Complete Product Overview
Copper C clamp for branch and parallel earth conductor connections (CCC)
Last updated:
The C clamp, also written C-clamp and also called a copper compression clamp, is a C-shaped copper part that holds the main copper conductor and the branch conductor side by side and is pressed onto both with a dedicated press. The result is a permanent, bolt-free connection, used to take a branch from the main conductor without cutting it and to join two conductors in parallel in the earthing network.
The C clamp is for connections that will not be opened and where exothermic welding is not possible or economical. It installs without flame, in any weather. Choose the code by the cross-sections of the main and branch conductors: we offer 23 sizes from CCC 1010 to CCC 2424 for main conductors of 10 to 240 and branches of 1.5 to 240 mm².
Permanent branch and parallel joints
A C clamp for branch and parallel joints of copper earth conductors, where the connection will not be opened.
- Permanent branch and parallel joints
- Copper, the same material as the earth conductor
- No bolts; closes under a press
- 23 sizes, conductors from 1.5 to 240
Even pressure, independent of the installer
Installation and pressing steps (PDF)The press and die set the connection force, not the installer's hand, so every connection on a project closes the same way.
The main conductor is not cut
The C clamp sits on the main conductor and the branch is pressed beside it, so the main run stays continuous.
Material
Copper body, the same material as the copper earth conductor.
23 standard codes
Dimension table for the 23 codes (PDF)Codes CCC 1010 to CCC 2424. Choose the code by the cross-sections of the main and branch conductors.
Advice from KALOT specialists
When you enquire, tell us the connection type (branch or parallel), the cross-sections of the main and branch conductors and the quantity you need, and our specialists will recommend the right code.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | C-shaped compression connection (C clamp) |
Material | Copper |
Application | Branch (T joint) and parallel joints of stranded copper conductors in earthing and bonding systems |
Main conductor (A) | 10 to 240 mm² (by code) |
Branch conductor (B) | 1.5 to 240 mm² (by code) |
Installation method | Dedicated C clamp press with a die matched to the size |
Connection type | Permanent; cannot be opened and closed |
Codes | CCC 1010 to CCC 2424 |
C clamp (CCC) codes and dimensions
Code | Main conductor A (mm²) | Branch conductor B (mm²) | L (mm) | W (mm) | H (mm) |
|---|---|---|---|---|---|
CCC 1010 | 10 | 4-10 | 13 | 12 | 9 |
CCC 1016 | 10-16 | 10-16 | 19 | 17 | 12 |
CCC 1604 | 16 | 4 | 19 | 17 | 12 |
CCC 1610 | 16-25 | 1.5-10 | 20 | 12 | 13 |
CCC 2516 | 25 | 10-16 | 21 | 19 | 12 |
CCC 2525 | 25 | 10-25 | 24 | 20 | 15 |
CCC 3516 | 35 | 1.5-16 | 24 | 20 | 15 |
CCC 3535 | 35 | 25-35 | 27 | 20 | 15 |
CCC 5016 | 50 | 4-16 | 27 | 20 | 15 |
CCC 5050 | 50 | 16-50 | 27 | 20 | 17 |
CCC 7025 | 70 | 1.5-25 | 27 | 20 | 17 |
CCC 5035 | 50-70 | 4-35 | 33 | 28 | 21 |
CCC 5070 | 50-70 | 35-70 | 34 | 28 | 21 |
CCC 7070 | 70-95 | 35-70 | 41 | 30 | 26 |
CCC 9535 | 95 | 4-35 | 41 | 30 | 26 |
CCC 7095 | 70-95 | 95 | 41 | 30 | 26 |
CCC 1212 | 120 | 35-120 | 45 | 30 | 28 |
CCC 1506 | 150 | 6-70 | 45 | 30 | 28 |
CCC 1515 | 150 | 95-150 | 45 | 30 | 28 |
CCC 1218 | 120-185 | 95-185 | 54 | 35 | 33 |
CCC 1570 | 150-185 | 70-150 | 54 | 35 | 33 |
CCC 2412 | 240 | 95-120 | 54 | 37 | 34 |
CCC 2424 | 240 | 150-240 | 54 | 40 | 34 |
Dimensions are in millimetres and cross-sections in square millimetres. L is the height of the C section, W is the clamp length along the conductor and H is the depth of the C. We keep improving our products and some dimensions may be updated, so please confirm the final dimensions with our specialists before you buy.
