Move your pointer over the image to zoom in
Complete Product Overview
Stainless steel earth rod (304L and 316 stainless steel)
Order Code: SSER 1615 · SSER 1620 · SSER 2015 · SSER 2020
Last updated:
The stainless steel earth rod, also known as the steel earth rod, from KALOT Group is a solid earth electrode in austenitic stainless steel. Our main grade is 304L, and for highly corrosive environments or on customer request we also manufacture grade 316. Stainless steel is hard and drives well, and it is a common, suitable alternative to a copper electrode beside buried pipes, tanks and steel structures and in installations with cathodic protection.
This earth rod is manufactured in 16 and 20 mm diameters and 1500 and 2000 mm lengths, as a pointed first earth rod and an extension earth rod with integral dowel. To compare it technically and financially with the solid copper earth rod and the copper-bonded earth rod, see the comparison table on this page.
Beside pipes, tanks and steel foundations
When an earth electrode is buried beside a steel foundation, pipe or tank, its material affects the corrosion of the steel structure. Stainless steel is a common choice in these places; it is hard and drives well.
- 304L stainless steel; grade 316 for highly corrosive environments
- 16 and 20 mm diameter; 1500 and 2000 mm long; M10 thread
- Pointed first earth rod, extension earth rod with integral dowel
- Less effect than copper on buried steel structures
304L, and 316 for highly corrosive environments
304L is our main grade; for highly corrosive environments or on customer request, we supply grade 316 with molybdenum.
Integral dowel, no extra part
The dowel of the extension earth rod screws into the internal thread of the first earth rod; the joint is the same material as the earth rod.
Beside steel structures
Pipes, tanks, large reinforced concrete foundations, and oil, gas and petrochemical installations with cathodic protection.
Hard and strong when driven
Stainless steel withstands impact far better than copper, and the point of the first earth rod clears the way through the soil.
Seven drawings and a datasheet
Stainless steel earth rod datasheet (PDF)You will find the dimensional drawing, technical drawing, exploded view, installation schematic, installation steps, connection modes and comparison table as PDF files beside the datasheet.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Product type | Solid stainless steel earth rod (earth electrode), two-length |
Material | Austenitic stainless steel 304L; for highly corrosive environments or on request, 316 |
Diameter D | 16 and 20 mm |
Thread | M10 on both diameters; internal thread depth and integral dowel length 20 mm |
First earth rod | Pointed, with a 20 mm point length; M10 internal thread 20 mm deep at the upper end |
Extension earth rod | Integral M10 dowel 20 mm long at the lower end; plain, chamfered upper end |
Length of each section | 1500 and 2000 mm |
Electrode depth | First earth rod and extension earth rod together: 3, 3.5 or 4 m |
Weight of a 1500 length (304L) | 2.36 kg (16 diameter) and 3.70 kg (20 diameter) |
Driving tools | Threaded driving head for the first earth rod; the extension earth rod is driven directly, and a hollow driving cap in hardened steel is supplied on request |
Design basis | Grade 316 based on the requirements of IEC 62561-2 |
Order code | SSER 1615, SSER 1620, SSER 2015 and SSER 2020 with suffix S (first earth rod) or E (extension earth rod); for 316, suffix -316 |
Models, order codes and weight
Order code | Type | Diameter D (mm) | Thread | Length L (mm) | 304L weight (kg) | 316 weight (kg) |
|---|---|---|---|---|---|---|
SSER 1615 S | First earth rod | 16 | M10 | 1500 | 2.36 | 2.38 |
SSER 1615 E | Extension earth rod | 16 | M10 | 1500 | 2.37 | 2.39 |
SSER 1620 S | First earth rod | 16 | M10 | 2000 | 3.16 | 3.18 |
SSER 1620 E | Extension earth rod | 16 | M10 | 2000 | 3.17 | 3.19 |
SSER 2015 S | First earth rod | 20 | M10 | 1500 | 3.70 | 3.72 |
SSER 2015 E | Extension earth rod | 20 | M10 | 1500 | 3.70 | 3.72 |
SSER 2020 S | First earth rod | 20 | M10 | 2000 | 4.94 | 4.97 |
SSER 2020 E | Extension earth rod | 20 | M10 | 2000 | 4.94 | 4.97 |
The first earth rod is pointed (point length P = 20 mm) and has an M10 internal thread at its upper end, L1 = 20 mm deep. The extension earth rod has an integral M10 dowel at its lower end, S = 20 mm long, and a plain, chamfered upper end. Length L is the overall length on both types. Grade 304L is the main grade; for grade 316 the suffix "-316" is added to the code (for example SSER 1615 S-316). Our products are continually improved and the dimensions of some may be updated; please confirm final dimensions with our specialists before buying.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Exploded view
Download the exploded view (PDF)
Structure: first earth rod and extension earth rod
The KALOT stainless steel earth rod comes in two types of length. The first earth rod has a pointed lower end that clears the way through the soil, and an M10 internal thread machined into its upper end; during driving, a threaded driving head screws into this thread. The extension earth rod has an integral M10 dowel at its lower end, which screws fully into the thread of the first earth rod until its shoulder seats on the top of the first earth rod; its upper end is plain and chamfered and is driven directly. The dowel is the same material as the earth rod itself, so there is no separate part in the joint.
