Steel bonding cylinder (earth bus) for metal structures
Last updated:
The KALOT Group steel bonding cylinder (earth bus) creates a permanent earth connection point on steel structures. The solid steel cylinder is welded to a column, beam, tank shell or equipment chassis, and the earth conductor is fixed with a cable lug on its M10 stud, so the metal structure connects to the earthing and bonding system with no drilling.
The cylinder body is carbon steel, and the stud, nuts and washers are stainless steel. We make the earth bus in five standard sizes, with a diameter of 40 or 50 and a length of 30 to 50 millimetres, and other sizes to order. To learn about bonding and its role in the earthing system, see our article.
A permanent earth connection point on metal structures
Choose the earth bus to suit the structure and the conductor's cable lug: the cylinder is welded to the steel of the structure and the earth conductor is fixed with a cable lug on its M10 stud.
- A welded earth connection point on steel structures
- Carbon steel body, stainless steel accessories
- M10 stud for the conductor cable lug
- Five EBOS sizes and custom sizes
No drilling in the structure
The cylinder is welded to the surface of the structure, so the column or tank shell is not drilled and its section is not weakened.
A connection that opens and closes
The conductor's cable lug is fixed on the stud and comes off easily for inspection, measurement or replacing the conductor.
Material: carbon steel and stainless steel
The cylinder body is carbon steel so that it welds to the steel of the structure; the double-ended stud, nuts and washers are stainless steel.
Five EBOS sizes and drawings
Steel bonding cylinder datasheet (PDF)The EBOS code table, dimensional drawing, technical drawing, exploded view, execution schematic, installation positions, installation steps and three-dimensional view are all available on this page and as PDF files, alongside the earth bus datasheet.
Advice from KALOT Group specialists
When you enquire, send us the type of structure, the conductor cross-section and cable lug type, and the number of connection points, and our experts will suggest the right earth bus size and stud.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | A welded earth connection point for steel structures |
Body | Solid carbon steel cylinder |
Accessories | Stainless steel: M10 double-ended stud, two nuts, two flat washers and one spring washer |
Thread | M10 |
Sizes | Diameter 40 or 50 and length 30 to 50 mm (five EBOS codes) |
Installation method | Flat face of the cylinder welded to the structure, with a fillet weld all the way round |
Conductor connection | Conductor cable lug on the stud, between two flat washers |
Installation location | Steel columns and beams, tank shells, equipment chassis, steel frames |
Special orders | Cylinder size and accessory size and material to order |
Earth bus sizes (EBOS)
Code | Diameter D (mm) | Length L (mm) | Thread |
|---|---|---|---|
EBOS 5050 | 50 | 50 | M10 |
EBOS 5040 | 50 | 40 | M10 |
EBOS 5030 | 50 | 30 | M10 |
EBOS 4040 | 40 | 40 | M10 |
EBOS 4030 | 40 | 30 | M10 |
Diameter and length are in millimetres; the first number of each code is the diameter and the second the length of the cylinder. Other sizes, and studs to match the cable lug, are made to order. We continually improve our products and some dimensions may be updated, so please confirm the final dimensions with our experts before you buy.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Exploded view
Download the exploded view (PDF)
Structure and accessories
The earth bus is a solid carbon steel cylinder. One face is flat and is welded to the structure; the other has a threaded M10 hole that takes the double-ended stud. On the stud go, in order, the lock nut, flat washer, conductor cable lug, flat washer, spring washer and nut. The lock nut holds the stud in place on the cylinder, and the cable lug is clamped between two washers. The stud, nuts and washers are stainless steel.
Click to view enlarged
Applications of the steel bonding cylinder
- Steel columns and beams: connects steel frame columns to an earth bar or bonding conductor, and connects the down conductor of the lightning protection system to the structure.
- Steel tanks and vessels: an earth connection point on the shells of storage tanks and vessels, for connecting them to the earthing system.
- Equipment chassis and panels: a connection point for protective and bonding conductors on machine chassis, equipment bases and panel frames.
- Building steel frames: main bonding connection points for the building on steel beams and columns.
Installation schematic
Download the execution schematic (PDF)
Installation positions
Download connection modes (PDF)
Earth bus installation steps
- Choose the earth bus size to suit the structure and the conductor's cable lug, and mark the installation spot on the structure, at an accessible height and away from existing welds.
- Grind the spot and a ring around it back to clean metal, removing paint, mill scale, rust and grease.
- Hold the cylinder square to the surface, tack weld it, then run a fillet weld all the way round in line with the project's welding procedure, and remove the slag.
- Cover the cylinder body, weld and ground area with anti-corrosion paint or tape, and keep the front face of the cylinder and the thread clean.
- Screw the double-ended stud into the cylinder and tighten the lock nut against the cylinder face. Then fit the flat washer, cable lug, flat washer, spring washer and nut, and tighten the nut according to the manufacturer's instructions.
- Measure the electrical continuity between the cable lug and the structure and record the result.
Download the installation steps (PDF)
Installation tools
For installation you need a welding machine and an angle grinder for preparation and welding, and a spanner to fit the M10 nut for fixing the cable lug.
Inspection and measurement
During periodic inspections, check the condition of the weld and anti-corrosion coating, the tightness of the nut and the cleanliness of the cable lug contact surface, and measure the electrical continuity between conductor and structure (earth resistance measurement). You can undo the cable lug to take a measurement.