Dimensional drawing of the copper C clamp
Download the dimensional drawing (PDF)
Technical drawing of the C clamp
Download the technical drawing (PDF)
Click to view enlarged
C clamp applications in earthing systems
- Taking a branch from the main bare copper conductor of the earthing network to connect equipment, panels and metal frames, without cutting the main conductor
- Parallel joints and run extensions of two copper conductors in the earthing networks of substations and industrial facilities
- Connecting bonding conductors of structures, cable trays and equipment to the main earth conductor
- Where exothermic welding is not possible or economical and the connection will not be opened
Execution schematic of a branch joint with a C clamp
Download the execution schematic (PDF)
C clamp installation and pressing steps
- Choose the C clamp code from the code table by the cross-sections of the main conductor (A) and branch conductor (B). Both conductors must fall within the range of the same code.
- Clean the strands of both copper conductors at the joint with a wire brush until bright copper shows. The inside of the C clamp must also be clean and free of grease.
- Fit the C clamp onto the main conductor without cutting it. The main conductor sits in the larger part of the C.
- Place the branch conductor in the smaller part of the C, beside the main conductor, with its end protruding slightly past the edge of the clamp.
- Fit the die matched to the clamp size onto the dedicated C clamp press. Do not use any other die.
- Centre the clamp in the die and press until the two die jaws meet fully. On long clamps, make a second press beside the first with a slight overlap.
- After pressing, check that the C has closed fully, that there are no cracks and that both conductors are firmly held.
Download the installation steps (PDF)
C clamp press and die
The C clamp (copper compression clamp) closes with a dedicated C clamp press, manual hydraulic or electric, and a die the same size as the clamp. The die compresses the clamp into an oval shape and locks both conductors inside it. To choose the right press and die for your project, please contact our specialists.
Inspecting a C clamp compression connection
A compression connection needs no retightening. During periodic inspection of the earthing system, check that the C clamp and conductors look sound and are free of corrosion or mechanical damage.
C clamp enquiries
When you enquire, tell us the connection type (branch or parallel), the cross-sections of the main and branch conductors and the quantity you need, and our specialists will recommend the right code.
Click to view enlarged
In a C clamp, also known in the market as a C-clamp or copper compression clamp, the press and die set the connection pressure, not the installer's hand, so on a project with hundreds of branches every connection closes the same way. There is no bolt to loosen over time either. The clamp's copper matches the copper conductor, and after pressing, the strands of both conductors are compressed and locked inside the clamp. If the connection will not be opened and exothermic welding is not possible or economical, the C clamp is a reliable, fast choice.
Advantages of the copper compression C clamp
- Permanent, bolt-free connection: there are no bolts or nuts to loosen with vibration, temperature changes or time.
- Consistent quality across all connections: the press and die set the pressure, so installer skill has less effect on connection quality.
- Copper-to-copper contact: the C clamp matches the conductor material, and after pressing, the strands of both conductors are compressed and locked in the copper body.
- The main conductor stays continuous: the branch is taken without cutting the main conductor.
- Fast installation, no flame or heat: unlike exothermic welding, it needs no graphite mould, weld powder or dry conditions, and it installs in any weather.
- Easy to inspect: a fully closed C after pressing shows at a glance that the connection is correct.
