Insulated one-hole clip for fixing conductors and cables to walls
Order Code: ICG 035 · ICG 050 · ICG 070 · ICG 095
Last updated:
At KALOT Group we offer the insulated one-hole clip for fixing PVC-sheathed copper conductors, such as green and yellow earth cable, to walls, façades and other surfaces. The body of the clip is a galvanised steel strip that loops around the cable, and the insulating cover on the loop protects the sheath from direct contact with metal, from cuts and from abrasion. The two tabs sit one on top of the other and fasten to the surface with a single screw: a quick, clean and reliable installation. We provide this clip in four sizes for 35, 50, 70 and 95 mm² conductors (ICG 035 to ICG 095), so your cable run is complete and consistent alongside KALOT's other earthing and lightning protection equipment.
Secure fixing for sheathed cable, with no damage to the sheath
Sheathed conductor runs, whether down conductors or earthing and bonding, need to be fixed neatly and firmly to the surface without damaging the cable sheath. That is exactly what we offer this clip for: the strength of a steel strip, an insulating cover on the loop and installation with just one screw.
- For PVC-sheathed copper conductors
- Galvanised steel with an insulating cover on the loop
- Installed with one screw through both tabs
- Four sizes: 35 to 95 mm²
Protects the cable sheath
The insulating cover on the loop sits between the metal strip and the PVC sheath, preventing cuts and abrasion to the cable sheath at the fixing point.
Quick installation with one screw
The clip's two tabs sit one on top of the other and one screw passes through both, so each clip needs only one hole in the surface.
Galvanised steel strip
The steel body with its galvanised coating gives the clip its mechanical strength and is protected against rust.
Chosen by cross-section
Four models, ICG 035, ICG 050, ICG 070 and ICG 095, for conductors from 35 to 95 mm².
A complete range from one supplier
Order this clip from us together with green and yellow earth cable, connectors and other earthing and lightning protection equipment, all in one place. Our specialists are with you as you choose the items for your project.
Technical Product Information
Feature | Value |
|---|---|
Product type | Insulated one-hole clip for fixing conductors and cables to walls (Isolated One Hole Cable Clip) |
Application | Fixing PVC-sheathed copper conductors to walls, façades and other surfaces |
Body material | Galvanised steel |
Cover | Insulating cover on the clip's loop; tabs uncovered |
Structure | Bent strip with a cable loop and two overlapping tabs; round hole in the upper tab and oval hole in the lower tab |
Conductor cross-section | Models for 35, 50, 70 and 95 mm² |
Cable outer diameter | 9 to 18.2 mm, depending on the model |
Clip dimensions | Loop inner diameter 12 to 19 mm and strip width 15 or 20 mm, depending on the model |
Installation method | One screw through both tabs into the surface |
Recommended screw | M6 for ICG 035 and ICG 050; M8 for ICG 070 and ICG 095 |
Order code | Conductor cross-section (mm²) | Cable outer diameter (mm) | Loop inner diameter D (mm) | Strip width b (mm) | Hole d (mm) / screw |
|---|---|---|---|---|---|
ICG 035 | 35 | 9 to 11.7 | 12 | 15 | 6.4 / M6 |
ICG 050 | 50 | 10.6 to 13.9 | 14 | 15 | 6.4 / M6 |
ICG 070 | 70 | 12.1 to 16 | 16 | 20 | 8.4 / M8 |
ICG 095 | 95 | 14.1 to 18.2 | 19 | 20 | 8.4 / M8 |
All models are galvanised steel with an insulating cover. The positions of D, b and d are shown in the "Technical drawing" tab. Our products are continually improved and some dimensions may be updated, so please confirm the final dimensions with our specialists before buying. For a cable diameter outside the table, please contact us as well.
Click to view enlarged
The technical drawing shows the side and top views of the clip: the bent strip with the cable loop, the two overlapping tabs and the screw position. The symbols D (loop inner diameter), b (strip width) and d (screw hole) appear on the drawing with the dimension table for each model. PDF and SVG files of the drawings can be downloaded from the documents and downloads section of this page.
Click to view enlarged
Where is it used?
- Fixing sheathed copper down conductors to building walls and façades
- Fixing PVC-sheathed earth and bonding cable on surface-mounted runs
- Runs where the cable sheath must not be in direct contact with the clip's metal strip
For bare round conductors we recommend the one-hole clip for fixing conductors to walls. You can also see our green and yellow sheathed copper cable on the green and yellow copper earth cable page.
