electrode, galvanised tape runs as a closed ring in the building's foundations. Before the pour, this clamp connects the tape to the reinforcing bars and to the round wires that lead to the down conductors and connection terminals.
Material: galvanised steel, matching the tape and round wire
The plates, bolts and nuts are all galvanised steel. The clamp matches galvanised tape and round wire, and also works with reinforcing bar and stainless steel conductors.
Code TRCG 3016 and drawings
Galvanised tape-to-earth rod clamp datasheet (PDF)The dimensional drawing and technical drawing show the tape and round conductor range, the execution schematic shows where the clamp goes in the foundation, and the installation steps show the sequence of work. You have them all in the technical specifications tab and as PDF files, alongside this clamp's datasheet.
Advice from KALOT Group specialists
Send us the tape and round conductor sizes and the joint location, and our specialists will tell you the right clamp and the price.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | Three-plate bolted clamp for connecting tape to a round conductor |
Material | Galvanised steel (plates, bolts and nuts) |
Plates | One saddle plate for the round conductor and two flat plates for the tape, all three of one design with two bolt holes |
Saddle | Round and straight, perpendicular to the plate length, across its full width and between the two holes |
Bolts | Two M8 hexagon bolts, property class 8.8 |
Nuts | Two M8 hexagon nuts |
Suitable tape | Width 25 to 30 and thickness 3 to 3.5 mm: 25 × 3 (for tape inside concrete), 30 × 3 and 30 × 3.5 |
Suitable round conductor | 8 and 10 mm galvanised round wire, reinforcing bar up to 16 mm in diameter over the ribs, and 16 mm stainless steel earth rod |
Conductor materials | Galvanised or stainless steel tape; galvanised steel round wire, reinforcing bar or stainless steel earth rod |
Arrangement of the two conductors | Parallel or at a slight angle to each other; both pass between the two bolts |
Conductor route | Through-run or terminating; the tape is neither drilled nor cut |
Do not use with | Copper or copper-coated conductor, tape or earth rod |
Connection type | Bolted, can be opened and refastened |
Main application | Foundation earthing and bonding, inside concrete |
Other locations | In air, where galvanised tape and round wire meet |
Code | TRCG 3016 |
Code and size range (TRCG)
Code | Tape width (mm) | Tape thickness (mm) | Round conductor diameter (mm) | Bolts and nuts | Number of plates |
|---|---|---|---|---|---|
TRCG 3016 | 25-30 | 3-3.5 | 8-16 | 2 × M8 | 3 |
Diameters and dimensions are in millimetres, and ribbed reinforcing bar is measured over the ribs. Dimensions may change without prior notice; send us your project's tape and round conductor sizes so that our specialists can confirm the right clamp. Our products are continually improved and some dimensions may be updated, so please check the final dimensions with our specialists before you buy.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Exploded view
Download the exploded view (PDF)
Saddle plate and flat plates
At its centre, the saddle plate has a round saddle formed straight and perpendicular to the plate length, across its full width and between the two bolt holes; the round conductor sits in this saddle. The two flat plates share the saddle plate's design and size, and the tape goes between them. Working from the bolt head side, the parts assemble in this order: saddle plate, round conductor, middle flat plate, tape, outer flat plate and nuts. The middle flat plate is always between the two conductors, and both conductors pass through the space between the two bolts.
