Earthing and lightning protection for steel plants and mines

A steel plant or mine is the toughest environment an earthing system can face. Furnace currents reach tens of thousands of amperes, machinery vibrates non-stop, dust and heat wear down the joints, and in rocky ground an earth rod is hard to drive. Tall structures often stand on open plains or mountainsides, making them the first target for lightning. We have worked alongside clients on more than 40 steel, iron ore and copper projects. On this page we first look at the real weak points and needs of this industry, then show which need our work on these projects has answered.

+40Steel, iron ore and copper projects
3Value chain: steel, iron ore and copper
8Common weak points covered on this page

Earthing weak points and needs in steel and mining

Each card is a common problem: what happens, what it costs and what to do.

1Melt shop, arc furnace and induction furnace

The problem

An arc furnace produces very high currents, harmonics and transient overvoltages. In an induction furnace, if molten metal penetrates the refractory and reaches the coil, an earth fault occurs, and this fault usually comes before a metal run-out from the furnace.

Consequence

Dangerous step and touch voltages beside the furnace, transformer damage and melting stoppages.

Our answer:
A meshed earthing grid under the melt shop with step and touch voltage calculations, bonding of the furnace shell and platforms to one common earth, and a furnace earth fault detector tested every shift.

Reference: IEEE 80 and IEEE 81

2Rolling mill, large drives and motors

The problem

The drive's common-mode voltage builds up on the motor shaft and discharges through the bearing. Little by little, the bearing surface becomes grooved.

Consequence

Vibration, early bearing failure and sudden rolling line stoppages.

Our answer:
Low-impedance bonding between motor, drive and the earthing network using wide conductors or tape, and shaft earthing rings on sensitive motors.

Reference: IEEE 1100

3Overhead crane and rails

The problem

Wheel-to-rail contact is not a reliable earth path, because dust, oil and corrosion interrupt it.

Consequence

The crane body stays live during a fault, putting the operator and maintenance staff at risk of electric shock.

Our answer:
A separate bonding conductor for the crane, and connection of the rails at both ends and across joints to the hall's earthing network with earthing and bonding clamps.

Reference: industrial electrical rules for cranes (NEC 610)

4Rocky soil and drought

The problem

An earth rod cannot be driven into rock. In drought, bentonite cracks and pulls away from the electrode, and earth resistance rises in the hot season.

Consequence

A system that was fine on handover day no longer carries fault current to earth a few years later.

Our answer:
Soil resistivity measurement before design, horizontal electrodes or deep wells, GIM ground improvement material and KALweld® exothermic welding for every buried joint.

Reference: IEEE 81 (Wenner method), IEC 62561-7

5Explosives magazine and blasting

The problem

Lightning and stray currents can set off detonators. If the conductive parts of the magazine are not bonded, sparks jump between them.

Consequence

Unintended detonation and risk to life.

Our answer:
Bonding and earthing of every conductive part of the steel magazine, a lightning protection system with regular inspection, and stopping blasting when a thunderstorm approaches. The blasting circuit itself is deliberately left unearthed and must not be tied to the facility earth.

Reference: IEC 62305-3 and mine safety regulations (MSHA 30 CFR 57.6132)

6Conveyors, overhead lines and remote control equipment

The problem

Conveyors and long lines expose a large area to lightning. A strike even hundreds of metres away induces voltage on control and telecom cables.

Consequence

Burnt-out PLC cards, sensors and radios, and a halted materials handling line.

Our answer:
A combination of five layers: structural lightning protection, earth electrode, equipment earthing, equipotential bonding, and power surge protective devices (SPDs) and data line SPDs at both ends of the cables.

Reference: IEC 62305-4 and IEC 61643

7Mobile mining machinery and substations

The problem

The supply cable of mobile equipment is constantly dragged and moved, and its earth conductor can break. A rubber-tyred machine parked in the open is also a lightning target.

Consequence

A live machine body and, in reported incidents, tyre explosions a few minutes after a lightning strike.

Our answer:
An earth conductor of adequate cross-section in the trailing cable, earth continuity monitoring, and a procedure for parking and moving people away during thunderstorms.

