KALOT Group
This translation is an AI-assisted draft pending human review. It is not indexed for search yet.Read the reviewed Persian original
Earth inspection pits

Complete Product Overview

Polyethylene earth pit (earth inspection pit)

Last updated:

The KALOT Group polyethylene earth pit (code PE 3030) is installed over the top of an earth rod or earth pit and keeps the joint between the earth electrode and the conductors within reach for inspection, testing and resistance measurement, with no digging. The body and cover are black polyethylene, made from virgin polymer resin with no recycled material and a UV-resistant additive. The reinforced 250 × 250 cover, with the KALOT mark and earth symbol, sits level with the ground and is fastened with two recessed Allen bolts. The standard bar is 304 stainless steel, 238 × 30 × 5 with four 10 mm holes. It stands upright on the diagonal in two slots on the pit's inner rim and connects the earth rod conductor to the building conductor, the lightning protection down conductor or the next pit. We also make bare or tinned copper bars to order. The pit is made to IEC 62561-5. Three samples were load tested at the Razi Metallurgical Research Centre to IEC 62561-5:2023, and the pit passed in heavy class (H) at a load of 30 kN. The polyethylene earth pit is one of KALOT Group's best-selling products and is also exported to markets abroad. We can also recommend the right bar, clamps and cable lugs.

The floor of this earth chamber is open and slotted so the earth rod can pass through, and its 300 × 300 base flange, with the concrete that is always poured around the pit, holds it firmly in place. The pit's 238 × 30 × 5 earth bar, with four 10 mm holes at 40 mm spacing, is made as standard from 304 stainless steel, and we also make bare or tinned copper versions to order. The number, diameter and spacing of the holes can change to suit the order and the project. The earth bar and its stainless steel bolts, nuts and washers are supplied separately. To see a three-dimensional view of how this pit is installed and executed, click here. You will find the table "Concrete or polyethylene earth pit: a comparison" under the "Why an earth pit?" tab on this page or on the concrete earth pit page.

Earth pit inspection point, level with the ground

The pit sits over the earth rod and keeps the joint between the electrode and the conductors always within reach. To inspect or measure, you simply open the cover.

  • Heavy load class (H), 30 kN; IEC 62561-5:2023 test on three samples
  • Open floor for the earth rod to pass through
  • 304 stainless steel bar with four holes, set diagonally in two slots on the inner rim
  • Lightweight polyethylene (1.8 kg) from virgin resin with a UV-resistant additive
  • Bar seating

    Two slots on the inner rim hold the 238 × 30 × 5 bar upright on the diagonal, so conductors can be fixed with cable lugs on its four 10 mm holes. The standard bar is 304 stainless steel and is supplied separately.

  • Open floor and wide flange

    The earth rod passes through the slotted floor, and the 300 × 300 base flange holds the pit firmly in the surrounding concrete.

  • Heavy load class (H), 30 kN

    Three samples of this pit were load tested at the Razi Metallurgical Research Centre to IEC 62561-5:2023 (clauses 4.1 and 6.4), and the pit passed in heavy class (H) at a load of 30 kN (about 3 tonnes). The seating and the concrete around the pit must suit the installation location. For vehicle routes, please agree the location with our specialists.

    Load test report (PDF)Website membership required · Sign in or join
  • Drawings and datasheet

    You have the dimensional drawing, technical drawing, exploded view, execution schematic, installation steps and earth rod connection methods as PDF files alongside the datasheet, and a three-dimensional view on this page.

    Polyethylene earth pit datasheet (PDF)
  • Advice from KALOT Group specialists

    Along with the pit, our specialists recommend the right clamps, bar and cable lugs for your installation location and conductor types.

Technical Product Information

Click to view enlarged

Feature

Value

Type

Earth electrode inspection pit (earth inspection chamber)

Code

⁦PE 3030⁩

Body and cover material

Black polyethylene from virgin polymer resin, no recycled material, with a UV-resistant additive

Pit dimensions

⁦300 × 300 × 205 mm⁩

Cover

Reinforced 250 × 250 mm cover with the KALOT mark and earth symbol, fastened with two recessed stainless steel Allen bolts in opposite corners

Base flange

300 × 300 mm, rounded corners, with reinforcing ribs

Body

Cylindrical, 190 mm diameter and about 150 mm long

Total height

⁦205 mm⁩

Weight

⁦1.8 kg⁩

Standard

To IEC 62561-5

Tested load rating

Heavy class (H), 30 kN; load test on three samples at the Razi Metallurgical Research Centre to IEC 62561-5:2023 (clauses 4.1 and 6.4), with no cracking

Bar seating

Diagonal, in two slots on the inner rim; the bar stands upright

Bar (supplied separately)

304 stainless steel (standard); bare or tinned copper to order

Bar dimensions

⁦238 × 30 × 5 mm⁩

Bar holes

4 Ø10 holes at 40 mm spacing (standard); the number, diameter and spacing of holes can change to suit the order and the project

Bar bolts and nuts

Stainless steel bolts, nuts and washers; supplied separately

Base

Slotted, for the earth rod to pass through

Installation location

Over the top of an earth rod or earth pit, level with the finished ground

Sizes

Model

Base flange A (mm)

Top and cover B (mm)

Body diameter D (mm)

Overall height H (mm)

⁦PE 3030⁩

⁦300 × 300⁩

⁦250 × 250⁩

⁦190⁩

⁦205⁩

Dimensions are in millimetres. The cylindrical body extends about 150 mm below the base flange, and after installation the top of the cover is level with the finished ground. We keep improving our products and some dimensions may be updated, so please confirm the final dimensions with our specialists before you buy.

