Raised floor pedestal earth clamp (pedestal clamp)
Last updated:
The KALOT Group raised floor pedestal earth clamp, also known on the market as a "pedestal clamp" or "raised floor earth clamp", connects the metal pedestals of a raised floor to the bonding network under the floor. In data centres and server rooms this network is called the "signal reference grid (SRG)", and it reduces potential differences between metal structures and sensitive equipment. The clamp fastens around the pedestal tube with a galvanised U clamp, and the network's copper conductor, held in the groove of its brass clamps, makes a bolted metal-to-metal connection with the pedestal. We make this clamp with a stainless steel strap and two brass clamps, so that the mesh's copper conductor connects to the pedestal with no welding or drilling.
Raised floor bonding does not replace the equipment's protective earth conductor; it works alongside it. For a complete network you can also get bare copper conductor, flexible bonding tape, the room earth bar and other earthing and bonding clamps from us.
The raised floor pedestal, part of the bonding network
In rooms with a raised floor, the metal pedestals under the floor connect to the bonding network so that the floor, structure and sensitive equipment stay at the same potential. The pedestal clamp makes this connection with no welding or drilling of the pedestal.
- Bonds raised floor pedestals to the mesh under the floor
- U clamp around the pedestal tube
- Two brass clamps on two perpendicular faces
- Stainless steel strap
Connection with no welding or drilling
The U clamp fastens around the pedestal tube, so the pedestal is not drilled and no welding is needed under the raised floor.
Two conductor connection points
One clamp is on the strap and one on the bent end. Each clamp holds one conductor firmly in its groove, between clamp and strap.
Brass and stainless steel
The clamps are made of brass and the strap of stainless steel, and the copper conductor sits on the brass clamp.
Drawings and datasheet
Raised floor pedestal earth clamp datasheet (PDF)On this page you will find the parts drawing, technical drawing, exploded view, installation schematic with underfloor mesh layout, installation steps and conductor connection modes as PDF files, alongside the datasheet.
Bonding network layout
Our specialists work through the mesh spacing, the number of bonded pedestals and the connection point to the earth bar with you during design.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | Bonding clamp for raised floor metal pedestals, with a U clamp and two conductor clamps |
Tape | Stainless steel, with one bent end |
U clamp | Galvanised steel with flat washer and nut; fastens around the round pedestal tube |
Conductor clamps | Two brass clamps, one on the strap and one on the bent end, each with a bolt and nut and one groove for the conductor |
Conductor | Bare copper conductor, or green and yellow insulated copper conductor stripped only at the clamp |
Installation location | On the pedestal tube, under the pedestal head or near the floor, according to the bonding network layout |
Application | Data centres, server rooms, control rooms and telecoms equipment rooms with a raised floor |
Parts and materials
Part | Quantity | Material |
|---|---|---|
L-shaped strap with U clamp holes | 1 | Stainless steel |
U clamp with two flat washers and two nuts | 1 | Galvanised steel |
Conductor clamp | 2 | Brass |
Clamp bolt and nut | 2 | Steel |
Our products are continually improved and some dimensions may be updated; please confirm the final dimensions with our specialists before you buy.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Exploded view
Download the exploded view (PDF)
Pedestal clamp construction
The clamp body is a stainless steel strap with one end bent at 90 degrees. The galvanised U clamp wraps around the back of the pedestal tube, passes through two holes in the strap and, with washers and nuts, holds the strap firmly on the pedestal. Two brass clamps are fixed on the strap and on the bent end. The conductor lies in the clamp's groove, between clamp and strap, and tightening the clamp bolt makes a bolted metal-to-metal connection. Each clamp takes one conductor.
Click to view enlarged
Applications of the raised floor pedestal earth clamp
- Data centres and server rooms: bonding raised floor pedestals to the signal reference grid under the floor, alongside earthing and bonding of sensitive equipment.
- Control rooms and telecoms equipment rooms: bringing the raised floor structure to the same potential as the room's racks and panels.
- UPS and battery rooms with a raised floor: connecting the metal floor structure to the room's bonding network.
- Refurbishing existing rooms: adding bonding to pedestals already installed, with no welding or drilling.
Installation schematic
Download the execution schematic (PDF)
Conductor connection modes
Download connection modes (PDF)
Steps for installing the clamp on a raised floor pedestal
- Check the bonding network layout: the conductor routes, the pedestals to be bonded and where the network connects to the room earth bar.
- Clean the pedestal tube surface where the clamp goes. If the pedestal is painted, remove paint only at the contact point and according to the design.
- Place the U clamp around the back of the pedestal tube, pass its two ends through the holes in the strap and fit the washers and nuts by hand. Adjust the clamp height.
- Lay the copper conductor in the clamp's groove, between clamp and strap. If a second conductor is needed, fix it in the clamp on the bent end. Connect the conductor to the mesh outside the clamp.
- Tighten the clamp bolts, then the U clamp nuts, alternately and evenly, according to the manufacturer's instructions. The pedestal tube must not deform.
- Measure the continuity of the connection with a low-resistance ohmmeter, record the result and label the connection point.
Download the installation steps (PDF)
Installation tools
For installation you need a spanner to match the nuts, a wire brush or abrasive paper to clean the contact point and a low-resistance ohmmeter for the continuity test.
Inspection and testing
During periodic inspections, check the tightness of the clamp bolts and U clamp nuts and the condition of the conductors, and measure network continuity again, especially after equipment has been moved or work has been done under the raised floor. Compare the result with the previous test.
Selection and price enquiry
To get a price for the raised floor pedestal earth clamp, send our specialists the pedestal tube diameter, the type and size of the mesh conductor (conductor or tape), the number of pedestals to be bonded and the type of room.