Reference: MSHA 30 CFR 77.906 and 57.12027

8Loose connections, separate earths and no testing

The problem

These three are the most common inspection findings. Bolted joints work loose with vibration and corrosion. A separate "clean earth" for instrumentation develops a potential difference from the main earth during lightning. And a surge protective device at the end of its life drops out of the circuit silently.

Consequence

A system that is complete on the drawing but does not work on the day of the incident.

Our answer:
Exothermic welding for buried joints, all earths integrated into one network, surge protective devices with status indicators and alarm contacts to the PLC, and annual testing with results recorded for comparison.

Reference: IEEE 837, IEEE 1100, IEC 62305-3 (Annex E)

A look at our work in this industry

We have matched each of the needs above with a service we have delivered on steel and mining projects.

What we have learned from these projects

Integrated earthing is cheaper from day one. In plants where halls were built in several phases, each section often has its own separate earthing. Connecting them after commissioning means digging and shutdowns; if it is planned into the design from the start, the cost is a small fraction of a later fix.

In mining, soil measurement comes first. Soil resistivity at a mine can vary several times over from one spot to the next. A design based on a single average figure will not work in the rocky areas.

Buried connections should be welded. In high-vibration, corrosive environments, a bolted joint underground cannot be seen and slowly fails. Exothermic welding removes this weak point at its root.

Some of our projects in steel, iron ore and copper

Steel and ironmaking: Hormozgan Steel, the melting and casting division of the National Steel Group, Hengam Industrial Supply (Khuzestan Steel), Bistoun Iron Smelting Complex, Kavir Damghan Steel, Bonab Industrial Steel and the oxygen plant of Shahriar Bonab Steel, Esfarayen Steel, Paya Steel, Tabarestan Steel Casting, Loushan Iron and Steel, Petro Foulad Bahman, Foulad Technic Isfahan, Yazd Alloy Steel and Kavir Kashan Steel

Iron ore, concentrate and pellets: Gol-e-Gohar Iron Ore Complex, Chadormalu Mining and Industrial Company, Sangan Pelletising, Zarand Steel Concentrate Complex, Iron Ore Concentrate Development 2 in Zarand and Sirjan, Tang-e Zagh Iron Development and Processing, Kavir Iron Ore, and Abhar Hematite Iron Ore Concentrate

Copper and non-ferrous metals: Sungun Copper, Sarcheshmeh Copper, National Iranian Copper Industries Company, Gohar Mes Industries and Mines Development, Jolgehaye Asemani copper mine, NIPEC non-ferrous processing, Non-Ferrous Metals Mining and Smelting Development, the Rasht copper wire plant and the Donyaye Mes plant in Kashan

Outside Iran: Borly mine project, Kazakhstan

What to send for design and a quotation

  • Soil resistivity measurements for each area (if you do not have them, we carry out the measurements)
  • Layout of the plant or mine, shed dimensions and the heights of stacks, silos and towers
  • Locations of furnaces, transformers, substations and crane runways
  • Lengths of conveyor belts and overhead power and telecom lines
  • Construction type of the explosives store (metal or masonry)
  • The latest earthing system test report, if you are upgrading an existing system

Frequently Asked Questions

What can be done in rocky ground where an earth rod cannot be driven?

Instead of a driven earth rod, horizontal electrodes are laid in a trench or a drilled borehole, with ground improvement material packed around the electrode. Joints are made by exothermic welding so they do not loosen underground.

Why doesn't bentonite always work at a mine?

Bentonite needs moisture to work. In a drought it shrinks, cracks and pulls away from the electrode, and earth resistance rises. In dry soil, the right choice is a ground improvement material that does not depend on moisture.

Is crane wheel contact with the rail enough to earth the crane?

No. Dust, oil and corrosion make that contact unreliable. The crane needs a separate bonding conductor, and the rails are connected to the earthing grid at both ends and across the joints.

How often should a mine's earthing system be tested?

Common practice is an annual test, plus a test after every repair or change. Structures with an explosion hazard, such as explosives stores, need shorter inspection intervals. Each test result is recorded so the trend in resistance can be seen.

Do instrumentation and PLCs need a separate earth?

A separate earth with no link to the main earth creates dangerous potential differences during lightning and faults. The right practice is a single integrated earthing grid, with instrumentation connected to it at one defined point.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.