Short answer: in a TT system, the transformer star point is connected to earth and equipment bodies connect to the building's own earth electrode, separate from the network earth. The network brings only the phases and neutral. Because fault current has to return through the soil between two electrodes, it is usually too small to trip a breaker or fuse, which is why TT needs a residual current device (RCD).
Structure of the TT system
In the building's board, the protective conductors of all circuits go to the earth bar and from there to a local earth electrode, such as a copper-bonded earth rod or an earth pit. The network neutral does not connect to this bar. This is why TT is also known as "local earth".
The protection condition and the role of the residual current device
Under IEC 60364-4-41, a TT system must meet this condition:
RA × IΔn ≤ 50 V
where RA is the combined resistance of the earth electrode and protective conductor, and IΔn is the rated current of the residual current device. In other words, when the device operates, the voltage on the equipment body does not exceed 50 V. The disconnection time is 0.2 seconds for final circuits on a 230/400 V network and at most 1 second for distribution circuits. Article 13 of the Earthing System Safety Code (1401) also makes the residual current device mandatory in TT.
With a 30 mA device this condition is met even at a fairly high earth resistance, but the resistance must also stay stable in the dry season. That is why we take the electrode down to the moist soil layer, use GIM ground improvement material in high-resistivity soil, and fit an inspection pit for inspection and measurement (earth resistance measurement).
Advantages and drawbacks of the TT system
- Independent of the network earth conductor: a break in the network neutral does not put a dangerous voltage on equipment bodies, because they are not connected to the neutral.
- Simple to install far from the network: well suited to standalone buildings, villages, telecom sites and temporary facilities.
- Reliant on the residual current device: if the device fails or is bypassed, protection is effectively lost, so its test button must be pressed periodically.
- Needs a good electrode and periodic testing: earth resistance changes with the season and with corrosion.
- Overvoltage: the potential difference between the network earth and the building earth during a fault or lightning strike makes a suitable power SPD all the more important.
Where TT sits among earthing systems
Each system's name has two or three letters. The first letter says how the source (the transformer star point) relates to earth: T means directly earthed, and I means isolated from earth or earthed through a high impedance. The second letter says where the metal enclosures of equipment connect: N means to the earthed point of the source through a protective conductor, and T means to the site's own earth electrode. A third letter appears only in the TN family: S means neutral and protective conductor are separate, and C means both share one conductor, called PEN.
System | Neutral and protective conductor | Protection against electric shock | Where you find it |
|---|---|---|---|
Separate from source to load | Circuit breaker or fuse, with Zs × Ia ≤ U0 | Factories and large buildings with their own substation | |
One PEN conductor | Circuit breaker or fuse; a residual current device will not work | Distribution networks and older installations | |
PEN up to the intake, then separate | Circuit breaker or fuse, plus a residual current device after the split point | Most buildings fed from the public network | |
TT | Neutral from the network; protective conductor to the site electrode | Residual current device, with RA × IΔn ≤ 50 V | Buildings and installations far from the network or on a separate earth |
Source isolated from earth; enclosures on the site electrode | Insulation monitoring for the first fault, disconnection on the second | Operating theatres, mines and industries where sudden loss of power is not acceptable |
For an overview, see types of earthing systems and specifying a protective earthing system.
At KALOT Group we carry out earthing and bonding design and earthing system measurement and testing, and we offer the components, from copper-bonded earth rods and earth bars to green and yellow earth conductors and polyethylene inspection pits. To choose the right system, send our engineers your single-line diagram and supply type, or get in touch through our contact page.





