Move your pointer over the image to zoom in
Complete Product Overview
One-piece clamp for connecting conductor to plates and metal structures (TECS)
Last updated:
The KALOT Group one-piece clamp for connecting conductor to plates and metal structures (code TECS) presses a copper earth conductor or lightning protection conductor directly onto a plate, column, beam, angle or building steel frame. The clamp is a single cast brass clamping plate with a conductor groove along its edge. A stainless steel bolt passes through the holes in the clamping plate and structure and, as the nut tightens, the plate presses the conductor onto the metal surface.
Because the conductor sits directly on the metal of the structure, the one-piece clamp is the simplest, lowest-profile way to connect an earth conductor to a steel frame, provided the surface is clean and flat at the contact point. We make it in two sizes: for 16 to 70 mm² conductors with an M8 bolt, and for 95 to 185 mm² conductors with an M10 bolt. If you want the conductor held between two brass clamping plates with no direct contact with the structure's surface, see the two-piece conductor-to-structure clamp (TECD).
One-piece clamp for direct connection of earth conductors to steel frames
To choose a one-piece clamp, check the conductor cross-section and make sure the structure's surface is clean and flat at the connection point. The code follows from the conductor, and the bolt length from the thickness of the structure.
- Direct connection of copper conductor to plates and steel frames
- Conductors from 16 to 185 mm² in two sizes
- One cast brass clamping plate, stainless steel bolt and nut
- Low profile, one hole in the structure
Direct conductor-to-metal contact
The brass clamping plate presses the conductor directly onto the plate or column, so current passes straight from conductor to structure.
Low profile and simple
Just one clamping plate, one bolt and one nut, installed with a single hole in the structure.
Material: brass and stainless steel
The clamping plate is cast brass and the bolt and nut are stainless steel. Brass is compatible with copper conductors and the bolt resists corrosion.
Two TECS sizes and drawings
One-piece clamp datasheet (PDF)You will find codes TECS 1670 and TECS 9518, with conductor range, conductor diameter and bolt size, in the technical specifications tab. The clamp's shape is shown in the dimensional drawing, technical drawing, exploded view and datasheet of the one-piece clamp.
Advice from KALOT Group specialists
When you enquire, send us the conductor cross-section, the type and thickness of the plate or structure (column, beam, angle, earth plate), whether it is painted or galvanised, and the quantity you need. Our specialists will confirm the right code, bolt length and price.
Technical Product Information
Click to view enlarged
Feature | Value |
|---|---|
Type | One-piece clamp for direct connection of one copper conductor to a plate or steel structure |
Body | One trapezoidal cast brass clamping plate with a conductor groove along the wider edge |
Bolts and nuts | Stainless steel: one hex bolt passing through the clamping plate and the hole in the structure, with a nut behind the structure |
Suitable conductor | Stranded or solid copper conductor: earth conductor, bonding conductor or lightning protection down conductor |
Conductor range | 16 to 70 and 95 to 185 mm², in two sizes |
Bolts and nuts | M8 × 35 for TECS 1670 and M10 × 50 for TECS 9518 |
Installation location | Plates, columns, beams, angles, earth plates and accessible steel structures with a clean, flat contact surface |
Connection type | Bolted, can be opened and refastened |
Codes | TECS 1670 and TECS 9518 |
One-piece clamp sizes and codes (TECS)
Code | Conductor cross-section (mm²) | Conductor diameter on the drawing (mm) | Bolts and nuts |
|---|---|---|---|
TECS 1670 | 16-70 | 5.1-10.7 | M8 × 35 |
TECS 9518 | 95-185 | 12.6-17.6 | M10 × 50 |
Cross-sections are in square millimetres. "Conductor diameter on the drawing" is the diameter of the conductors drawn for each size in our manufacturing drawings. The bolt length of each size is set for the usual thickness of plates and angles. If your structure is thicker, tell us its thickness when you enquire. We continually improve our products and some dimensions may be updated, so please confirm the final dimensions with our specialists before you buy.
Dimensional drawing
Download the dimensional drawing (PDF)
Technical drawing
Download the technical drawing (PDF)
Exploded view
Download the exploded view (PDF)
KALOT AutoCAD drawing
Download the AutoCAD drawing (PDF)
Conductor groove and contact with the structure
Along its wider edge, the clamping plate has a semicircular groove facing the structure. The conductor lies in this groove on the surface of the structure, the bolt passes through the central hole of the plate and the hole in the structure, and the nut is tightened behind the structure. As the nut tightens, the plate acts like a lever and presses the conductor onto the metal. Because the conductor is in direct contact with the surface, the cleanliness of that surface plays the main part in the quality of the connection.
