Conductor-to-earth rod exothermic welding

Complete Product Overview

CE17 exothermic weld: two parallel copper conductors to the top of an earth rod

Last updated:

The CE17 exothermic weld joins two parallel copper conductors to the top of an earth rod for earthing networks, bonding and lightning protection. We produce its graphite mould under the KALweld® brand and offer it with weld powder and a handle. Once welded, the joint is one piece with the conductors, with no nuts or bolts to work loose over time. KALweld® welds have been tested to IEEE 837 and UL 467 at the Power and Water University of Technology (Shahid Abbaspour) and have passed the freezing, thermal cycling and short-circuit tests.

The CE17 mould is made for 14.2 and 17.2 mm earth rods and 16 to 300 mm² conductors. The mould and powder code for each size is in the "Mould and powder selection" table, and the HC 01 handle fits all its sizes.

Technical Product Information

Click to view enlarged

Mould body material: graphite; mould lid material: stainless steel; suitable handle: HC 01.

CE17 mould and powder selection table

Earth rod diameter (mm)

Thread (inch)

Conductor (mm²)

Weld powder

Mould code

⁦14.2⁩

⁦5/8"⁩

⁦16⁩

⁦KWD 065⁩

⁦CE17-142-016⁩

⁦14.2⁩

⁦5/8"⁩

⁦25⁩

⁦KWD 090⁩

⁦CE17-142-025⁩

⁦14.2⁩

⁦5/8"⁩

⁦35⁩

⁦KWD 090⁩

⁦CE17-142-035⁩

⁦14.2⁩

⁦5/8"⁩

⁦50⁩

⁦KWD 115⁩

⁦CE17-142-050⁩

⁦14.2⁩

⁦5/8"⁩

⁦70⁩

⁦KWD 150⁩

⁦CE17-142-070⁩

⁦14.2⁩

⁦5/8"⁩

⁦95⁩

⁦KWD 200⁩

⁦CE17-142-095⁩

⁦14.2⁩

⁦5/8"⁩

⁦150⁩

⁦2 × KWD 150⁩

⁦CE17-142-150⁩

⁦14.2⁩

⁦5/8"⁩

⁦185⁩

⁦2 × KWD 150⁩

⁦CE17-142-185⁩

⁦14.2⁩

⁦5/8"⁩

⁦240⁩

⁦2 × KWD 200⁩

⁦CE17-142-240⁩

⁦14.2⁩

⁦5/8"⁩

⁦300⁩

⁦2 × KWD 250⁩

⁦CE17-142-300⁩

⁦17.2⁩

⁦3/4"⁩

⁦16⁩

⁦KWD 090⁩

⁦CE17-172-016⁩

⁦17.2⁩

⁦3/4"⁩

⁦25⁩

⁦KWD 090⁩

⁦CE17-172-025⁩

⁦17.2⁩

⁦3/4"⁩

⁦35⁩

⁦KWD 090⁩

⁦CE17-172-035⁩

⁦17.2⁩

⁦3/4"⁩

⁦50⁩

⁦KWD 115⁩

⁦CE17-172-050⁩

⁦17.2⁩

⁦3/4"⁩

⁦70⁩

⁦KWD 150⁩

⁦CE17-172-070⁩

⁦17.2⁩

⁦3/4"⁩

⁦95⁩

⁦KWD 200⁩

⁦CE17-172-095⁩

⁦17.2⁩

⁦3/4"⁩

⁦150⁩

⁦2 × KWD 150⁩

⁦CE17-172-150⁩

⁦17.2⁩

⁦3/4"⁩

⁦185⁩

⁦2 × KWD 150⁩

⁦CE17-172-185⁩

⁦17.2⁩

⁦3/4"⁩

⁦240⁩

⁦2 × KWD 250⁩

⁦CE17-172-240⁩

The thread on the earth rod top must be cut off before welding.

Need another size, or do your conductors not match this table? Send the conductor details or the joint drawing to our specialists and they will recommend the right mould.

KALweld® exothermic welding: copper wire to earth rod

Drag to rotate; scroll to zoom.Open full screen

Documents & Downloads

Certificates & test reports

  • Laboratory test report for KALweld® four-way conductor-to-conductor exothermic weld | Power and Water University of TechnologyPersian · 2017-03-14
  • Laboratory test report for the KALweld® conductor-to-conductor T exothermic weld | Power and Water University of TechnologyPersian

Installation & application guides

Frequently Asked Questions

What is the CE17 mould code for the smallest size?

For 14.2 / 5/8" / 16, use mould CE17-142-016 with KWD 065 powder. All other sizes are listed in the table on this page.

How many welds can each mould make?

Our moulds are made of high-grade graphite and, used correctly and according to the instructions, last for 50 to 60 welds. Cleaning with a wire brush, knocks, moisture and opening too early all shorten mould life.

After ignition, when should the mould be opened?

Wait at least one minute for the molten metal to solidify, then open the mould carefully.

Which weld powder is right?

The powder size for each conductor size is shown in the table on this page and on the mould lid. Do not substitute powder of another size or another mould.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.