Short answer: Yes. Moisture is one of the most important factors in soil resistivity, and therefore in the resistance of the earthing system. A given soil conducts far better when moist than when dry. In the IEEE Std 142 data, the resistivity of sandy loam falls by about 2.4 times as moisture rises from 10 to 20%, and that of red clay by about 18 times from 12 to 20%. But moisture alone is not enough: water conducts only when it holds dissolved salts and the soil can retain it.

The resistance of an earth electrode (an earth rod or earth pit) depends above all on the resistivity of the soil where it is installed (what soil resistivity is and how it is measured). Resistivity in turn depends on the soil type, dissolved salts, moisture and temperature. In this article, we at KALOT Group use a chart to show how much moisture matters and how earth resistance can be kept stable even in the dry season.

Chart: the effect of moisture on soil resistivity

Resistivity of three soil types against moisture, per Table 4-3 of IEEE Std 142.

This chart is plotted from Table 4-3 of IEEE Std 142 (the IEEE Green Book on earthing of industrial and commercial systems) and shows three soil types from dry to moist. The vertical axis is logarithmic, so each horizontal line is several times the one below it. A few points stand out:

  • Below about 10% moisture, resistivity climbs steeply. Sandy loam is about 1850 ohm-metres at 2% moisture and comes down to about 220 ohm-metres at 10%. Red clay has no value at all in the table below 12%, since even at 12% it is about 1800 ohm-metres.
  • Between 10 and 20%, moisture still has a strong effect. Topsoil goes from 600 to 120 ohm-metres and sandy loam from 220 to 90 ohm-metres.
  • Above about 20%, the curves almost flatten out. More water lowers resistivity a little further, but there is no longer any big jump.

That is why BS 7430:2026 (clause 8.2.1) recommends choosing a location for the earthing system where, ideally, soil moisture is always between 15 and 20%. The figures in this chart apply to those three tested soils; the resistivity of the soil at each site has to be measured.

Why does moist soil conduct better?

Current passes through water and dissolved salts in the soil pores, not through the grains themselves.

Soil grains (sand, silt and clay) are themselves almost non-conductive. According to IEEE Std 142 (clause 4.1.4), soil resistivity is really the resistance of the "electrolyte" within it: current passes through the water in the soil pores and the salts dissolved in it. BS 7430 (clause 8.3) likewise says that soil resistivity is essentially electrolytic and depends on moisture, the ability of the soil to hold moisture, and the type and concentration of salts dissolved in the water.

In dry soil there is air between the grains and no route is left for the current. When the soil becomes moist, a thin film of water surrounds the grains, the soil salts dissolve in it and a continuous conductive path forms.

Why is moisture alone not enough?

IEEE Std 142 makes an important point: water at the surface does not necessarily mean low resistivity. There are several reasons:

  • Water without dissolved minerals is not a good conductor. Conductivity comes from the ions of dissolved salts, so water with little salt gives little conductivity, even if it soaks the soil completely.
  • Running water washes away the soil salts. BS 7430 (clause 8.2.1) says to avoid places where water flows over the surface, such as stream and river beds, because the useful salts in the soil may be washed out completely.
  • Sand and gravel do not hold water. According to BS 7430 (clause 8.14.3.3), sand and gravel are poor conductors and should not be the main backfill around the electrode; they raise the earth resistance, especially when they dry out. The same standard says a waterlogged site is not necessary unless the soil is sandy or gravelly.
  • Climate matters too. Table 2 of the same standard gives the resistivity of clay as 5 to 20 ohm-metres in high-rainfall regions and 10 to 100 ohm-metres in low-rainfall and desert regions.

Good contact between the electrode and the soil also matters. BS 7430 says the soil around the electrode should be rammed and compacted, because the conductivity of soil increases with compaction.

Depth, season and temperature

Take the electrode down to the layer that is always moist; the top 0.5 m is not counted as effective.

The moisture of the upper soil layers changes with the seasons: they dry out in summer and may freeze in winter. According to IEEE Std 142 (Table 4-4), the resistivity of a sample soil at zero degrees goes from about 100 ohm-metres (water) to 300 ohm-metres (ice), and reaches 700 ohm-metres at 5 degrees below zero. For this reason:

  • BS 7430 (clause 8.3) says that any part of the electrode less than 0.5 m below the surface should not be counted as effective.
  • Take the electrode as far as possible down to a layer that is always moist. This is the old advice to "keep digging or driving the earth rod until you reach damp soil". Copper-bonded earth rods can be joined with couplings and driven deeper.
  • Resistance measured in the wet season may rise in the dry season. BS 7430 also says that a value measured long after installation may differ greatly from the initial one. Periodic measurement is therefore necessary (how to measure earth terminal resistance).

One more point: high fault current also heats and dries the soil around the electrode. According to BS 7430, as moisture moves away from the electrode surface the resistance rises, and if the temperature reaches about 100 degrees the electrode effectively stops working. The size and surface area of the electrode must therefore be adequate for the fault current (earth electrode resistance formula).

Watering an earth pit and injecting solutions

Many earth pits have a pipe built in so they can be watered in the dry season. IEEE Std 142 (clause 4.1.7) mentions dripping water through a pipe beside the electrode, and clause 4.4.3 lists "increasing moisture" as one way to bring down resistance that has risen. But watering is a maintenance measure, not a design: if an earthing system reaches the required value only through watering, it will fail in the first dry season or as soon as the watering is forgotten.

Pouring salt water or a "reducing liquid" into the pit is not a lasting solution either. According to IEEE Std 142, salts such as sodium chloride, magnesium sulphate and copper sulphate lower resistance, but they are not permanent, have to be renewed periodically and damage the corrosion protection of the electrode. BS 7430 (clause 8.2.2) also says that chemical treatment of the soil has an environmental impact, raises the risk of corrosion of the earthing system and should not be regarded as a long-term solution. There is more on this in Are salt and charcoal standard materials? and ground improvement materials and earthing system corrosion.

What role does ground improvement material play?

Ground improvement material fills the space around the electrode and completes its contact with the soil. The different types behave differently with moisture:

  • Bentonite: according to BS 7430 (clause 8.14.2.2), this is a clay that holds moisture well and helps where soil moisture rises and falls with the seasons. But it depends on moisture itself and shrinks when dry (Is bentonite a standard material?). BS 7430 (clause 8.2.2) also stresses that the material must stay in contact with the electrode after drying and must not shrink or separate from it.
  • Carbon-based materials: their conductive part is carbon, whose conductivity does not depend on pore water, so they stay more stable in the dry season and do not wash out (carbon-based ground improvement materials).

We produce the GIM family of ground improvement materials in line with IEC 62561-7: GIM for highly corrosive soils and environments, GIM LIGHT for normal conditions, and ECO GIM. A simple calculation of how far a ground improvement material lowers resistance is given in Why are ground improvement materials useful?