Earthing System Testing and Earth Resistance Measurement

At KALOT Group we test earthing systems and measure earth resistance to assess the condition of the earthing, the continuity of protective paths and compliance with design and operating requirements. We choose the test method and interpret the results according to the type of installation, the supply arrangement and the site conditions, and in line with the relevant references, including IEEE 81, BS 7430 and the requirements of IEC 60364-6 for low-voltage installations.


Earthing system testing with a suitable method and a record of the measurement conditions.

Our earth testing and earth resistance measurement services

Figure 1. Each method measures a different quantity, and the choice depends on the earthing system layout and site conditions.
  • Initial review and test planning: We review the documents, the earthing arrangement and the condition of accessible components. We then set the measurement points, the test method and the safety measures, including any need to disconnect connections, in coordination with the site operator.
  • Earth resistance or impedance measurement: We select and apply the right method, including fall-of-potential and selective or clamp methods, after confirming the conditions for its use. We define the quantity to be measured and consider the effect of parallel paths, given how the electrodes and earth grid are connected.
  • Continuity of protective and bonding conductors: We test the electrical continuity of earthing paths, protective conductors and bonding connections, and assess the resistance of each path against the conductor data, the condition of the connections and the design requirements.
  • Measurement quality control: We check that the equipment suits the test, the measuring range and the accuracy required, and that it is working correctly and within calibration. We also review the layout of the auxiliary electrodes, the repeatability of readings, and the effect of electrical interference and site conditions on the results.
  • Protective performance requirements: Depending on the protection method, we check automatic disconnection of supply in low-voltage installations by assessing fault loop impedance and testing residual current devices (RCDs). On projects where it applies, we also measure and assess touch and step voltages within the agreed scope.
  • Technical report and corrective recommendations: We record the test method and reference, equipment details, measuring frequency where relevant, test points and how the system was connected. Results are presented with units, conditions and test limits, and compliance is assessed against the applicable standard, the approved design requirements and the protection operating conditions. Where needed, we recommend corrective action and a retest.
Figure 2. A reading at about 62% of the distance, with two check readings either side of it, shows the measurement lies in the valid flat zone (curve is illustrative).
Figure 3. In low-voltage installations, fault loop impedance and RCD operation are checked so that automatic disconnection of supply occurs within the permitted time (IEC 60364-6).

A sample of our reports

We carry out these tests with leading instruments from Chauvin Arnoux, Metrel and Megger for high accuracy. They are built for exactly this work and always hold valid calibration certificates. The image below is a sample of the report we hand to our clients.

Sample of the report we deliver after earthing system testing (sample data).