Brass down conductor disconnector for lightning protection (Test Joint)
Order Code: SKADL 100
Last updated:
The KALOT brass disconnector (Test Joint) is the disconnection point of the down conductor in a lightning protection system. Normally it keeps the lightning current path from the down conductor to the earthing system continuous. For testing, opening all four bolts separates the down conductor from the earthing system so the earth resistance can be measured separately.
We make this disconnector in brass under the code SKADL 100. The 25 × 3 mm copper tape of the down conductor connects from above and the 50 mm² earthing system conductor from below. Each disconnector comes with four stainless steel Allen bolts, one Allen key, and screws and wall plugs for wall mounting.
A lightning mark, the KALOT ABHAR name and an earth symbol are cast into the body, so the disconnector is easy to identify during inspection. Dimensions: 80 × 57 × 20 mm.
The test point of every down conductor
NF C 17‑102 requires a test joint on each down conductor so it can be separated from the earthing system for measurement. This joint is usually installed about 2 metres above ground level. The KALOT brass disconnector is made for exactly this point: it stays closed in normal service and opens with a tool only for testing and inspection.
Disconnection for earth testing
Opening all four bolts separates the down conductor from the earthing system, so the earthing system's resistance can be measured without the effect of parallel paths. After the test, the joint is closed again.
25×3 tape to 50 mm² conductor
The tape down conductor connects from above and the earthing system conductor from below. This is where the façade tape joins the earth conductor.
Solid brass, stainless steel bolts
A cast solid brass body and four stainless steel bolts, for a joint that stays outdoors on the building façade for years.
Closed in service, opened only with a tool
The Allen bolts open only with a key. The disconnector stays closed in normal conditions and needs a tool for testing.
Markings on the body
A lightning mark at the top and an earth symbol at the bottom are cast into the body, so the installation direction and the role of each conductor are clear at first glance.
Technical Product Information
Feature | Value |
|---|---|
Product type | Down conductor disconnector (test joint) (Special Test Clamp) |
Order code | SKADL 100 |
Application | Disconnecting and reconnecting the down conductor from the earthing system for testing, measurement and inspection |
Down conductor (top inlet) | Copper tape, 25 × 3 mm |
Earthing system conductor (bottom outlet) | 50 mm² conductor |
Body material | Solid brass |
Bolts | 4 stainless steel Allen bolts |
Supplied with the part | One Allen key, stainless steel screws and plastic wall plugs for wall mounting |
Dimensions | L = 80 mm, W = 57 mm, H = 20 mm |
Markings on the body | Lightning mark, KALOT ABHAR and earth symbol |
Installation location | On the route of each down conductor, before the connection to the earthing system, usually about 2 metres above ground level |
Our products are continually improved and some dimensions may be updated; please confirm the final dimensions with our specialists before you buy.
Click to view enlarged
The KALOT dimensional drawing shows three views of the disconnector: the front view with the four bolts, lightning mark, KALOT ABHAR band and earth symbol; the side view with the raised middle section; and the end view. Dimensions: L = 80 mm · W = 57 mm · H = 20 mm. The PDF and SVG files of this drawing are in the "Documents and downloads" section of this page.
Click to view enlarged
Where the disconnector sits in a lightning protection system
The disconnector sits on each down conductor, between the lower part of the down conductor on the façade and the earthing system. According to NF C 17‑102, the test joint is usually installed about 2 metres above ground level, where it is accessible for inspection but not exposed to tampering by passers-by. If you use a lightning event counter, it is installed above the disconnector on the same down conductor.
Installation sequence
- Mark the disconnector position on the down conductor route, about 2 metres above ground level.
- Fix the disconnector to the wall with the supplied screws and wall plugs, with the lightning mark facing up and the earth symbol facing down.
- Clean dirt, oxide and oil from the contact surfaces of the tape and conductor.
- Place the 25 × 3 mm down conductor tape into the disconnector from above and the 50 mm² earthing system conductor from below.
- Tighten the four bolts gradually and evenly with the Allen key.
- Run the conductor below the disconnector inside a protective pipe to below ground level and connect it to the earthing system.
- Check the continuity of the route from the down conductor to the earthing system.
Choosing the right test joint
- Tape down conductor and 50 mm² earth conductor, on the façade: this disconnector, SKADL 100.