Click to view enlarged
Applications of the galvanised tape-to-earth rod clamp
- Foundation earthing: connecting the galvanised tape of the foundation earth electrode to the foundation reinforcing bars before the pour; for joints that stay in concrete, fix the tape with two clamps to two separate bars
- Electrode ring and mesh: connecting tape to 10 mm galvanised round wire where part of the foundation electrode ring or mesh has been built with round wire
- Branch to test joint and down conductor: connecting the foundation electrode tape to a branch that rises inside a concrete column or wall and reaches the test joint, the down conductor of the lightning protection system or the main earth bar. Bring a galvanised branch out into the air on the surface of the column or wall or inside the building, not through soil. Wherever the branch route has to pass through soil, build it in stainless steel and make the change of material inside the concrete with this same clamp
- Passing into soil with stainless steel: connecting galvanised tape inside the concrete to a 16 mm stainless steel earth rod, also inside the concrete, so that only stainless steel passes from concrete to soil. This is a joint between two dissimilar metals, so cover it fully with a moisture-proof compound or tape before the pour
- Insulated or watertight foundations: when damp-proofing, bituminous sheet or thermal insulation is laid under and around the foundation, or the concrete is watertight, contact between concrete and soil is limited and the galvanised tape in the concrete mostly serves for bonding. Build the earth electrode outside the insulation, in soil and in stainless steel, and fix its stainless steel branch to the tape inside the concrete with this clamp. The branch passes through the insulation according to the designer's waterproofing details
- Structural bonding: connecting galvanised bonding tape to the structural reinforcement, for bonding the structure to the earthing system
- In air, on the roof or facade: connecting galvanised tape to the galvanised round wire of the air termination network or down conductor, where both conductors are galvanised
Installation schematic
Download the execution schematic (PDF)
Connection modes: parallel and at a slight angle
Download connection modes (PDF)
Installation steps for the galvanised tape-to-earth rod clamp
- Check the conductor materials and sizes: the tape must be galvanised or stainless steel, the round conductor galvanised round wire, reinforcing bar or a stainless steel earth rod, and both sizes within the clamp's range. If you are fitting the clamp to an existing lightning protection system on a roof or facade, do not work during a thunderstorm, and leave the job to an installer familiar with earthing and lightning protection systems.
- Choose the clamp position before installation: fit this clamp only where tape meets a round conductor, and bend the tape at the corners of the ring rather than cutting and rejoining it. In a reinforcement cage, position the clamp between two transverse bars so that the bolts and plates do not touch another reinforcing bar, and in a strip foundation fix the tape to the longitudinal reinforcing bar running in line with it.
- Secure the tape with spacers or tie wire so that it does not lie on the formwork floor or blinding concrete and the concrete can fill around the tape and clamp from every side. Setting the tape on edge also helps with this.
- Clean the joint area of mud, cement slurry, rust, paint and grease with a cloth or soft brush. Do not scrape the zinc coating of the tape, round wire or clamp.
- Undo the nuts and slide the two flat plates off the bolts. The bolts stay in the saddle plate.
- Place the saddle plate on the round conductor so that the conductor sits in the saddle with a bolt on either side, then fit the middle flat plate onto the bolts from the other side of the conductor. If the round conductor is an earth rod, put the saddle on its smooth body, not on the driving end or the joint between two earth rod sections.
- Lay the tape on the middle flat plate, between the two bolts and parallel or at a slight angle to the round conductor. Fit the outer flat plate onto the bolts and run the nuts on by hand.
- Line up the plates and tighten the nuts with a spanner, evenly and in turn, following the manufacturer's instructions. Then check that the round conductor sits in the saddle across the full width of the plate and that the tape lies flat between the plates. If the conductor ends at this clamp, leave at least 2 cm of it projecting beyond the clamp edge.
- Before the pour, measure the concrete cover from the nearest point of the clamp, meaning the bolt heads and nuts, to the floor and side of the formwork: at least 5 cm of structural concrete, which does not include blinding concrete. Make joints that stay in concrete with two clamps on two separate reinforcing bars, and photograph every joint.
Download the installation steps (PDF)
Installation tools
Two spanners matching the bolt head and nut are enough for installation: one holds the bolt head while the other turns the nut. This joint needs no welding, heat, electricity or drilling.
