Lightning protection clamps, connectors and fittings

Complete Product Overview

Stainless steel hose clamp (Hose Clamp) for lightning protection down conductors

Last updated:

KALOT's stainless steel hose clamp fixes the down conductor of a lightning protection system, that is copper tape or copper wire, to a tubular air terminal mast, a guyed mast base, a telecommunications tower or any other cylindrical object. The stainless steel band wraps around the pipe and conductor, and tightening the worm screw presses the conductor against the pipe surface with no drilling or welding. In usual practice these clamps are installed every 30 to 33 cm along the whole mast, and stainless steel offers good resistance to rust outdoors. Three models, CCS35, CCS68 and CCS11, are offered for diameters of 33 to 57, 65 to 89 and 105 to 127 mm.

We provide these clamps in three sizes, so your down conductor stays neat and lasting on any mast or tower.

A firm, neat down conductor from the top of the mast to its foot

In a lightning protection system mounted on a tubular mast, the down conductor must be fixed to the pipe along the mast's whole length. KALOT's stainless steel hose clamp does this with a stainless steel band and a worm screw: no drilling, no welding, and it can be retightened during periodic checks.

  • Fixes copper tape or wire to pipes
  • Stainless steel for outdoor installation and corrosion prevention
  • Three sizes for diameters from 33 to 127 mm
  • No drilling of the pipe or conductor
  • Stainless steel, made for the outdoors

    The clamp stays in rain and sun for the whole life of the system. Stainless steel resists rust and, unlike an ordinary steel clamp or a damaged galvanised one, does not lose its clamping force or the neat look of the conductor run to rust.

  • No drilling or welding

    The conductor is pressed between the band and the pipe, so neither the mast pipe nor the conductor is drilled. NF C 17-102 does not permit drilling a down conductor to fix it to its support.

  • For copper tape and wire

    One type of clamp for both forms of down conductor: tape sits flat on the pipe and wire is held under the band.

  • Simple selection by diameter

    Three models, CCS35, CCS68 and CCS11; the range of each model must cover the diameter of the pipe plus the conductor. For other diameters, please contact KALOT Group.

  • Quick installation with simple tools

    The worm screw tightens with a spanner or screwdriver, and clamps that have loosened can be retightened during periodic checks.

Technical Product Information

Feature

Value

Product type

Hose clamp (band clamp with worm screw) (Clamping Collar)

Material

Stainless steel (Stainless Steel)

Application

Fixing down conductors to tubular air terminal masts, guyed mast bases, telecommunications towers and other cylindrical objects

Conductor type

Copper tape or copper wire

Fixing method

Slotted band around the pipe and conductor; tightened with a worm screw

Common installation spacing

About 30 to 33 cm along the mast (three points per metre)

Models

⁦CCS35⁩, ⁦CCS68⁩, ⁦CCS11⁩

Models and clamping diameter range

Order code

Clamping diameter range (mm)

Material

⁦CCS35⁩

33 to 57

Stainless steel

⁦CCS68⁩

65 to 89

Stainless steel

⁦CCS11⁩

105 to 127

Stainless steel

The outer diameter of the pipe plus the conductor thickness must fall within the range of the chosen model. For other sizes, please contact our sales department.

Hose clamp and cable tie on a tubular pole

Drag to rotate; scroll to zoom.Open full screen

Frequently Asked Questions

What is a hose clamp used for in a lightning protection system?

For fixing down conductors, that is copper tape or copper wire, to tubular air terminal masts, guyed mast bases, telecommunications towers and other cylindrical objects. The stainless steel band wraps around the pipe and conductor, and tightening the screw presses the conductor against the pipe.

How far apart should the clamps be on the air terminal mast?

In KALOT Group's usual practice, one clamp is installed every 30 to 33 cm. This spacing is consistent with the NF C 17-102 recommendation of three support points per metre. On each project, the system designer sets the final spacing.

Which clamp size should I choose?

Measure the outer diameter of the pipe plus the thickness of the conductor: CCS35 for 33 to 57, CCS68 for 65 to 89 and CCS11 for 105 to 127 mm. For an air terminal mast with an outer diameter of 38.25 mm, we recommend CCS35. For diameters between these ranges, please contact us.

Why is a stainless steel clamp better than a galvanised one?

Clamps stay outdoors for years. A galvanised coating is lost once it is damaged and the clamp then rusts; rust reduces the clamping force and stains the mast and façade. Stainless steel resists rust, and the clamp holds its function better over the life of the system.

Is a hose clamp enough to connect the conductor to the air terminal?

No. The hose clamp is a part that holds the conductor along the mast. Connecting the down conductor to the air terminal or its mast, joining two conductors and connecting to the earthing system must be done with connection parts dedicated to each task.

Is this clamp also suitable for copper wire?

Yes, this clamp suits both copper tape and copper wire. In both cases, the diameter of the pipe plus the conductor must fall within the range of the chosen model.

What should I watch for if the mast is galvanised and the conductor is copper?

In damp or corrosive environments, direct contact between copper and the zinc (galvanised) coating can lead to galvanic corrosion. Review a suitable solution with the system designer, such as tinned copper tape or stainless steel tape.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.