- Test joint between two round conductors: Two-way conductor-to-conductor clamp.
- Test joint between a round conductor and a tape: two-way conductor-to-tape clamp.
- Holding the down conductor tape on the wall above the disconnector: two-piece brass clamp for fixing tape to walls or two-piece stainless steel clamp for fixing tape to walls.
Technical notes
- The disconnector must stay closed in normal service. Open it only for testing and inspection, then close it again straight away.
- Copper conductors and the brass body are compatible. Avoid connecting aluminium or galvanised steel conductors directly to the disconnector, and leave material compatibility to the system designer.
- Run the conductor below the disconnector inside a protective pipe to below ground level, to keep it safe from mechanical damage and tampering.
Click to view enlarged
If the down conductor stays connected to the earthing system during measurement, parallel paths (other down conductors, bonding connections and the building's metal frame) make the instrument read lower than the true value. Opening the disconnector lets you measure the earthing system of that down conductor on its own.
Test steps
- Carry out the test in calm weather. Do not open the disconnector in stormy conditions or when lightning is possible.
- Undo all four bolts with the Allen key and separate the earth conductor from the disconnector.
- Measure the earthing system's resistance from the earth conductor side with an earth tester and record it. In systems designed to NF C 17‑102, the earthing system resistance of each down conductor must be 10 ohms or less.
- Put the earth conductor back in place, tighten all four bolts evenly and check the continuity of the route.
- Record the date and result of the measurement in the system's inspection log.
Periodic inspection
At each inspection, check the disconnector for loose bolts, corrosion and mechanical damage, check the condition of the protective pipe below it, and make sure the markings on the body are legible.
The following standards set the position and requirements of the test joint in a lightning protection system:
NF C 17-102 (ESE air terminals)
Each down conductor needs a test joint so it can be separated from the earthing system for measurement. The test joint must be marked and is usually installed about 2 metres above ground level. A lightning event counter, if used, goes above it. Read the key points of the NFC 17-102 standard in this article.
IEC 62305-3 (system design and installation)
Where the earthing system connects to the down conductor, a test joint is fitted on each down conductor, except on natural down conductors connected to a foundation electrode. The joint opens with a tool for measurement and stays closed in normal service.
IEC 62561-1 (connection components)
This standard sets the requirements and tests for the connection components of a lightning protection system, including test joints.
Test joint and down conductor test clamps
Documents & Downloads
Drawings & schematics
Installation & application guides
Frequently Asked Questions
What is a down conductor disconnector?
A disconnector, or test joint (Test Joint), is a part fitted on each down conductor of a lightning protection system. Normally it keeps the route from the down conductor to the earthing system continuous. During testing it is opened so the down conductor can be separated from the earthing system and the earth resistance measured.
Are the earth disconnector, lightning disconnector and test joint the same part?
Yes. Earth disconnector, lightning disconnector, test connection and test joint are common names for this same disconnection point between the down conductor and the earthing system.
At what height should the disconnector be installed?
According to NF C 17‑102, the test joint is usually installed about 2 metres above ground level, where it is accessible for inspection but not exposed to tampering. The conductor below the disconnector runs inside a protective pipe to below ground level.
Which conductors is the SKADL 100 disconnector suitable for?
This disconnector connects a 25×3 mm tape down conductor from above to a 50 mm² earthing system conductor from below.
Why must the disconnector be opened to measure earth resistance?
If the down conductor stays connected, parallel paths such as other down conductors and bonding connections make the reading lower than the true value. Opening the disconnector lets you measure the earthing system of that down conductor on its own.
What is the disconnector made of?
The disconnector body is made entirely of brass, and its four bolts are stainless steel.
What comes with the disconnector?
Each disconnector comes with four stainless steel Allen bolts, one Allen key, and screws and plastic wall plugs for wall mounting.
Should the disconnector normally stay closed?
Yes. The disconnector is opened with the Allen key only for testing and inspection. After the measurement it must be closed again and its bolts tightened evenly.
What is the difference between a disconnector and an earth bar with a disconnect link?
The disconnector is installed on the route of each down conductor, on the building façade. An earth bar with a disconnect link usually sits in a panel or inspection pit, brings several earth conductors together, and each of its links is separated for testing.