C clamp compared with bolted clamps and exothermic welding
Feature | C clamp (compression) | Bolted clamp | exothermic welding |
|---|---|---|---|
Connection type | Permanent; does not open | Can be opened and re-closed | Permanent; the two conductors melt and fuse into one |
Installation tools | Press and a die the same size as the clamp | Spanner, preferably a torque wrench | Graphite mould, weld powder and igniter |
Main quality factor | The correct clamp, die and press, and a full press | Tightening the bolt to the correct degree during installation | Dry, clean mould and conductor, and a hot mould |
Check after installation | Fully closed C and firmly held conductors | Visual inspection; periodic tightening is not recommended | Weld appearance: one piece, copper-coloured and free of voids |
Flame and heat | No | No | Yes (exothermic reaction) |
Weather conditions | In any weather | In any weather | Mould and conductor must be dry |
Best location | Accessible branches and parallel joints | Inspection points and disconnection for measurement | Connections buried in soil |
IEEE 837 and IEC 62561-1 judge connections by performance, not by how they are made: every type of connection, whether compression, bolted or welded, must keep its electrical resistance within the permitted range after heating and cooling cycles, corrosion and short-circuit current. So the choice between these three methods depends on the connection location, the need to open it and the site conditions.
If these conditions apply to you, see these clamps as well
Clamp | When |
|---|---|
When the connection must stay removable and close with a spanner. | |
When no press is available or the connection closes in a very tight space. | |
Single-bolt parallel clamp for connecting two conductors to metal structures (PTEC) | When two conductors must also connect to a metal structure at the same time. |
Compare all our earthing clamps in the "Which clamp should we choose?" table.
Like all our earthing clamps, the KALOT C clamp is designed and made to IEC 62561-1, the standard that sets the requirements for connection components of lightning protection and earthing systems, including clamps. Under this standard, connection components are assessed for lightning current in two classes, H (heavy) and N (normal), after first being exposed to corrosive salt mist and a sulphurous atmosphere, so that the behaviour of the connection over time becomes clear.
IEC 62305-3 and BS 7430 call for periodic inspection of the earthing system, so bolted connections should sit where they can be seen, tightened and, if needed, opened for measurement, for example inside an inspection pit or on the structure.
Copper C clamp for earth wire branches and parallel joints
Documents & Downloads
Drawings & schematics
- Dimensional drawing of the copper C clamp (CCC) | dimension table for 23 codesLanguage: Persian (opens in a new tab)
- Technical drawing of the copper C clamp (CCC) | section A-A and dimension tableLanguage: Persian (opens in a new tab)
- Working schematic of the C clamp | branch connection and parallel connectionLanguage: Persian (opens in a new tab)
- C clamp installation in five stepsLanguage: Persian (opens in a new tab)
Frequently Asked Questions
What conductor sizes does the C clamp suit?
It suits stranded copper conductors of earthing and bonding systems, from 1.5 to 240 mm². Each code is made for a range of main and branch conductor cross-sections, and both conductors must fall within that range.
What is a C clamp (C-clamp) and what is it used for?
A C-shaped copper part that holds the main and branch conductors side by side and is pressed onto them to form a permanent connection. It takes a branch from the main earth conductor without cutting it and also joins two conductors in parallel.
What tool is used to press a C clamp?
With a dedicated C clamp press and a die matched to the clamp size. The wrong die produces an incomplete connection.
Can a C clamp be opened after pressing?
No. A C clamp closes under a press and is meant for connections that will not be opened. For a removable connection, see the two-bolt parallel clamp or the split bolt.
How do we choose the right C clamp size?
Choose by the cross-sections of the main conductor (A) and branch conductor (B); both must fall within the range of the same code. For example, for a 50 mm² main conductor and a 25 mm² branch, code CCC 5050 is the right fit.
What is the difference between a C clamp and exothermic welding?
Both make permanent connections. A C clamp installs without flame in any weather and suits accessible branches. For connections buried in soil, exothermic welding is the choice.
Is the copper C clamp also suitable for aluminium conductors?
The KALOT C clamp is copper and made for copper conductors. For aluminium conductors, please speak to our specialists.
Have a Technical Question?