Choosing and pricing an earth bus
To request an earth bus price, send our experts the type of structure (column, tank, chassis), the conductor cross-section and cable lug type, and the number of connection points. If you need another size or thread, tell us that too.
Click to view enlarged
An earth conductor can be connected to a steel structure by drilling and bolting or with a clamp, but drilling a column or tank shell is not always allowed or desirable. With a single weld, the earth bus creates a permanent, uniform connection point on the structure, where the conductor is fixed with a cable lug and can be undone for inspection and measurement.
Advantages of the earth bus
- No drilling: the structure is not drilled and its section stays untouched.
- A permanent, reliable connection: the all-round weld makes the cylinder one with the steel of the structure.
- Easy to inspect: the cable lug is fixed on the stud, and it can be undone for measurement and refitted.
- Stainless accessories: the stud, nuts and washers are stainless steel.
- The right size for every job: five standard sizes, and made to order.
Earth bus or bolted clamp on the structure?
Feature | Earth bus (steel cylinder) | Conductor-to-structure clamp |
|---|---|---|
Fixing to the structure | Cylinder welded to the surface of the structure | Drilling the structure and fitting a bolt |
Conductor connection | Cable lug on the M10 stud | Conductor between the clamp plates |
Suitable for | Structures where welding is allowed | Structures where drilling is allowed |
To connect a conductor to a structure with a bolt and no welding, see the two-piece conductor-to-structure clamp (TECD) and the one-piece clamp (TECS).
If this matches your situation, see these products too
Product | When |
|---|---|
For the end of the earth conductor that fixes on the earth bus stud. | |
When you want a two-bolt connection. | |
When you fix a conductor to a structure without welding. | |
For gathering bonding conductors together. | |
For connecting a conductor to reinforcing bar in concrete. | |
When the connection is buried in soil. |
Compare all earthing and bonding clamps in the "Which clamp should we choose?" table.
The KALOT Group earth bus is designed and made in line with IEC 62561-1, the standard that sets the requirements for connection components of lightning protection and earthing systems.
IEC 62305-3 treats the metal frame of a structure as a natural component of the lightning protection system and requires metal parts to be bonded. Part Thirteen of the Iranian National Building Regulations also counts the main metal parts of a building, including the steel frame, among the elements of main building bonding.
For steel tanks, standards such as API RP 545 and NFPA 780 deal with connecting the tank to the earthing system and bonding it. Welding on a tank or pressure vessel is subject to the welding procedure and the approval of the project's technical supervisor.
The earthing system designer decides the positions of the connection points, the conductor cross-section and the connection method. To learn more, see earthing system design and installation standards.
Three-dimensional installation view of the earth bus
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Steel bonding cylinder dimensional drawingLanguage: Persian (opens in a new tab)
- Steel bonding cylinder technical drawingLanguage: Persian (opens in a new tab)
- Steel bonding cylinder exploded viewLanguage: Persian (opens in a new tab)
- Steel bonding cylinder installation schematicLanguage: Persian (opens in a new tab)
- Steel bonding cylinder connection modesLanguage: Persian (opens in a new tab)
- Steel bonding cylinder installation stepsLanguage: Persian (opens in a new tab)
Frequently Asked Questions
What is an earth bus (steel bonding cylinder)?
An earth bus is a solid steel cylinder welded to a steel structure such as a column, beam or tank shell, with an M10 stud on it for fixing the cable lug of the earth conductor. This gives the structure a permanent earth connection point that can be inspected.
What is the KALOT Group earth bus made of?
The cylinder body is carbon steel so that it welds to the steel of the structure. The double-ended stud, two nuts, two flat washers and spring washer are stainless steel. We can provide other sizes and materials of accessories to order.
What sizes are available?
Five standard sizes with M10 thread: EBOS 5050, EBOS 5040, EBOS 5030, EBOS 4040 and EBOS 4030. The first number is the diameter and the second the length of the cylinder, in millimetres. We make other sizes to order.
How is an earth bus installed?
The installation spot is ground back to clean metal, the cylinder is welded to the structure with a fillet weld all the way round, and the weld area is covered with anti-corrosion paint or tape. The cable lug of the conductor is then fixed on the stud between two washers and the nut is tightened according to the manufacturer's instructions.
Can an earth bus be installed on a tank?
Yes. The earth bus is used to create an earth connection point on the shells of steel tanks and vessels. Welding on a tank or pressure vessel must follow the welding procedure and be approved by the project's technical supervisor.
Is an earth bus better, or a conductor bolted to a drilled hole in the structure?
Both methods are used. The earth bus needs no drilling in the structure and becomes one with it through welding. Where welding is not allowed, a bolted conductor-to-structure clamp with drilling is the suitable option.
What conductors connect to an earth bus?
Any earth or bonding conductor with a cable lug on its end whose hole suits an M10 stud, such as stranded copper conductor with green and yellow insulation, or tape with a hole.
What needs doing after welding?
Remove the slag and cover the cylinder body, weld and ground area with anti-corrosion paint or tape. Keep the front face of the cylinder and the thread clean so that the cable lug keeps good contact. Then measure the electrical continuity.
What information should we send for a quote?
Send us the type of structure, the conductor cross-section and cable lug type, the number of connection points and any other size or thread you need, and our experts will make a proposal and give you a price.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.