Installation steps
- Choose the clip size by the conductor cross-section and make sure the sheathed cable sits in the loop without excessive pressure.
- Lay the cable straight and free of twists on the surface and mark the clip positions. The system designer sets the clip spacing.
- Drill the screw position and insert a suitable wall plug in masonry walls.
- Place the cable inside the clip's loop and hold the two tabs together over the hole.
- Pass the screw through both tabs and tighten it firmly, without overtightening, so the cover and cable sheath are not crushed.
Inspection and maintenance
During periodic inspections, check that clips and screws are tight, that the insulating cover and cable sheath are intact at the clip, and that there is no rust on the strip or tabs. Replace any clip whose cover has cracked or shifted, or that has come loose.
How it differs from the plain one-hole clip
Both clips share the same structure: a bent strip, a loop and two tabs with one screw. The plain one-hole clip (copper, galvanised or stainless steel) is for bare round conductors, and its metal touches the conductor directly. The insulated clip is for PVC-sheathed conductors, and the insulating cover on the loop sits between the clip's metal and the cable sheath.
Choosing the size
The clip model is chosen by the conductor cross-section: ICG 035 for 35, ICG 050 for 50, ICG 070 for 70 and ICG 095 for 95 mm². The cable should sit in the loop with no play and no excessive pressure. The suitable cable outer diameter for each model is in the "Models and order codes" table.
Technical notes
- The insulating cover is designed to protect the cable sheath mechanically. The electrical insulation of the run comes from the cable's own sheath, and this clip does not replace insulation or separation distance in lightning protection system design.
- The clip holds the conductor in place; connecting conductors to each other and to the earthing system is done with dedicated connection parts.
- The recommended screw is M6 for ICG 035 and ICG 050 and M8 for ICG 070 and ICG 095. Match the wall plug to the surface material and the screw material to the installation environment.
- For special conditions, such as high temperatures or chemical environments, please consult our technical specialists before ordering.
- Where the conductor must stand off from the wall, use the BPH 76 down conductor stand-off base.
The following standards are the reference for the design, installation and fixing of conductors in a lightning protection system.
System design: IEC 62305-3
This standard covers the design, installation, inspection and maintenance of a structure's lightning protection system, and requires conductors to be firmly fixed to prevent movement and mechanical damage. The system designer sets the number and spacing of supports.
ESE lightning protection systems: NF C 17-102
For fixing down conductors, this standard recommends three support points per metre; the supports must be compatible with the surface they are fixed to.
Round conductor holding clamps for walls
Documents & Downloads
Drawings & schematics
Frequently Asked Questions
What is an insulated one-hole clip used for?
For fixing PVC-sheathed copper conductors, such as green and yellow earth cable, to walls, façades and other surfaces. The cable sits inside the clip's loop and one screw fastens the clip to the surface.
How does this clip differ from the plain one-hole clip?
The plain one-hole clip is for bare round conductors. The insulated clip has an insulating cover on its loop and is made for PVC-sheathed cable, so the metal of the clip does not sit directly on the cable sheath.
What is the clip made of?
Galvanised steel with an insulating cover on the loop; the tabs are uncovered.
Which model should I choose?
Choose the model by the conductor cross-section and the cable's outer diameter: ICG 035 for 35, ICG 050 for 50, ICG 070 for 70 and ICG 095 for 95 mm². The suitable cable diameter and dimensions of each model are in the "Models and order codes" table. For a cable diameter outside the table, please contact us.
Is it also suitable for bare copper conductor?
For bare conductors we recommend our plain one-hole clip, available in three materials: copper, galvanised steel and stainless steel. The insulated clip is designed for sheathed cable.
How far apart should the clips be on the wall?
The system designer sets the clip spacing. For down conductors in ESE lightning protection systems, NF C 17-102 recommends three support points per metre.
Does the insulating cover electrically separate the conductor from the wall?
The cover is designed to protect the cable sheath mechanically. The electrical insulation of the run comes from the cable's own sheath, and this clip does not replace insulation or separation distance in the protection system design.
Which screw should I use for installation?
We recommend an M6 screw for ICG 035 and ICG 050 and an M8 screw for ICG 070 and ICG 095. Choose the wall plug to suit the surface material.
Have a Technical Question?
KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.