Move your pointer over the image to zoom in
Complete Product Overview
Conventional air rod in solid copper
Order Code: ATC 0516 … ATC 2020
Last updated:
KALOT's conventional air rod in solid copper, also called a Franklin rod or passive lightning rod, is a copper air rod with a conical tip. As the air terminal of a lightning protection system, it covers the highest points of a structure and carries the lightning current to the down conductors and the earthing system.
The air rod screws onto its dedicated base by the thread at its end, and each one is supplied with a lock nut. Standard models are made in 16 mm and 20 mm diameters and lengths of 500 to 2000 mm, and we make other diameters and lengths to your order.
We manufacture our air rods to the requirements of IEC 62561-2 and successfully pass the standard's tests.
A copper air terminal for the protection angle, rolling sphere and mesh methods
When a lightning protection system is designed, conventional air rods go at the points the designer sets using the protection angle, rolling sphere or mesh method. Their height and number come from that same design, and we provide them in the diameter and length your design calls for.
Solid copper
The air rod body is copper, a metal with high electrical conductivity and good resistance to atmospheric corrosion, and it works well with the system's copper and brass conductors and connectors.
Tapered tip and threaded end
The air rod has a tapered tip, and the other end carries an M16 or M20 thread so it fixes directly onto a base or coupling.
Supplied with a lock nut
Each air rod comes with one lock nut, which holds it firmly on the base or connector and stops it working loose.
Eight standard models, made to order
Diameters of 16 and 20 mm in four lengths: 500, 1000, 1500 and 2000 mm. We make other diameters and lengths to order.
Produced in line with IEC 62561-2
We produce these copper air rods in line with the requirements of IEC 62561-2, the standard for conductor and electrode components of lightning protection systems.
Technical Product Information
Feature | Value |
|---|---|
Product type | Conventional air rod with tapered tip (Taper Point Air Rod) |
Air rod material | Copper (solid copper) |
Air rod diameter | 16 mm or 20 mm |
Threaded end | M16 for 16 diameter, M20 for 20 diameter |
Standard length | 500, 1000, 1500 and 2000 mm |
Nut | One lock nut with each air rod; nut material: stainless steel |
Made to order | Other diameters and lengths |
Production standard | IEC 62561-2 |
Order code | ATC 0516 to ATC 2020 |
Order code | Length L (mm) | Air rod diameter (mm) | Thread | Material |
|---|---|---|---|---|
ATC 0516 | 500 | 16 | M16 | Copper |
ATC 1016 | 1000 | 16 | M16 | Copper |
ATC 1516 | 1500 | 16 | M16 | Copper |
ATC 2016 | 2000 | 16 | M16 | Copper |
ATC 0520 | 500 | 20 | M20 | Copper |
ATC 1020 | 1000 | 20 | M20 | Copper |
ATC 1520 | 1500 | 20 | M20 | Copper |
ATC 2020 | 2000 | 20 | M20 | Copper |
In the order code, the first two digits give the air rod length in decimetres (05 to 20) and the last two give its diameter in millimetres. Each copper air rod comes with one lock nut. For other diameters and lengths, tell us the size you need when you order.
Click to view enlarged
The KALOT drawing shows the air rod with its tapered tip, length L and threaded end, and the same sheet carries a table of the eight standard ATC models with the diameter, thread and length of each. This is not a manufacturing drawing. Its PDF and SVG files are in the "Documents and downloads" section of this page.
Click to view enlarged
Application
The conventional air rod is the simplest type of air terminal and is used in standard (passive) lightning protection systems:
- on flat roofs, parapets and roof edges, at the points set by the system design;
- on roof ridges, chimneys, towers and tall structures;
- together with a roof conductor network (mesh) to cover projecting points.
The air rod is one part of the system: it receives the lightning strike and directs it through the base and the horizontal and down conductors to the earthing system. The system designer sets the number, height and position of the air rods using the protection angle, rolling sphere or mesh method.
How is the protection zone of an air rod determined?
Under IEC 62305-3, the position of air terminals is determined by one of three methods: rolling sphere, protection angle or mesh. The higher the protection class (Class I is the strictest), the smaller the sphere and the finer the mesh, and the closer together the air rods must stand. Their height and spacing are the outcome of this design, not a choice made from a catalogue.
Lightning protection system (LPS) class | Rolling sphere radius | Mesh size |
|---|---|---|
I | 20 m | 5 × 5 m |
II | 30 m | 10 × 10 m |
III | 45 m | 15 × 15 m |
IV | 60 m | 20 × 20 m |
Related components
- Air rod base for mounting on a flat surface: air rod base for flat surfaces.