Pre-pour checks and inspection
Clamps inside concrete cannot be seen after the pour, so check every joint one by one beforehand, and once more just before the pour, when the steel fixers and formwork crews have finished. Rule out these mistakes: a round conductor outside the saddle or tape skewed between the plates; a loose nut; a bolt head or nut less than 5 cm from the floor or side of the formwork; tape lying on the floor; a connection to the reinforcement with only one clamp; tape running rigidly across a structural expansion joint, since the designer provides separately for connecting the two sides of the joint; and a galvanised conductor passing from concrete into soil. Do not use the clamp to carry the weight or tension of the conductors. Mark the tape route so that it is not mistaken for reinforcing bar, and mark and protect the end of every branch leaving the concrete until the work is finished, so that it is not hidden under concrete or finishes or cut off. Photograph the whole route and every joint, with the grid number or a label visible beside the joint. Measure electrical continuity with an ohmmeter between the main earth bar terminal and all other terminals, and record the results with the drawing and photographs. Even if the steel fixing crew fitted the clamps, checking and documentation rest with the electrical or lightning protection specialist. For terminal details, see the terminals and access for testing section of our foundation earthing article. During periodic inspections, check accessible joints in air for tight nuts, a sound zinc coating and any sign of corrosion, such as a white layer of zinc oxide (white rust) or red steel rust. Undo a loose or corroded joint, clean the contact surface and retighten it following the manufacturer's instructions. To measure earth termination resistance, use the terminals that come out of the foundation concrete.
Choosing the galvanised tape-to-earth rod clamp and requesting a quote
To estimate the quantity, count on the foundation earthing drawing every point where tape connects to reinforcement (two clamps for a joint that stays in concrete), every branch and every stainless steel earth rod, and keep a few extra clamps for site changes. When requesting a quote, send us the material and size of the tape (width × thickness), the type, material and diameter of the round conductor (round wire, reinforcing bar or earth rod), the arrangement of the two conductors (parallel or at an angle), the location of the joint (inside concrete or in air), the quantity and, if you have it, the foundation earthing drawing. Our specialists will tell you the right clamp and its price.
Click to view enlarged
Wherever galvanised tape meets a round steel conductor in an earthing or bonding system, this clamp is made for that joint, mostly inside foundation concrete. The tape is gripped between two flat plates and is not drilled, so its cross-section stays complete. The connection is bolted and needs no welding on reinforcing bar, which would require the structural designer's agreement. Its material is also compatible with galvanised and stainless steel conductors. Our recommendation: this clamp for galvanised tape; our brass clamps for copper systems; and the multi-purpose stainless steel four-way clamp for stainless steel conductor and tape joined at right angles. We compare the materials side by side in the section earth clamp material: brass, copper or galvanised.
Advantages of this clamp for connecting tape to reinforcing bar and round wire
- Can be checked before the pour: you see the joint before the pour, tighten it and photograph it, and if it is in the wrong place, it can be undone and moved.
- No drilling or welding: the tape is not drilled and its cross-section stays intact. The joint is made with two bolts and two spanners, with no need for welding, heat or electricity.
- No cutting of a through-run conductor: the tape and round conductor can pass through the clamp and continue, or one of them can end at this clamp. Both pass between the two bolts, parallel or at a slight angle.
- One clamp for round wire, reinforcing bar and earth rod: the same saddle takes 8 and 10 mm galvanised round wire, reinforcing bar and a 16 mm stainless steel earth rod, and the tape always stays between the flat plates.
- Same material as galvanised tape and round wire: the plates, bolts and nuts are all galvanised steel, matching galvanised tape and round wire.
- Change of material inside concrete: it fixes galvanised tape inside the concrete to a stainless steel earth rod or branch, so that only stainless steel passes from concrete to soil. This is the pattern earthing standards recommend for foundation electrodes.