Click to view enlarged
Applications of the one-piece conductor-to-plate clamp
- Building steel frames: connecting the earth conductor to columns, beams and column base plates, to establish bonding between the frame and the earthing system
- Plates and connection plates: connecting the conductor to a steel plate or earthing connection plate provided on the structure or equipment
- Towers and industrial structures: connecting the earth conductor to tower angles, platforms, skids, tank shells and equipment supports
- Lightning protection system: connecting the down conductor or bonding conductor to metal columns and roof structures
- Larger conductors: size TECS 9518 for 95 to 185 mm² conductors, where the main earth conductor is large
Installation schematic
Download the execution schematic (PDF)
Connection modes
Download connection modes (PDF)
One-piece clamp installation steps
- Choose the clamp code by the conductor cross-section and make sure the bolt is long enough for the thickness of the structure.
- Mark the clamp position and drill a hole slightly larger than the bolt diameter, then deburr the edge of the hole.
- Clean the surface under the conductor and clamping plate back to bare metal, removing paint, rust and grease. This is the most important installation step, because the conductor is pressed directly onto this surface. On galvanised structures, remove only the dirt and do not scrape off the zinc coating.
- Clean the conductor at the connection point and place it on the surface of the structure, under the groove of the clamping plate.
- Pass the bolt through the clamping plate and the hole in the structure, hand-tighten the nut behind the structure, then tighten to the manufacturer's instructions so the plate presses the conductor evenly onto the metal.
- Check that the conductor is seated in the groove and does not slip under the clamping plate, then cover the joint and the cleaned surface with paint or a moisture-proof compound.
Download the installation steps (PDF)
Installation tools
For installation, all you need is a drill with a bit to suit the bolt diameter, two spanners to fit the bolt head and nut, and a wire brush or abrasive paper to clean the surface of the structure. This connection needs no welding or crimping tools.
Inspection and measurement
During periodic inspections of the earthing and lightning protection system, check the clamp for looseness, corrosion of the contact surface and conductor damage. If you see rust or corrosion under the clamping plate, open the clamp, clean the surface again and retighten to the manufacturer's instructions. For earth resistance measurement, the test joint or disconnect link of the earthing system is opened. Check the continuity of the conductor-to-structure connection with a low-resistance ohmmeter, between conductor and structure, with the clamp closed.
Choosing and requesting a price for the one-piece clamp
When you enquire, send us the conductor cross-section, the type and thickness of the plate or structure (column, beam, angle, earth plate), whether it is painted or galvanised, and the quantity you need. Our specialists will confirm the right code, bolt length and price.
Click to view enlarged
The one-piece clamp creates the shortest path between an earth conductor and a steel frame: the conductor is pressed directly onto the metal, with no welding, cable lug or extra part. For columns, beams and plates whose surface can be cleaned back to bare metal, it is the simplest, lowest-profile choice. If you would rather not, or cannot, clean the surface back to bare metal, or the structure will receive cladding or wall lining, the two-piece clamp (TECD) holds the conductor between two brass clamping plates. If two conductors reach the structure at one point, see the single-bolt parallel clamp (PTEC). To compare clamp materials, see Earth clamp materials: brass, copper or galvanised.
Advantages of the one-piece clamp
- Direct contact: the conductor is pressed straight onto the metal of the structure, giving the shortest current path from conductor to structure.
- Simple and low profile: one clamping plate, one bolt and one nut, our lowest-profile clamp for connecting a conductor to a structure.
- Conductors from 16 to 185 mm²: two sizes, 16 to 70 with an M8 bolt and 95 to 185 with an M10 bolt, covering everything from bonding conductors to large earth grid conductors.
- Brass body, stainless steel bolt: the body material is compatible with a copper conductor, and the bolt and nut resist corrosion.
- No welding: installed with one hole, with no heat on painted or galvanised structures.
- Can be opened and retightened: for inspection, cleaning the contact surface or repair, simply undo the nut and tighten it again.
One-piece or two-piece clamp?
Feature | One-piece clamp (TECS) | Two-piece clamp (TECD) |
|---|---|---|
Conductor position | Between the jaw and the structure's surface | Between two brass jaws |
Conductor contact with the structure | Direct | Indirect, through the brass |
Dependence on the structure's surface | High: the surface must be clean back to bare metal | Lower |
Clamp thickness | Thinner (one clamping plate) | Thicker (two clamping plates) |
Conductor cross-section (square millimetres) | 16 to 185 (two sizes) | 16 to 185 (two sizes) |
Both clamps fix to the structure with one hole and one bolt. If the surface can be cleaned back to bare metal and you want a simple, low-profile clamp, choose the one-piece. If the conductor needs to be held in brass, or the structure will be clad, choose the two-piece. For connections buried in soil, we recommend exothermic welding.
