Soil Resistivity Measurement
At KALOT Group we measure soil resistivity in line with the relevant references, including IEEE 81, BS 7430 and ASTM G57, and according to the scope of each reference, the site conditions and the project requirements. The result is reliable soil resistivity data: the technical basis for choosing the type and layout of electrodes and for calculating the earthing system.
Our soil resistivity measurement services
- Site review and survey planning: We review the project area, access conditions and buried services. We then set the position and direction of the survey lines and the range of electrode spacings to suit the size of the earthing system and the design needs.
- Field measurements: We carry out the survey using recognised arrangements, including the four-electrode Wenner method, in line with the chosen test reference. We record the geometry, the depth of the test electrodes, and the measured values and units.
- Quality control and data validity: We check that the instrument is working correctly and within calibration, and we check the contact resistance of the test electrodes and the repeatability of readings. We also look at how electrical noise, buried conductors and existing earthing systems affect the results, and repeat the survey where needed.
- Site conditions and seasonal factors: We record the environmental conditions, the state of the ground and the time of the test. We also consider seasonal effects on how the results are used in design, based on documented data and assumptions.
- Interpreting results and modelling the soil: We calculate the apparent soil resistivity and analyse how it changes with electrode spacing. We then present an equivalent electrical soil model, uniform or layered, to suit the data available and the design needs, and assess how well it matches the survey results.
- Technical report and design data: The report covers the method and edition of the test reference, survey locations and layouts, equipment details, test conditions, and raw and calculated data with units. Design parameters are delivered in ohm-metres (Ω·m), together with the assumptions and limits of the model and how the results should be applied.
A sample of our reports
We carry out these measurements with leading instruments from Chauvin Arnoux, Metrel and Megger for high accuracy. They are built for exactly this work and always hold valid calibration certificates. The image below is a sample of the report we hand to our clients.
Related articles and services
To learn more, read what soil resistivity is and how it is measured. The results feed directly into earthing and bonding system design and consultancy.
Press the “Request a Technical Consultation” button and our engineers will contact you to discuss your project.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.