Comparison with the galvanised U clamp and the brass A-type clamp
Feature | This clamp | galvanised U clamp | Brass A-type clamp |
|---|---|---|---|
What it connects | Tape to round wire, reinforcing bar or earth rod | Round wire or tape to reinforcing bar or earth rod | Copper tape to earth rod |
Material | Galvanised steel | Galvanised steel | Brass ring, stainless steel bolt |
Tape (mm) | Width 25 to 30, thickness 3 to 3.5 | Maximum width 30 | Copper, width 25, 30 or 50 (three models) |
Round conductor (mm) | 8 to 16 | Earth rod or reinforcing bar 14 to 34 | Earth rod up to 16, 20 or 25 (three models) |
Structure | Three plates and two M8 bolts | U bolt, two plates and two M6 nuts | One piece and one bolt |
Main joint location | Inside foundation concrete or in air | On foundation reinforcing bar | Head of the earth rod, inside the inspection pit |
For a quick choice: galvanised tape to round wire, reinforcing bar or earth rod up to 16 mm, parallel or at a slight angle: this clamp. Reinforcing bar or earth rod 14 to 34 mm: the galvanised U clamp. From 14 to 16 mm, as with a 16 earth rod, both clamps work and our specialists will recommend one according to the joint location. Two galvanised round wires crossing at right angles: the galvanised cross clamp. Stainless steel conductor and tape joined at right angles: the multi-purpose stainless steel four-way clamp. Bonding large foundation reinforcing bars: the foundation earthing and bonding clamp. Copper conductor: our brass clamps, such as the A-type clamp. Exothermic welding creates a permanent, one-piece joint and needs a mould, powder and a trained installer. Make any joint buried directly in soil, or one the designer wants welded and permanent, with exothermic welding. Inside concrete, this bolted clamp makes the same connection without a mould or heat, and can be seen and checked before the pour.
If these conditions apply to you, see these clamps as well
Clamp | When |
|---|---|
Galvanised U clamp for connecting conductor to earth rod and reinforcing bar | When you are fixing a conductor to a larger reinforcing bar or earth rod, 14 to 34 mm. |
Galvanised cross clamp for conductor-to-conductor connections | When you are connecting two galvanised round wires at a crossing or branch. |
When you are sourcing the galvanised round conductor itself for a down conductor, a roof network or a connection to the foundation. | |
When the earthing system has to pass from foundation concrete into soil. | |
When you are bonding a conductor to large foundation reinforcing bars. | |
Multi-purpose stainless steel four-way clamp for connecting conductor and tape | When you are connecting stainless steel conductor and tape at right angles. |
Compare all our earthing clamps in the "Which clamp should we choose?" table.
KALOT Group's galvanised tape-to-earth rod clamp is designed and made in accordance with IEC 62561-1, the standard that sets the requirements for lightning protection system connection components, including bolted clamps.
In its examples, IEC 62305-3 shows a clamp connecting solid tape to a reinforcing bar. For a clamped connection to reinforcement, which can no longer be seen after the pour, it advises two clamps on two separate reinforcing bars, and it does not consider a connection made only with tie wire sufficient for lightning current. According to the same standard, galvanised steel tape inside concrete may be connected directly to the reinforcing bars, and an electrode outside the concrete in soil is better made of stainless steel or copper. Joints between dissimilar metals should be avoided or protected, and an electrode covered by at least 5 cm of suitable concrete is adequately protected against corrosion.
IEC 60364-5-54 accepts a clamp or mechanical connector, alongside exothermic welding and compression joints, for connecting earth electrodes and earthing conductors, provided it is installed according to the manufacturer's instructions and does not damage the electrode or conductor. This standard's minimum for steel inside concrete is tape with a 75 mm² cross-section and 3 mm thickness and round wire of 10 mm diameter, so 25 × 3 tape is adequate only inside concrete. The same standard recommends setting electrode tape on edge so that no void is left beneath it, letting only stainless steel pass directly from foundation concrete into soil, and keeping joints between two dissimilar metals out of contact with soil.
Part Thirteen of the Iranian National Building Regulations counts tape among the types of horizontal electrode and also treats steel reinforcing bars inside reinforced concrete as an earth electrode. For steel inside concrete it gives the same minimum of 75 mm² tape with 3 mm thickness and 10 mm round wire. In this part's table of metal compatibility, a small galvanised part on stainless steel is not suitable for a joint in soil. The safety code for earthing systems requires the connection part's material to be compatible with the electrode and conductor, and if tape is drilled for a bolt, it limits the diameter of that bolt; with this clamp, the tape is not drilled. We give a fuller review of these regulations in our article on standards for the design and installation of earthing systems.