If these conditions apply to you, see these clamps as well
Clamp | When |
|---|---|
Two-piece clamp for connecting conductor to plates and metal structures (TECD) | When the conductor needs to be held between two brass clamping plates. |
When two conductors reach a structure or tower base at one point. | |
When the conductor is a tape rather than a stranded or solid conductor. | |
When the connection is buried in soil or a permanent connection without bolts is needed. |
Compare all our earthing clamps in the "Which clamp should we choose?" table.
KALOT Group's one-piece clamp is designed and manufactured to IEC 62561-1, the standard that sets the requirements for connection components of lightning protection and earthing systems.
Under IEC 62305-3, a building's steel frame, if electrically continuous, can act as a natural part of the lightning protection system, including as a down conductor. The conductor's connection to such a frame must be reliable and checked during periodic inspections.
EN 50522 and BS 7430 require earthing system connections to have stable electrical continuity and protection against corrosion. Where copper or brass connects to steel, the joint must be kept away from moisture and covered with a protective coating.
In Iran, Part Thirteen of the National Building Regulations requires reliable, secure connections and attention to galvanic corrosion when connecting dissimilar metals. To learn more, see Standards for the design and installation of earthing systems.
One-piece clamp, wire to metal plates and structures
Documents & Downloads
Catalogues & datasheets
Drawings & schematics
- Dimensional drawing of the one-piece clamp for connecting conductor to structures (TECS)Language: Persian (opens in a new tab)
- Technical drawing of the one-piece clamp for connecting conductor to structuresLanguage: Persian (opens in a new tab)
- Exploded view of the one-piece clamp for connecting conductor to structuresLanguage: Persian (opens in a new tab)
- Installation schematic of the one-piece clamp for connecting conductor to structuresLanguage: Persian (opens in a new tab)
- Connection modes of the one-piece clamp for connecting conductor to structuresLanguage: Persian (opens in a new tab)
- Installation steps for the one-piece clamp for connecting conductor to structuresLanguage: Persian (opens in a new tab)
- AutoCAD drawing of the one-piece clamp for connecting conductor to structures (TECS)Language: Persian (opens in a new tab)
Frequently Asked Questions
What is a one-piece conductor-to-plate clamp?
It is a one-piece brass clamp that uses a single stainless steel bolt to press a copper earth or lightning protection conductor directly onto a steel plate, column, beam or angle. The conductor is held between the groove of the clamping plate and the surface of the structure.
Which clamp should we use to connect an earth conductor to a building's steel frame?
If the surface of the column or plate can be cleaned back to bare metal, the one-piece clamp is the simplest route. If the conductor needs to be held between two clamping plates, or the frame will be clad, choose the two-piece clamp. Both install with a single hole in the structure.
Which one-piece clamp size should I choose?
Choose the size by conductor cross-section: TECS 1670 for 16 to 70 mm² conductors with an M8 × 35 bolt, and TECS 9518 for 95 to 185 mm² conductors with an M10 × 50 bolt.
Why does cleaning the structure's surface matter so much with a one-piece clamp?
Because the conductor is pressed directly onto that surface, any paint, rust or grease between conductor and metal raises the resistance of the connection. Clean the area under the conductor and clamping plate back to bare metal and, once tightened, cover the joint with paint or a moisture-proof compound.
Can it be installed on galvanised structures as well?
Yes. On galvanised structures, remove only dirt and grease and do not scrape off the zinc coating. Since copper and brass are dissimilar to galvanised steel, cover the joint with paint or a moisture-proof compound after tightening so that moisture cannot reach the contact point.
What conductor diameter is the one-piece clamp made for?
In our manufacturing drawings, the 16 to 70 size is drawn for conductors of about 5 to 11 mm in diameter, and the 95 to 185 size for conductors of about 13 to 18 mm. If your conductor falls between these two ranges, tell our specialists its cross-section and type.
How does the thickness of the column or plate affect the choice?
The bolt passes through the clamping plate and the structure itself, so the thicker the structure, the longer the bolt must be. The bolt length of each code is set for common plates and angles. For a thick column or plate, tell us the thickness when you enquire.
Can the one-piece clamp be used below ground?
No. This clamp is for accessible connections on structures, so it can be seen and retightened. For connections below ground, we recommend exothermic welding.
What should we do for conductors larger than 185 mm²?
The one-piece clamp is made for conductors up to 185 mm². For larger conductors, or where two large conductors reach the structure at one point, see the single-bolt parallel clamp or talk to our specialists.
Can we also connect a tape conductor to a plate with this clamp?
The one-piece clamp is made for conductors and round wire. For copper tape, see the tape-to-metal plate bonding clamp.