Click to view enlarged
Under a raised floor, metal pedestals and rails sit next to power and network cabling. If the floor structure is not connected to the bonding network, potential differences between the floor, racks and equipment can cause noise, data errors or a risk of electric shock. A signal reference grid creates a low-impedance equipotential plane under the equipment, and bonding the pedestals connects the floor structure to that same plane. The pedestal clamp makes this connection with no welding, on pedestals already installed, and stays open to later inspection.
Advantages of the KALOT raised floor pedestal earth clamp
- Fits existing pedestals: the U clamp fastens around the pedestal tube, so the pedestal is not drilled and no welding is needed.
- Two connection points on one clamp: the clamp on the strap and the clamp on the bent end each hold one conductor firmly in their groove.
- Brass clamp: the copper conductor sits on the brass clamp and is held firm by a bolt.
- Stainless steel strap: the clamp body needs no separate paint or coating.
- Open to inspection: the connection is bolted, so it can be checked and retightened at periodic inspections.
Methods of bonding a raised floor pedestal
Method | Fits existing pedestals | Can be opened and readjusted | Note |
|---|---|---|---|
Bolted clamp on the pedestal (pedestal clamp) | Yes | Yes | No welding; the conductor is fixed in the clamp |
Exothermic welding of conductor to pedestal | Limited | No (permanent joint) | Needs a mould and hot-work safety precautions under the floor |
Connecting the floor rails to each other only | Yes | Yes | On its own, does not match the performance of a copper network |
For permanent joints, see exothermic welding.
If this matches your situation, see these products too
Product | When |
|---|---|
For the copper mesh conductors under the raised floor. | |
For a tape mesh under the floor. Please agree the tape-to-pedestal connection with our specialists before you order. | |
For a tape mesh with a tin coating. | |
For bonding racks and cabinets to the mesh. | |
As the room's bonding bar. | |
For connecting conductors at mesh crossings. | |
Where conductor and tape meet at a mesh crossing. |
Compare all earthing and bonding clamps in the "Which clamp should we choose?" table.
IEEE 1100 (the Emerald Book) describes the signal reference grid as copper conductors running in two directions, joined at their crossings with mechanical clamps or exothermic welds. The grid is either laid on the concrete floor or fixed to the pedestals just below their heads with X-Y clamps and U clamps. Its recommended mesh matches the pedestal grid, that is, 60 × 60 cm.
TIA-942 (2005 edition), in its informative annex, recommends bonding raised floor pedestals regularly at a set spacing to the computer room mesh, and bonding each rack to the mesh separately.
NFPA 70 (the US National Electrical Code, section 645.15) requires a signal reference grid, where installed, to be connected to the protective earth conductor of the IT equipment. In other words, this grid complements protective earthing and does not replace it.
Bonding standards for telecoms buildings, such as ANSI/TIA-607 and EN 50310, describe common and mesh bonding networks (CBN and Mesh-BN). To learn more, see bonding and equipotential bonding.
Raised floor pedestal earth clamp
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Raised floor pedestal earth clamp dimensional drawingLanguage: Persian (opens in a new tab)
- Raised floor pedestal earth clamp technical drawingLanguage: Persian (opens in a new tab)
- Raised floor pedestal earth clamp exploded viewLanguage: Persian (opens in a new tab)
- Raised floor pedestal earth clamp installation schematicLanguage: Persian (opens in a new tab)
- Raised floor pedestal earth clamp connection modesLanguage: Persian (opens in a new tab)
- Raised floor pedestal earth clamp installation stepsLanguage: Persian (opens in a new tab)
Frequently Asked Questions
What is a pedestal clamp?
A pedestal clamp, or raised floor pedestal earth clamp, connects the metal pedestal of a raised floor to the copper conductor of the bonding network under the floor. Our clamp fastens around the pedestal tube with a U clamp, and the conductor is held firmly in its brass clamps.
Why do we bond raised floor pedestals?
So that the metal floor structure, racks and sensitive equipment stay at the same potential. Bonding reduces noise and potential differences between structures, and creates a controlled path for fault current and static electricity.
What is a signal reference grid (SRG), and how does it differ from protective earthing?
A signal reference grid is a mesh of copper conductors under the raised floor that creates a low-impedance equipotential plane for the equipment. Protective earthing is for safety against electric shock; this grid complements it and does not replace it.
Must every raised floor pedestal be connected to the mesh?
The project designer decides how many pedestals are bonded and at what spacing. References range from bonding every pedestal at a mesh crossing to bonding pedestals regularly at a set spacing. Our design specialists can help you choose.
Should the copper mesh go on the concrete floor or under the pedestal heads?
Both methods are common. A mesh on the concrete floor stays clear of the floor panels, while a mesh close to the pedestal heads is nearer the equipment. Either way, the pedestal clamp connects the conductor to the pedestal, and you set the clamp height on the pedestal tube.
For a mesh under a raised floor, is copper conductor or copper tape better?
Both are used. Bare copper conductor is simpler to install, while copper tape has more conductor surface and lower impedance at high frequencies. The choice depends on the project design. For the clamps on this product, please confirm the conductor type and size with our specialists when you enquire.
How do racks and cabinets connect to the mesh under the floor?
Each rack connects to the mesh separately with a flexible bonding tape or a short conductor. Racks are not connected to each other in series.
Does a painted or galvanised pedestal need preparation?
Clean the tube surface where the clamp goes. If the pedestal is painted, remove paint only at the contact point and according to the design, and do not scrape off galvanised coating without good reason.
What test should be done after installation?
Measure continuity between the pedestal, the mesh conductor and the room earth bar with a low-resistance ohmmeter and record the result. The same test is repeated at periodic inspections.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.