Galvanised clamp, tape to earth rod and round wire
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Dimensional drawing of the galvanised clamp for tape to earth rod and round wireLanguage: Persian (opens in a new tab)
- Technical drawing of the galvanised clamp for tape to earth rod and round wireLanguage: Persian (opens in a new tab)
- Exploded view of the galvanised clamp for tape to earth rod and round wireLanguage: Persian (opens in a new tab)
- Installation schematic of the galvanised clamp for tape to earth rod and round wireLanguage: Persian (opens in a new tab)
- Connection modes of the galvanised clamp for tape to earth rod and round wireLanguage: Persian (opens in a new tab)
- Installation steps for the galvanised clamp for tape to earth rod and round wireLanguage: Persian (opens in a new tab)
Frequently Asked Questions
What is a galvanised tape-to-earth rod clamp (galvanised tape clamp), and what does it connect?
The galvanised tape-to-earth rod clamp is a bolted fitting in galvanised steel that joins steel tape to a round steel conductor: galvanised round wire, reinforcing bar or a stainless steel earth rod. The round conductor is held in the saddle of the upper plate and the tape between two flat plates. Its main use is foundation earthing and bonding, inside the concrete and fitted before the pour.
How do we connect galvanised tape to round wire?
With this very clamp, also known in the market as a "round wire to tape clamp". Place the round wire in the saddle of the saddle plate and the tape between the two flat plates, so that both pass between the two bolts and run parallel or at a slight angle to each other. Then tighten the nuts following the manufacturer's instructions. Our galvanised steel round wire is the same material as the galvanised tape and this clamp.
Which sizes of tape, round wire and earth rod does this clamp suit?
The clamp with code TRCG 3016 takes tape 25 to 30 wide and 3 to 3.5 mm thick: 25 × 3 (for tape inside concrete), 30 × 3 and 30 × 3.5. Its round conductor can be 8 or 10 mm galvanised round wire, reinforcing bar up to 16 mm in diameter over the ribs, or a 16 mm stainless steel earth rod. In this application the galvanised tape stays inside concrete or in air, not in soil. 30 × 3.5 is among the most common galvanised tapes in earthing systems. The 8 mm round wire is used mostly for down conductors and roof networks, and the 10 mm round wire inside foundation concrete. For a larger reinforcing bar or earth rod, see the galvanised U clamp. If your project sizes sit near the limits of these ranges, our specialists will recommend the right clamp.
Can this clamp join tape and round wire (or an earth rod) both in parallel and crossing?
The tape and the round conductor both pass through the space between the two bolts, so this clamp joins them parallel or at a slight angle to each other, not crossing at right angles. If the two conductors run perpendicular to each other, bend the round wire slightly at the joint so that it lines up with the tape along the clamp. In a reinforcement cage, choose the reinforcing bar that runs in line with the tape. For a vertical earth rod, bend the end of the tape so that it rises alongside the earth rod. For a 90-degree crossing of two galvanised round wires, see our galvanised cross clamp.
Why does this clamp have three plates, and where do the tape and round conductor go?
Because each conductor has its own place. The round conductor sits in the saddle of the saddle plate, on the bolt head side. After it come the middle flat plate, then the tape, and finally the outer flat plate and the nuts. The middle plate keeps the two conductors apart, so that the round conductor in the saddle and the flat tape between two flat surfaces are each clamped separately.
Does installing this clamp require drilling the tape or welding?
No. The tape is not drilled and its cross-section stays intact. Two spanners are enough for installation, with no need for welding, heat or electricity. We made this clamp for joints inside concrete and in air. Make joints that must be buried directly in soil permanent with exothermic welding.
Can this clamp connect galvanised tape to a copper or copper-bonded earth rod, or to the copper conductor of an earth pit?
No. Connecting galvanised tape to a copper-bonded earth rod in soil is a common site mistake: in moisture, the zinc coating next to copper can corrode quickly, and fine particles shed by a copper part higher up damage the galvanised part even without contact. The same goes for a copper conductor or copper plate in an earth pit. You have two sound options: build the whole system in copper and fix copper tape to the earth rod with our brass A-type clamp, or choose a stainless steel earth rod so that this clamp can connect it to the galvanised tape. To tie an existing copper system into the foundation, consult our specialists before starting work.
