Short answer: bentonite in itself is neither a banned nor a "non-standard" material. BS 7430:2026 lists bentonite among the acceptable fillers around an earth electrode, provided it is fully hydrated during installation. But being "standard" is a property of a product, not of a name: any ground improvement material, bentonite-based or carbon-based, is standard when it has passed the IEC 62561-7 tests. Bentonite works well in moist soil; its main weakness is that it shrinks in dry soil and pulls away from the electrode.
In this article, we at KALOT Group explain what earthing bentonite is, its advantages and limits, where it is a good choice and how it should be installed.
What is earthing bentonite?
Bentonite is a natural clay made mostly of the mineral montmorillonite, formed by the breakdown of volcanic ash. The sodium type used in earthing systems swells to several times its dry volume when mixed with water (up to about 13 times in technical sources), sticks to the electrode surface and the wall of the hole, and draws moisture from the surrounding soil.
Bentonite's conductivity is ionic: current passes through water and the mineral ions inside the clay. According to IEEE Std 80, the resistivity of bentonite at very high moisture is about 2.5 ohm-metres, and because these ions are part of the clay itself, they do not wash out as easily as salt. This dependence on water is both bentonite's strength and its weakness. You can read more about the role of moisture in earth resistance in Is soil moisture the key factor in lowering earth resistance?
Is bentonite a standard material?
The answer has two levels:
- Bentonite as a type of material: BS 7430:2026 (clause 8.14.2) treats bentonite as a "moisture-retaining clay" and an acceptable filler, and says it suits soils whose moisture changes during the year. The Australian and New Zealand standard AS/NZS 1768 also presents bentonite as a mild filler that creates a uniform, non-corrosive environment around the electrode, while it rejects salts because they wash out and cause corrosion.
- A specific bentonite product: to call a particular bag a "standard ground improvement material", it must have a test report to IEC 62561-7: resistivity, corrosion assessment, sulphur below 2 percent, leaching and pH. The Earthing System Safety Regulation (1401), in Article 63, also requires additives to be tested to the national standard. Details of these tests are in The standard for ground improvement materials.
So the statement "bentonite is a non-standard material" is not accurate. It is more accurate to say that bentonite without a test report, like any other ground improvement material without one, is not approved.
Advantages and disadvantages of bentonite in earthing systems
Advantages of bentonite:
- Cheap and easy to get: bentonite is a common mineral with a low price.
- Holds moisture: it absorbs moisture from rain and the surrounding soil and keeps it for a while, so in soils with seasonal moisture changes it helps keep resistance stable.
- Good contact with the electrode: as it swells, it fills the gaps between the electrode and the wall of the hole. This is why bentonite slurry has long been a common filler for holes drilled in rocky ground.
- Low corrosion in the low-salt type: IEEE Std 80 describes bentonite as non-corrosive and stable. A university study (Industrial University of Santander, Colombia, 2017) also measured the lowest copper corrosion rate in low-salt bentonite.
Disadvantages and limits of bentonite:
- Dependence on moisture: as moisture falls, the resistivity of bentonite rises quickly.
- Shrinks when dry: according to IEEE Std 80, bentonite in a very dry environment may shrink, pull away from the electrode and raise the electrode's resistance. BS 7430:2026 (clause 8.2.2) also says the filler around the electrode must be chosen and installed so that it does not shrink, swell or separate from the electrode after drying.
- Salted bentonite: some products sold as "earthing bentonite" or "active bentonite" may contain added salt or chemicals. In the same study, the highest copper corrosion was seen in salt-added bentonite (Ground improvement materials and earthing system corrosion).
- Higher resistivity than carbon materials: even at its best, the resistivity of bentonite is several times that of good carbon-based ground improvement materials.
Bentonite or carbon-based ground improvement material?
Feature | Bentonite | Carbon-based ground improvement material (such as GIM) |
|---|---|---|
Conduction type | Ionic; depends on moisture | Electronic (through carbon particles); low dependence on moisture |
Resistivity | About 2.5 ohm-metres at very high moisture; more when dry | Below 0.5 ohm-metres for GIM |
In dry soil | May shrink and separate from the electrode | Stays hard and monolithic |
Best use | Moist soil and high-rainfall areas | Dry, sandy, rocky and high-resistivity soil |
Cost | Lower | Higher, with longer life and greater stability |
A full comparison of all types of ground improvement material is in the Comparison table of ground improvement materials, and carbon materials are explained in Carbon-based ground improvement materials.
Where is bentonite a good choice, and where is it not?
- Suitable: moist, high-rainfall areas such as northern Iran, soil that holds some moisture all year, and drilled holes where the electrode sits deep in moist soil.
- Unsuitable: dry, sandy and well-drained soil, low-rainfall areas and places with a low water table. In these conditions it is better to use carbon-based ground improvement materials.
How should bentonite be installed correctly?
- Pour bentonite as a slurry, not as dry powder: BS 7430:2026 stresses that bentonite must be fully hydrated during installation. Take the water-to-powder ratio from the technical sheet of that product.
- Fill the hole completely: place the electrode in the centre of the hole and pour the slurry so that it fills evenly all around, leaving no voids.
- Add native soil on top and compact it: according to BS 7430:2026, the filler must be compacted to make good contact with the electrode, and surface soil must not mix with the filler around the electrode.
- Do not add salt: adding salt to bentonite or to an earth pit speeds up corrosion (Are salt and charcoal a standard material?).
- Make the joints properly: make underground joints with KALweld® exothermic welding and choose a copper-bonded earth rod for corrosive soils.
When buying, also ask for the IEC 62561-7 test report and the product's salt and chloride content. A simple sign of salt: dissolve a little of the material in a glass of water; if a white layer of salt stays on the glass after the water evaporates, the material contains salt. This is only a sign, not a standard test. The other properties of a good ground improvement material are in Specifications of standard ground improvement materials.
Our recommendation
If the soil on site is always moist and the budget is limited, low-salt bentonite installed correctly can do the job. But for dry, rocky and high-resistivity soils, or when you want earth resistance to stay stable for years without maintenance, we produce the GIM ground improvement material family: GIM for highly corrosive soils and environments, GIM LIGHT for normal conditions, and ECO GIM. Work out the quantity you need with the GIM quantity calculator. See the other types in Types of ground improvement material.