Lightning protection clamps, connectors and fittings

Complete Product Overview

Brass down conductor disconnector for lightning protection (Test Joint)

Order Code: SKADL 100

Last updated:

The KALOT brass disconnector (Test Joint) is the disconnection point of the down conductor in a lightning protection system. Normally it keeps the lightning current path from the down conductor to the earthing system continuous. For testing, opening all four bolts separates the down conductor from the earthing system so the earth resistance can be measured separately.

We make this disconnector in brass under the code SKADL 100. The 25 × 3 mm copper tape of the down conductor connects from above and the 50 mm² earthing system conductor from below. Each disconnector comes with four stainless steel Allen bolts, one Allen key, and screws and wall plugs for wall mounting.

A lightning mark, the KALOT ABHAR name and an earth symbol are cast into the body, so the disconnector is easy to identify during inspection. Dimensions: 80 × 57 × 20 mm.

The test point of every down conductor

NF C 17‑102 requires a test joint on each down conductor so it can be separated from the earthing system for measurement. This joint is usually installed about 2 metres above ground level. The KALOT brass disconnector is made for exactly this point: it stays closed in normal service and opens with a tool only for testing and inspection.

  • Disconnection for earth testing

    Opening all four bolts separates the down conductor from the earthing system, so the earthing system's resistance can be measured without the effect of parallel paths. After the test, the joint is closed again.

  • 25×3 tape to 50 mm² conductor

    The tape down conductor connects from above and the earthing system conductor from below. This is where the façade tape joins the earth conductor.

  • Solid brass, stainless steel bolts

    A cast solid brass body and four stainless steel bolts, for a joint that stays outdoors on the building façade for years.

  • Closed in service, opened only with a tool

    The Allen bolts open only with a key. The disconnector stays closed in normal conditions and needs a tool for testing.

  • Markings on the body

    A lightning mark at the top and an earth symbol at the bottom are cast into the body, so the installation direction and the role of each conductor are clear at first glance.

Technical Product Information

Feature

Value

Product type

Down conductor disconnector (test joint) (Special Test Clamp)

Order code

⁦SKADL 100⁩

Application

Disconnecting and reconnecting the down conductor from the earthing system for testing, measurement and inspection

Down conductor (top inlet)

Copper tape, 25 × 3 mm

Earthing system conductor (bottom outlet)

50 mm² conductor

Body material

Solid brass

Bolts

4 stainless steel Allen bolts

Supplied with the part

One Allen key, stainless steel screws and plastic wall plugs for wall mounting

Dimensions

⁦L = 80 mm⁩, ⁦W = 57 mm⁩, ⁦H = 20 mm⁩

Markings on the body

Lightning mark, KALOT ABHAR and earth symbol

Installation location

On the route of each down conductor, before the connection to the earthing system, usually about 2 metres above ground level

Our products are continually improved and some dimensions may be updated; please confirm the final dimensions with our specialists before you buy.

Test joint and down conductor test clamps

Drag to rotate; scroll to zoom.Open full screen

Frequently Asked Questions

What is a down conductor disconnector?

A disconnector, or test joint (Test Joint), is a part fitted on each down conductor of a lightning protection system. Normally it keeps the route from the down conductor to the earthing system continuous. During testing it is opened so the down conductor can be separated from the earthing system and the earth resistance measured.

Are the earth disconnector, lightning disconnector and test joint the same part?

Yes. Earth disconnector, lightning disconnector, test connection and test joint are common names for this same disconnection point between the down conductor and the earthing system.

At what height should the disconnector be installed?

According to NF C 17‑102, the test joint is usually installed about 2 metres above ground level, where it is accessible for inspection but not exposed to tampering. The conductor below the disconnector runs inside a protective pipe to below ground level.

Which conductors is the SKADL 100 disconnector suitable for?

This disconnector connects a 25×3 mm tape down conductor from above to a 50 mm² earthing system conductor from below.

Why must the disconnector be opened to measure earth resistance?

If the down conductor stays connected, parallel paths such as other down conductors and bonding connections make the reading lower than the true value. Opening the disconnector lets you measure the earthing system of that down conductor on its own.

What is the disconnector made of?

The disconnector body is made entirely of brass, and its four bolts are stainless steel.

What comes with the disconnector?

Each disconnector comes with four stainless steel Allen bolts, one Allen key, and screws and plastic wall plugs for wall mounting.

Should the disconnector normally stay closed?

Yes. The disconnector is opened with the Allen key only for testing and inspection. After the measurement it must be closed again and its bolts tightened evenly.

What is the difference between a disconnector and an earth bar with a disconnect link?

The disconnector is installed on the route of each down conductor, on the building façade. An earth bar with a disconnect link usually sits in a panel or inspection pit, brings several earth conductors together, and each of its links is separated for testing.