- Connecting a conductor to a conventional air rod: coupling for connecting conductor to air rod and coupling for connecting tape to air rod.
- A multi-point tip on a copper air rod: three-pronged tip for conventional air rods (MP 016 / MP 020). When you order, please talk to us about matching the air rod tip to the three-pronged fitting.
- All KALOT conventional (Franklin) air rod models: conventional air rods.
Installation sequence
- Mark the position and height of the air rod according to the lightning protection system design.
- Install and secure the base that suits the surface (flat roof, roof ridge or wall).
- Run the lock nut onto the threaded end of the air rod, screw the threaded end into the thread of the base or coupling, and tighten the nut against the base so the air rod stays firm.
- Connect the system conductors to the base or coupling with a suitable connector.
- After installation, check that the connections are tight and that the path to the earthing system has electrical continuity.
Technical notes
- Outdoors, copper darkens over time and forms a surface layer (patina). This colour change is natural and does not harm how the air rod works.
- Use a copper air rod with copper or brass connectors. Direct contact between copper and aluminium or galvanised steel, especially where there is moisture, can make galvanic corrosion worse.
- Longer air rods bear greater wind loads, so choose the base and bracing method to suit their length and the site conditions.
- Taller air rods take a greater wind load. For example, the American standard NFPA 780 requires an air terminal taller than 610 mm to be braced at a height of at least half its length. Choose the base and bracing method to suit the air rod length and the wind conditions at the site.
Inspection and maintenance
During periodic inspections of the lightning protection system, check the air rod, lock nut and conductor connections for loosening, a bent body, corrosion and mechanical damage, and measure the electrical continuity of the path if needed. Inspect also after every known lightning event.
The standards below are listed to help you understand the requirements for air rods and their place in a lightning protection system.
Component standard: IEC 62561-2
This standard sets the requirements for conductors and earth electrodes of lightning protection systems, including air rods (air terminals): material, dimensions, and mechanical and electrical tests. We produce our conventional air rods in line with its requirements.
System design standard: IEC 62305-3
This standard covers the design, installation, inspection and maintenance of a structure's lightning protection system. Air terminals are positioned by the protection angle, rolling sphere or mesh method, and the height and number of air rods are the outcome of this design.
Installing an all-copper conventional air rod on a building
Frequently Asked Questions
What is a conventional copper air rod used for?
A conventional air rod is the air terminal of a lightning protection system: installed on the highest points of the structure, it receives the lightning strike and carries its current through the down conductors to the earthing system.
What is the difference between a conventional air rod, a Franklin air rod and a passive air rod?
There is no difference. These names, along with "rod-type air terminal", all describe the same kind of air terminal: a simple metal air rod that, with no electronic parts, receives the lightning strike and carries it through the conductors to earth. "Franklin" comes from Benjamin Franklin, who invented the air rod, and "passive" means non-active. The opposite type is the electronic (active) ESE air terminal.
Which diameters and lengths are available?
Standard models are made in 16 mm (M16 thread) and 20 mm (M20 thread) diameters, in lengths of 500, 1000, 1500 and 2000 mm. We make other diameters and lengths to order.
How are the height and number of air rods determined?
The lightning protection system designer sets the position, height and number of air rods according to the required protection level, using the protection angle, rolling sphere or mesh method.
How is an air rod installed?
The air rod fixes onto a base or coupling by its threaded end, and the lock nut supplied with it holds it firmly on the base. The system conductors connect to the base or coupling.
How does a copper air rod differ from the stainless steel or nickel-chrome plated copper types?
A solid copper air rod offers high conductivity and works well with copper and brass conductors and connectors. A stainless steel air rod has greater mechanical strength, and the nickel-chrome plated copper type keeps its bright, shiny look. The choice depends on the system's conductor material, the installation environment and the appearance you want.
Can the three-pronged tip be fitted to this air rod?
The three-pronged tip for conventional air rods (MP 016 and MP 020) is made for use with our pointed copper air rods. When you order, please talk to us about matching the air rod tip to the three-pronged fitting.
Does a copper air rod change colour outdoors?
Yes. Over time copper darkens and forms a surface layer. This colour change is natural and has no effect on how the air rod works.
Which standard are these air rods produced to?
We produce our conventional air rods in line with the requirements of IEC 62561-2, and the protection system itself is designed to IEC 62305-3.
How many air rods does my roof need?
It depends on the protection class and the design method. Under IEC 62305-3, for example, the rolling sphere radius for Class I to IV is 20, 30, 45 and 60 m respectively, and every point of the structure the sphere can touch must be covered by an air terminal. The system designer decides the number and position of the air rods, and we are at your side when you choose the model and installation parts.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.