Click to view enlarged
Applications of the stainless steel earth rod
- Beside buried pipes, tanks and steel structures: where a copper electrode would worsen corrosion of the nearby steel.
- Installations with cathodic protection: pipelines, tanks and oil, gas and petrochemical facilities; coordinate the design with the cathodic protection designer.
- Large reinforced concrete foundations: electrodes driven at the bottom of the foundation excavation and connected to the foundation earth ring.
- Acidic soils and soils containing organic acids: where copper lasts less well.
- Coastal and highly corrosive environments: with grade 316.
- Building lightning protection and earthing systems: the vertical electrode of each down conductor, with the conductor joint inside the earth pit.
Installation schematic: driven or in a borehole
Download the execution schematic (PDF)
Ways of connecting the conductor to the earth rod
Download connection modes (PDF)
How to install and drive the stainless steel earth rod
- Check the soil resistivity and the electrode location, and mark the route of underground services. Dig the hole for the earth inspection pit.
- Screw the threaded driving head into the thread at the upper end of the first earth rod, and stand the earth rod vertically with its pointed end down.
- With a sledgehammer or electric hammer, strike with even, axial blows until a short part of the earth rod remains above ground; if it leans, stop and straighten it.
- Remove the driving head and, by hand and with a clean thread, screw the integral dowel of the extension earth rod fully into the internal thread of the first earth rod until its shoulder seats on the top of the first earth rod.
- Drive the extension earth rod directly on its plain upper end until its top sits inside the earth pit; we supply a hollow driving cap in hardened steel on request.
- In rocky soil, you can drill a borehole, place the two joined lengths at its centre and fill around them with ECO GIM ground improvement material.
- Measure the resistance of the electrode; if it is above the required value, drive another electrode at a spacing at least equal to the electrode length.
- Fix the copper conductor to the top of the earth rod inside the earth pit with a KALOT G clamp (conductor) or KALOT A clamp (tape), then set the pit in place and pour concrete around it.
Download the installation steps (PDF)
Installation tools
Sledgehammer or electric hammer, threaded driving head for the first earth rod, hollow driving cap for the extension earth rod (on request), level or plumb line. Fit the dowel by hand, and if a spanner is needed, use one with soft jaws so the body is not scratched.
Measurement and inspection
Measure the electrode resistance with the fall-of-potential method (62 percent); in systems with several electrodes connected together, a clamp-on tester is also used. Record the result with the season and soil moisture, and at periodic inspections inside the pit check that the clamp is tight and the conductor is sound. For the measurement method, see how the resistance of an earth termination is measured.
Selection and price enquiry
To request a price for the stainless steel earth rod, send our specialists the order code or the diameter (16 or 20 mm), length (1500 or 2000 mm), number of first and extension earth rods, grade (304L or 316) and the accessories you need (driving head, cap, clamp and earth pit). Our specialists at KALOT Group will help you choose the right grade and size for your project.
Click to view enlarged
The electrode material does not determine the earth termination resistance; the soil and the electrode length do. What the material determines is the life of the electrode and its effect on other metals in the soil. Copper is more noble than steel, and if it is connected to an uncoated steel structure in the soil, it worsens that structure's corrosion. According to BS 7430, beside steel structures with cathodic protection, an austenitic stainless steel electrode wastes less protective current than a copper electrode, which is why it is common in oil, gas and petrochemical installations. Stainless steel is hard and drives well. Grade 316, with molybdenum, resists pitting corrosion better in chloride environments.
Advantages of the KALOT stainless steel earth rod
- Two grades: 304L as the main grade; 316 for highly corrosive environments or on request.
- More suitable than copper beside steel structures: the common option beside pipes, tanks and foundations and in installations with cathodic protection, in coordination with the cathodic protection designer.
- Impact resistant: harder and stronger than copper; suitable for driving with an electric hammer.
- Integral dowel: the dowel is the same material as the earth rod itself; there is no separate part in the joint.
- No coating: there is no coating to wear or come off during driving.
- Diameter meets the standard minimum: 16 and 20 mm, equal to or above the minimums in the IEC standards and Topic 13.
