Solar power plant earthing and lightning protection

A solar plant is built on open, exposed ground with thousands of metres of DC cable and hundreds of metal structures. Most failures seen after a storm, such as inverters shutting down, burnt tracker controllers and false insulation fault alarms, come from an earthing system designed only for power-frequency faults that never took lightning into account.

We have equipped about 140 solar power plants with lightning protection, earthing and bonding systems, working alongside the developers and operators on these projects. This page shares what we have seen on them: at which stage of a plant's life each mistake happens.

About 140solar power plants equipped with lightning protection and earthing
12provinces, from Golestan and Azerbaijan to Bushehr and Fars
5stages, at each of which an earthing system can fail

Common mistakes, stage by stage

The plant life cycle: knowing the ground, design, construction, commissioning and operation.

Knowing the ground

Desert soil and corrosive soil

The problem

Designing dry soil around a single average figure. Soil resistivity varies with depth and across the seasons, and a design based on surface measurements fails in summer.

Ignoring soil corrosivity. Galvanised steel piles in damp or saline soil, next to bare copper conductors, act as anodes and rot away well before the end of the plant's life.

Our answer:
Soil resistivity measurement by the Wenner method down to depth at several points, and selection of electrode and conductor materials to suit the soil and structure before any equipment is bought.
Design

Earthing designed only for grid faults

The problem

An earthing system sized only for a 50 Hz short circuit does not disperse high-frequency lightning current. If the air rods are not far enough from the panels, part of the lightning current enters the DC cabling, and if they are badly placed they shade the cells. A DC arc does not extinguish by itself either, so the DC side SPD must be one made specifically for photovoltaics.

Our answer:
Earthing system design with a mesh across the whole plant, separation distance calculation and placement of conventional air rods without significant shading, and photovoltaic system surge protective devices (SPDs) of Type 1 or 2 based on the lightning protection design and inverter type.
Construction

Induction loops and buried connections

The problem

When positive and negative cables are run apart, or a data cable crosses several strings, a large loop forms in which a nearby strike induces voltage. Bolted joints underground and copper to galvanised joints in soil also fail over time.

Our answer:
Supervision of the cable route, KALweld® exothermic welding for buried joints, and copper connected to galvanised structures only in air above ground, using tinned cable lugs or a brass clamp with an anti-corrosion coating.
Commissioning

Handover without figures

The problem

If protective earth continuity and insulation resistance are not recorded on handover day, a small earth fault goes unnoticed for years until the day it starts a fire.

Our answer:
Earthing system testing, continuity testing and a written report as the baseline for comparison.

References: IEC 62305-2 to 4, IEC TR 63277, IEC 60364-7-712, IEC 61643-31 and 32, IEC 62446-1, IEEE 81

Our power plants in 12 provinces

Examples: Kahak power plant in Qazvin, the 20 MW plant in Bahabad, the 10 MW plant in Tabas, Dasht-e Abbas in Dehloran, Shahid Soleimani Square in Kish, and the universities of Maragheh, Madani and Sahand.

  • Golestan
  • Bushehr
  • Fars
  • East Azerbaijan
  • West Azerbaijan
  • Ilam
  • Kish (Hormozgan)
  • Ardabil
  • Semnan
  • Qazvin
  • Yazd
  • South Khorasan

What to send for design and a quotation

Array layout and capacity, structure type (fixed or tracker) and its material, inverter type (central or string), DC and data cable routes, the location of the substation and control building, and soil measurement results if you have them.

Frequently Asked Questions

Does a solar plant need lightning protection, or is earthing the structure enough?

It depends on the risk assessment. Large plants usually need air rods, positioned so that the separation distance is maintained and they cast no significant shadow on the panels.

Can an AC SPD be installed on the DC side?

No. The DC side needs SPDs designed for photovoltaics, because a DC arc does not extinguish by itself.

Can a copper conductor be connected to a galvanised structure?

Yes, in air and above ground, with a tinned cable lug or a brass clamp and an anti-corrosion coating. In soil, copper and galvanised steel must not be connected to each other.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.