Dimensional drawing

Dimensional drawing of the polyethylene earth pit.

Download the dimensional drawing (PDF)

Technical drawing

Technical drawing of the polyethylene earth pit.

Download the technical drawing (PDF)

Exploded view

Exploded view of the polyethylene earth pit with a parts list.

Download the exploded view (PDF)

Pit construction

The pit has two parts: a one-piece body and a cover. The body consists of a wide base flange with reinforcing ribs, which holds the pit in the surrounding concrete, and the cylinder below it, which sits over the earth rod. The reinforced square cover is fastened to the body with two recessed Allen bolts in opposite corners. The floor of the cylinder is slotted so the earth rod can pass through, and two slots on the inner rim hold the bar upright on the diagonal, so conductors can be fixed to it with cable lugs.

KALOT Group polyethylene earth pit; a 250 × 250 reinforced cover with the KALOT mark and the earth symbol, a 300 × 300 base flange and a cylindrical body.

Three-dimensional view of polyethylene earth pit installation

The pit over an earth rod in the soil, with sand bed, concrete around the pit, bar and conductors, plus cutaway, cover opening, earth rod connection methods and parts list.Open full screen

Frequently Asked Questions

What is a polyethylene earth pit and what is it used for?

It is a small polyethylene chamber installed over the top of an earth rod or earth pit, level with the ground. It keeps the joint between the earth electrode and the conductors within reach for inspection and resistance measurement, with no digging.

What are the pit's dimensions and weight, and how deep does it go into the soil?

The code for this pit is PE 3030 and it measures 300 × 300 × 205 mm: cover 250 × 250, base flange 300 × 300 and body diameter 190 mm, with a weight of 1.8 kg. It is installed so that the top of the cover is level with the finished ground and the body sits down to a depth of 205 mm below it.

Why is the floor of the pit open, and how does the earth rod pass through it?

The floor of the body is slotted so you can set the pit over an earth rod that has already been driven, with the rod passing through the centre of the floor. The top of the earth rod and its clamp stay inside the pit and within reach.

How does the bar sit inside the pit, and how many conductors connect to it?

The 238 × 30 × 5 earth bar is supplied separately and stands upright on the diagonal, in two slots on the pit's inner rim. The standard earth bar is 304 stainless steel with four 10 mm holes at 40 mm spacing. We also make bare or tinned copper earth bars to order, and the number, diameter and spacing of the holes can change to suit the order and the project. Each hole takes one conductor with a cable lug, for example the earth rod conductor, the lightning protection down conductor, the building conductor and the conductor to the next pit. The earth rod conductor goes on an end hole so it is easy to undo for testing. We also supply matching stainless steel bolts, nuts and washers separately.

How is the cover fastened?

The reinforced square cover is fixed to the body with two recessed stainless steel Allen bolts in opposite corners. The bolt heads sit inside the cover, and the KALOT mark and earth symbol on the cover show where the earth electrode is.

What load can a polyethylene earth pit carry?

Three samples of this pit were load tested at the Razi Metallurgical Research Centre to IEC 62561-5:2023, and the pit passed in heavy class (H) at a load of 30 kN (about 3 tonnes). The standard defines light class (L) at 4 kN for pavements, medium class (M) at 15 kN for slow passenger car traffic and heavy class (H) at 30 kN for slow multi-axle vehicle traffic. The seating and the structure around the pit must suit the installation location. Always pour concrete around the pit, and for vehicle routes please agree the location with our specialists.

Which is better, a polyethylene or a concrete earth pit?

At 1.8 kg the polyethylene pit is far lighter and easier to move and place. It is made from virgin polymer resin, its edges do not chip in handling, its open floor sits over the earth rod and its tested load class is heavy (H). The concrete earth pit weighs 21.2 kg, has a medium (M) load rating of 15 kN and takes a 300 × 50 × 5 bar. The choice depends on the installation location and the method of execution.

Why must concrete be poured around the pit?

Concrete around the pit holds it in place, so over time it does not tilt or shift with soil settlement or passing loads, and the cover always stays level with the ground.

How do we measure earth pit resistance from inside the pit?

Open the cover and undo the earth rod conductor's cable lug from the bar, so the earth rod is isolated from the rest of the system. Measure its resistance with an earth resistance tester, record the result and reconnect the joint.

What information should we send for a quote?

Send us the number of pits, the installation location, the earth rod diameter, the conductor types and the material and number of holes of the bar, and our specialists will propose the clamps, bars and cable lugs and give you a price.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.