Comparison and selection guide
Download the comparison and selection guide (PDF)
Technical and financial comparison table of KALOT earth rods
Feature | Galvanised | Copper-bonded | Solid copper | Stainless steel 304L | Stainless steel 316 |
|---|---|---|---|---|---|
Material | S275 steel core with hot-dip galvanised coating (50 to 70 microns) | Steel core with copper coating (at least 0.25 mm) | Copper throughout the cross-section | Low-carbon austenitic stainless steel (18% chromium, 8% nickel) | Austenitic stainless steel with molybdenum (10% nickel, 2% molybdenum) |
KALOT sizes | Diameters of 16 and 20; lengths of 1500 and 2000 | 5/8 and 3/4 inch; length 1500 | Diameters of 16 and 20; length 1500 | Diameters of 16 and 20; lengths of 1500 and 2000 | Diameters of 16 and 20; lengths of 1500 and 2000 |
Weight per 1500 length (kg) | 2.38 and 3.71 | 1.95 and 2.76 | 2.68 and 4.19 | 2.36 and 3.70 | 2.38 and 3.72 |
Joining lengths | One piece, no thread; several parallel earth rods with a galvanised conductor | Brass coupling; several lengths end to end | M10 dowel; several lengths end to end | Integral dowel; first earth rod and extension earth rods | Integral dowel; first earth rod and extension earth rods |
Installation method | Direct driving with a driving cap, or a borehole with ground improvement material | Driving to great depth | Borehole with ground improvement material, or driving in soft soil | Driving; in rocky soil, a borehole with ground improvement material | Driving; in rocky soil, a borehole with ground improvement material |
Minimum diameter according to IEC 62305-3 (mm) | 14 | 14 (with 0.25 mm coating) | 15 | 15 | 15 |
Tensile strength according to IEC 62561-2:2018 (N/mm²) | 350 to 770 | 350 to 770 | 200 to 450 | 350 to 770 | 350 to 770 |
Maximum electrical resistivity according to IEC 62561-2:2018 (µΩ·m) | 0.25 | 0.25 | 0.018 | 0.80 | 0.80 |
Corrosion resistance | Moderate; the zinc coating is gradually consumed | Good, as long as the coating is intact | Very good | Good | Very good |
Saline and chloride soil | Poor to moderate | Medium | Good | Moderate; pitting corrosion is possible | Very good |
Acidic and organic soil | Poor | Medium | Medium | Good | Good |
Beside buried steel and cathodic protection | Compatible, with faster consumption of the zinc coating; not when connected to foundation reinforcing bars | With caution | With caution | More suitable than copper; in coordination with the designer | More suitable than copper; in coordination with the designer |
Ease of driving | Very good | Very good | Limited | Good | Good |
Raw metal value per 1500 length (US dollars) | 1.2 and 1.8 | 3.0 and 3.8 | 39.7 and 62.1 | 5.2 and 8.1 | 10.3 and 16.1 |
Metal value index (copper-bonded = 1) | 0.4 to 0.5 | 1 | 13 to 16 | 1.7 to 2.1 | 3.4 to 4.2 |
Cost rank (1 = lowest) | 1 | 2 | 5 | 3 | 4 |
Recommended use | All-galvanised earthing networks: towers, fences and galvanised steel structures; temporary site earthing; neutral, well-drained soil | Most projects: buildings, substations, lightning protection and towers | Saline and corrosive soils; high fault current | Beside foundations and steel pipes and tanks; low-salt, well-drained soil | Coastal areas, chloride soil, chemical industries; projects that call for IEC requirements |
This table was prepared on 21 Mehr 1405. Metal value is calculated from the official London Metal Exchange (LME) prices for copper, nickel and zinc, global market reference prices for steel, chromium and molybdenum on those same days, and the weight of each length, and it changes as metal prices change; the selling price also includes manufacturing cost. Weights are for the smaller and larger size of each type. Earth resistance is determined by the soil and the electrode length, not the material; choose the material based on the soil, the surrounding metal structures and the installation method. To learn more, see choosing the right material for an earth electrode and calculating earth termination resistance.
If this matches your situation, see these products too
Product | When |
|---|---|
For very saline, corrosive soils and copper systems. | |
For all-galvanised earthing networks such as towers, fences and galvanised steel structures, with the lowest metal value. | |
For most projects, and for driving to great depths at lower cost. | |
For driving the first earth rod without damaging the thread at its end. | |
Connects copper wire to the earth rod. | |
Connects copper tape to the earth rod. | |
Protects the top of the earth rod and the conductor connection, and allows measurement. | |
A lightweight inspection pit that is easy to handle; like the concrete one, it has concrete poured around it. | |
For filling boreholes in rocky or high-resistivity soil. |
IEC 62561-2 (lightning protection system components; conductors and earth electrodes) sets the minimum cross-section of a stainless steel earth rod at 176 mm², that is, a 15 mm diameter; our 16 and 20 mm diameters exceed it. The KALOT 316 stainless steel earth rod is designed and manufactured based on the requirements of this standard.