Can this clamp also be used with a stainless steel earth rod or stainless steel tape?
Yes. Unlike copper, stainless steel can be used next to galvanised steel in concrete and in air, and the standards recommend that an electrode running from foundation concrete into soil be made of stainless steel. So you can fix galvanised tape inside concrete to a 16 mm stainless steel earth rod with this clamp. This is a joint between two dissimilar metals: place it inside concrete or somewhere dry above ground level, not in soil, and cover it fully with a moisture-proof compound or tape before the pour or in air. If the head of the earth rod is inside an inspection pit, do not make this joint there, because the pit is in contact with soil and moisture. Connect the galvanised tape to a stainless steel branch inside the concrete, so that only stainless steel reaches the pit. If both conductors are stainless steel and you are joining 50 or 70 mm² conductor to 20 × 3 or 30 × 2 tape at right angles, see the multi-purpose stainless steel four-way clamp. For a stainless steel earth rod with stainless steel tape, consult our specialists.
Where should the galvanised foundation tape be joined to an earth rod or a conductor going into soil?
Inside the concrete, with at least 5 cm of cover, so that only stainless steel leaves the concrete: not at the boundary between concrete and soil, and not in soil. A galvanised conductor or joint must not pass straight from concrete into soil. Make any joint that has to be buried in soil with exothermic welding. If the project is in a coastal area or has saline groundwater, consult our specialists before using galvanised parts.
Can this clamp connect the foundation electrode tape to the round wire leading to a test joint or down conductor?
Yes. Galvanised round wire that rises inside a concrete column or wall and reaches the test joint or the down conductor of the lightning protection system sits in the saddle of this clamp, with the foundation tape between the two flat plates. For down conductors, 8 mm round wire is common. Bring this round wire out into the air on the surface of the column or wall or inside the building, not through soil, and mark and protect its end until the work is finished.
What is the code of the galvanised tape-to-earth rod clamp, and what information should we send for a quote?
The code of this clamp is TRCG 3016: TRCG denotes the galvanised clamp connecting tape to a round conductor, 30 is the maximum tape width and 16 the maximum round conductor diameter. When requesting a quote, send us the material and size of the tape (width × thickness), the type, material and diameter of the round conductor (round wire, reinforcing bar or earth rod), the arrangement of the two conductors (parallel or at an angle), the location of the joint (inside concrete or in air), the quantity and, if you have it, the foundation earthing drawing. Our specialists will tell you the right clamp and its price.
Does this clamp also connect galvanised tape to foundation reinforcing bars?
Yes. The ribbed reinforcing bar sits in the saddle of the saddle plate and the tape between the two flat plates. What counts is the bar diameter over the ribs, which must not exceed 16 mm: that means bar number 12 and thinner. Fix the tape to a reinforcing bar running in line with it, and for joints that stay in concrete, connect the tape with two clamps to two separate bars, because these joints can no longer be inspected after the pour. For a larger reinforcing bar, see the galvanised U clamp (reinforcing bar 14 to 34 mm).
How many of these clamps does a building's foundation earthing need?
Count them from the foundation earthing drawing: every point the designer has set for connecting tape to reinforcement (for a joint that stays in concrete, two clamps on two reinforcing bars), every branch reaching a down conductor or test joint, every branch or terminal leaving the concrete, and every stainless steel earth rod. The designer sets the spacing of the connections to the reinforcement according to earthing and lightning protection standards. Keep a few extra clamps for site changes as well.
Should we tie the tape to the reinforcing bar with tie wire, weld it or use a clamp?
Tie wire only holds the tape in place until the pour. Lightning protection standards do not consider such a connection sufficient for lightning current and require the electrical connection to be made by clamp or weld. Welding on reinforcing bar needs the structural designer's agreement and a skilled welder. This clamp goes on beside the formwork and reinforcement without welding or heat, can be inspected before the pour, and can be undone and moved if it is in the wrong place. So hold the tape along its route with tie wire and fit this clamp at the connection points set by the designer. If the designer has asked for a permanent welded joint, see connection by exothermic welding.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.