Earth bar without disconnect link
Last updated:
The KALOT earth bar without a link is the simplest earth bar on insulators. It shares one earthing system output among several loads and, being mounted on insulators, stays separate from the wall or panel it is fixed to. Its length depends on the number of inputs and outputs, and it is made in six sizes, from 2 to 12 holes. The bar is 50 x 5 mm copper and the base is stainless steel.
The bar is 50 x 5 mm copper, mounted on 2 to 4 reinforced polyester insulators and a stainless steel base. Codes EB 020L to EB 120L have 2 to 12 holes and lengths of 161 to 511 mm, with M10 or M12 connection bolts. This model suits secondary earth bars, such as a floor or plant room earth bar that is itself fed from the main earth bar.
Mounted on insulators, separate from the mounting surface
The earthing system input conductor and the load conductors are each fixed to one of the bar's holes with a cable lug of matching size.
- Mounted on insulators, separate from the mounting surface
- 50 x 5 copper bar; tinned to order
- Stainless steel base
- Six lengths, from 2 to 12 holes
Suited to secondary earth bars
For a floor or plant room earth bar fed from the main earth bar. The insulators keep the bar separate from walls and structures.
Common point for earth conductors
The earth conductor, protective conductors and bonding conductors are each fixed to the bar's holes with their own cable lug.
Copper or tinned copper
Bare copper for dry environments and the inside of panels. The tinned version helps reduce oxidation and discolouration of the copper surface in damper or more corrosive environments.
6 standard codes
Codes EB 020L to EB 120L. Other dimensions are made to order.
Made by KALOT Group
Designed and made to KALOT drawings and technical catalogue. The datasheet for each model is in the documents section.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | Earth bar on insulators, without disconnect link |
Bar | 50 x 5 mm copper; tinned copper to order |
Base | Stainless steel |
Insulator | Reinforced polyester; 2 to 4 depending on bar length |
Bolts, nuts and washers | Stainless steel or brass |
Number of holes | 2, 4, 6, 8, 10 or 12 (according to code) |
Cable lug connection bolt | M10 or M12, to order |
Codes | EB 020L to EB 120L |
Codes and dimensions
Code | Number of holes | L (mm) | W (mm) | H (mm) |
|---|---|---|---|---|
EB 020L | 2 | 161 | 90 | 90 |
EB 040L | 4 | 231 | 90 | 90 |
EB 060L | 6 | 301 | 90 | 90 |
EB 080L | 8 | 371 | 90 | 90 |
EB 100L | 10 | 441 | 90 | 90 |
EB 120L | 12 | 511 | 90 | 90 |
Dimensions are in millimetres. Our products are continually improved and some dimensions may be updated, so please confirm final dimensions with our specialists before you buy.
Click to view enlarged
Dimensional drawing of the earth bar without disconnect link, based on KALOT drawings and catalogue. The dimensions of each code are in the table below.
Code | Number of holes | L (mm) | W (mm) | H (mm) |
|---|---|---|---|---|
EB 020L | 2 | 161 | 90 | 90 |
EB 040L | 4 | 231 | 90 | 90 |
EB 060L | 6 | 301 | 90 | 90 |
EB 080L | 8 | 371 | 90 | 90 |
EB 100L | 10 | 441 | 90 | 90 |
EB 120L | 12 | 511 | 90 | 90 |
Download: Datasheet (PDF) · Drawing PDF · Drawing SVG · Colour drawing PDF
Click to view enlarged
The earth bar in the earthing system
An earth bar is the common point where the earth conductor (from the electrode or earthing network), protective conductors and bonding conductors meet. Each conductor is fixed with a cable lug of matching size and a bolt and nut to one of the bar's holes, so the number of holes, and with it the earth bar length, depends on the number of inputs and outputs.
The earthing system input conductor and the load conductors are each fixed to one of the bar's holes with a cable lug of matching size. If you need to isolate the earthing system for measurement, choose the one-link or two-link earth bar. We supply the bar in two types, bare copper and tinned copper. The tinned version helps reduce oxidation and discolouration of the copper surface in damper or more corrosive environments.
Installation
Install the earth bar on a flat, solid surface, in a dry place accessible for inspection. For wall mounting, the KALOT catalogue recommends 1½ inch No. 12 countersunk wood screws with No. 12 wall plugs. Fix each conductor to the bar with a cable lug of matching size and tighten the bolts evenly. In open or busy locations, place the earth bar inside a protective enclosure.
Typical connections
The secondary earth bar of each floor or plant room is fed from the main earth bar and bonds the nearby metal water and gas pipes, boiler body, pump and cable tray.
Enquiries
When you enquire, tell us the number of inputs and outputs, the number of disconnect links, the cross-section of the conductors and the installation location, and our specialists will recommend the right code. Other dimensions and hole counts are also made to order.
IEC 60364-5-54 provides for a means of disconnecting the earth conductor from the main earthing terminal: a device in an accessible place that opens only with a tool and is used for measuring earth resistance. A disconnect link does exactly this. In lightning protection systems, IEC 62305-3 provides test joints for measuring earth resistance.
Three-dimensional view of an earth bar installation in a building
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
Similar & Complementary Products
Frequently Asked Questions
What is an earth bar used for?
An earth bar is the common connection point for the earth conductor, protective conductors and bonding conductors, and it shares one earthing system output among several loads.
What is a disconnect link for?
To separate the earthing system from the loads during inspection and earth resistance measurement, without opening the connection of each individual load.
How do I choose the right code?
The number of inputs and outputs sets the number of holes you need, and the number of earthing systems to be measured separately sets the number of links.
Bare or tinned copper: which should I choose?
Bare copper is sufficient for dry environments and the inside of panels and electrical rooms. In damper or more corrosive environments, the tinned version helps reduce oxidation and discolouration of the copper surface.
Is an earth bar without a link suitable as a building's main earth bar?
For the main earth bar, where the electrode conductor arrives, the model with a link is usually chosen so measurement is possible without opening the cables. The model without a link is mostly used for secondary earth bars.