Introduction

Short answer: an SPD (Surge Protective Device) comes in three main types: Type 1 in the building's incoming panel, which withstands part of the direct lightning current; Type 2 in distribution panels, which handles induced and switching overvoltages; and Type 3 close to sensitive equipment, which is the last step of protection. Working together in coordination, these three types bring lightning voltage down stage by stage.

In normal conditions an SPD behaves like an open circuit. When an impulse voltage arrives, it conducts within a few nanoseconds, sends the impulse current to the earth bar and earthing system, and holds the voltage at its protection level (Up), which must be below what the equipment can withstand. The SPD is the core of secondary lightning protection. Its selection and placement depend on the lightning protection level, the earthing arrangement and the lightning protection zones (LPZ). The main standards are IEC 61643-11 for the SPD itself, IEC 60364-5-53 for selection and installation, and IEC 62305-4 for protecting equipment.

SPD types

Three types of power SPD: installation point, test waveform and common element.

Type 1 SPD (Type 1)

  • Where: the incoming or main panel of a building with an air terminal or an overhead incoming line.
  • Test: impulse current Iimp with a 10/350 µs waveform, which resembles direct lightning current.
  • Value: if it has not been calculated, IEC 60364-5-53 requires at least 12.5 kA for each protection path.
  • Common element: a spark gap or a high-capacity varistor.
  • Examples: Class 1 three-phase TNC power SPD, Class 1 three-phase TNS and Class 1 three-phase TT.

Type 2 SPD (Type 2)

  • Where: distribution panels and sub-panels, and the incoming panel of buildings without an air terminal.
  • Test: nominal discharge current In with an 8/20 µs waveform, at least 5 kA under IEC 60364-5-53.
  • Common element: metal oxide varistor (MOV).
  • Against: induced overvoltage from nearby strikes and switching overvoltage.
  • Examples: Class 2 three-phase TNC power SPD, Class 2 three-phase TNS and Class 2 three-phase TT.

Type 3 SPD (Type 3)

  • Where: close to sensitive equipment: socket, rack and control panel.
  • Test: combination wave of 1.2/50 µs voltage and 8/20 µs current.
  • Common element: a small varistor, sometimes with a filter.
  • Note: Type 3 is always installed downstream of a Type 2 SPD and is not enough on its own. Examples: Class 3 three-phase TNC power SPD and socket-type SPD.

What do the 10/350 and 8/20 waveforms tell us?

At the same peak, the 10/350 wave carries about 30 times the charge and 20 times the energy of the 8/20 wave.

The first number is the time to reach the peak and the second is the time to fall to half the peak, in microseconds. The 10/350 wave is far longer: at the same peak, its electrical charge is nearly 30 times and its energy about 20 times that of the 8/20 wave. That is why a Type 2 SPD cannot replace a Type 1 at the entry of a building with an air terminal, even if its kiloampere figure is larger.

Staged reduction and SPD coordination

Lightning impulse voltage on lines can reach tens of kilovolts. SPDs bring it down step by step. The SPD at the entry usually holds the protection level at around 1.5 to 2.5 kV. The Type 2 SPD lowers it further, and the Type 3, close to the equipment, keeps the voltage below what electronic equipment can withstand (1.5 kV on a 230 V network). It also removes voltage oscillation in the long cable between panel and equipment.

Coordination means each SPD takes its share of the energy and the smaller SPD does not fail before the larger one. Between a Type 1 spark gap and a Type 2 varistor, a length of cable or a decoupling inductor is usually needed, unless the manufacturer guarantees their coordination without spacing. So it is best to choose the SPDs in a chain from one family and according to the manufacturer's coordination table. If the equipment is far from the last SPD (usually more than about 10 m), a Type 3 SPD close to the equipment becomes necessary.

Combined SPDs

A combined SPD holds several types in one module, such as Type 1+2 or 1+2+3. Its internal coordination is guaranteed by the manufacturer, it takes up less room in the panel and it is simpler to install. For residential, office and commercial buildings, a combined SPD in the incoming panel is the most common choice. Large installations with many panels still need Type 2 SPDs in the sub-panels and Type 3 close to the equipment. Examples: combined Class 1+2+3 three-phase TNC SPD, three-phase TNS, three-phase TT, combined 1+2 three-phase TNC and combined 1+2 with EMI filter.

SPD layout in the electrical panel: TN-C, TN-S and TT (3+1)

The SPD arrangement depends on the earthing system; in TT it is a 3+1 or 1+1 arrangement.
  • TN-C: three modules from the three phases to PEN.
  • TN-S and the TN-S part of a TN-C-S system: four modules from the three phases and neutral to PE.
  • TT: a "3+1" layout: three varistors from the phases to neutral and a spark gap from neutral to PE. In single-phase, the layout is "1+1". The neutral-to-PE spark gap prevents a varistor failure from making enclosures live through the earth electrode. Example: combined single-phase TT 1+1 SPD.

That is why our power SPDs are supplied under the names TNC, TNS and TT. See them all in power surge protective devices (SPDs).

SPDs for data lines, telecoms and special systems

Data and telecom lines need their own SPDs, which are tested to IEC 61643-21 and must match the line's operating voltage, transmission speed and connector type. Examples: RJ45 data SPD, PoE SPD, BNC SPD and RS485 SPD in data line surge protective devices (SPDs). For solar systems we supply the photovoltaic DC SPD (solar plant protection), for fire alarms the fire alarm SPD, and for explosive atmospheres the spark gap for EX environments.

Choosing an SPD at a glance

Question

Answer

Does the building have an air terminal or an overhead incoming line?

Type 1 or combined 1+2 in the incoming panel

No air terminal on the building and an underground incoming line?

Type 2 in the incoming panel is usually enough (subject to risk assessment)

Is the sub-panel far from the incoming panel?

Type 2 in the sub-panel

Is the sensitive equipment far from the last SPD?

Type 3 or socket-type SPD close to the equipment

Earthing arrangement?

TNC, TNS or TT (3+1 / 1+1)

Uc and Up?

Uc at least 1.1 times the phase voltage (common: 275 V); Up below what the equipment can withstand

Website membership required · Sign in or join

Keep the SPD connecting leads short, with a total length preferably no more than 0.5 m (earthing, bonding and EMC). We carry out overvoltage protection design and SPD selection and SPD installation. To choose an SPD, send our specialists your single-line diagram and earthing arrangement, or call us through our contact us page.