IEC 62305-3 (protection of structures against lightning) lists a diameter of 15 millimetres for solid copper and stainless steel earth rods in its table of electrode dimensions. In a Type A arrangement, at least one electrode is connected to each down conductor, and the minimum number of electrodes is two.
IEC 60364-5-54 (earthing arrangements) gives 16 mm as the minimum diameter for a vertical stainless steel earth rod and, for electrode stainless steel, specifies a composition of at least 16 percent chromium, 5 percent nickel and 2 percent molybdenum; 316 stainless steel has such a composition. An annex of the same standard says the junction of two dissimilar metals must not be in contact with the soil, which is why we place the joint between the copper conductor and the earth rod inside the earth pit.
Topic 13 of the Iranian National Building Regulations requires a driven vertical electrode to reach a depth of at least 2 m, sets the minimum diameter of a stainless steel earth rod at 16 mm, and in a separate table shows the compatibility of different metals when bonded in soil.
BS 7430 (code of practice for earthing) regards the austenitic stainless steel electrode, for steel structures with cathodic protection, as an option that usually wastes less cathodic protection current than copper, and says a bare copper electrode must not be connected directly to such a structure.
Installing a stainless steel earth rod: first rod and extension
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Stainless steel earth rod dimensional drawingLanguage: Persian (opens in a new tab)
- Stainless steel earth rod technical drawingLanguage: Persian (opens in a new tab)
- Stainless steel earth rod exploded viewLanguage: Persian (opens in a new tab)
- Stainless steel earth rod installation schematicLanguage: Persian (opens in a new tab)
- Stainless steel earth rod connection modesLanguage: Persian (opens in a new tab)
- Stainless steel earth rod installation stepsLanguage: Persian (opens in a new tab)
- Stainless steel earth rod comparison and selection guideLanguage: Persian (opens in a new tab)
Frequently Asked Questions
Where are stainless steel earth rods used?
Beside buried pipes, tanks and steel structures, in installations with cathodic protection, beside large reinforced concrete foundations and in acidic soils. Grade 316 suits coastal and highly corrosive environments.
Which is better for an earth rod, 304L or 316 stainless steel?
Our main grade is 304L, which suits most projects and is more economical. Grade 316 contains molybdenum, resists pitting corrosion better in saline and chloride environments, and its composition matches what IEC 60364-5-54 specifies for stainless steel electrodes. We supply it for highly corrosive environments or on customer request.
Do stainless steel earth rods rust?
Stainless steel protects itself with a thin protective oxide layer and remains stable in most soils. In highly corrosive, high-chloride environments, choose grade 316.
Stainless steel or copper: which earth rod is better?
Both last a long time. Stainless steel is harder, drives better and is more suitable beside steel structures and cathodic protection; a solid copper earth rod is a durable option for very saline soils and copper systems. The comparison table on this page sets out the technical and cost differences side by side.
What is the difference between the first earth rod and the extension earth rod?
The first earth rod is pointed and has an M10 internal thread at its upper end. The extension earth rod has an integral M10 dowel at its lower end, which screws into the thread of the first earth rod, and a plain upper end. Together they form a two-length electrode 3, 3.5 or 4 m long.
What tools are used to drive a stainless steel earth rod?
For the first earth rod, a threaded driving head screws into the thread at the upper end so the thread is not damaged. The extension earth rod is driven directly on its plain end with a sledgehammer or electric hammer; if you wish, we also supply a hollow driving cap in hardened steel that sits on top of the earth rod.
How many metres should a stainless steel earth rod be driven?
Topic 13 of the Iranian National Building Regulations requires a driven vertical electrode to reach a depth of at least 2 m, and the top of the electrode stays inside the earth pit. That is why we usually use the first and extension earth rods together (3, 3.5 or 4 m). The final depth depends on the resistance the project needs and the measurement result.
Can a copper conductor be connected to a stainless steel earth rod?
Yes. Copper and stainless steel have close potentials in soil and do little harm to each other. Fix conductor with a KALOT G clamp and tape with a KALOT A clamp, and keep the joint inside an earth pit so it stays dry and open to inspection. Exothermic welding is also possible with a mould suited to the earth rod diameter. Do not connect an aluminium conductor or cable lug to a stainless steel earth rod.
How much does a stainless steel earth rod weigh?
Each 1500 mm length in 304L weighs 2.36 kg at 16 mm diameter and 3.70 kg at 20 mm diameter. The weights of all models are given in the models table.
Is a 16 or a 20 mm diameter better?
Diameter has little effect on earth resistance. The 20 mm size is stiffer and better suited to driving deeper with an electric hammer; the 16 mm size is lighter and more economical.
How is earth rod resistance measured?
Usually with the fall-of-potential method and an earth resistance tester: the current electrode sits at a far distance and the voltage electrode at 62 percent of that distance. Repeat the measurement after installation and at periodic inspections.
Have a Technical Question?