KALOT Group
This translation is an AI-assisted draft pending human review. It is not indexed for search yet.Read the reviewed Persian original
Conductor-to-steel plate exothermic welding

Complete Product Overview

CS9 exothermic weld: through-run copper conductor lying flat on a steel plate

Last updated:

The CS9 exothermic weld connects a through-run copper conductor lying flat on a steel plate in earthing, bonding and lightning protection networks. We manufacture its graphite mould under our KALweld® brand and supply it complete with weld powder and handle. Once welded, the joint becomes one piece with the conductors, with no nuts and bolts to loosen over time. KALweld® welds have been tested to IEEE 837 and UL 467 at the Power and Water University of Technology (Shahid Abbaspour) and successfully passed the freeze, thermal cycling and short-circuit tests.

CS9 is the lighter, lower-profile version of this joint and suits smaller conductors and thinner steel plates. For heavier joints, see the CS2 exothermic weld.

The CS9 mould is made for 16 to 240 mm² conductors. The mould and powder code for each size is in the "Mould and powder selection" table, and the HC 01 handle suits all its sizes.

Technical Product Information

Click to view enlarged

Mould body material: graphite; mould lid material: stainless steel; suitable handle: HC 01.

CS9 mould and powder selection table

Main conductor (mm²)

Weld powder

Mould code

⁦16⁩

⁦KWD 045⁩

⁦CS9-016⁩

⁦25⁩

⁦KWD 045⁩

⁦CS9-025⁩

⁦35⁩

⁦KWD 090⁩

⁦CS9-035⁩

⁦50⁩

⁦KWD 090⁩

⁦CS9-050⁩

⁦70⁩

⁦KWD 115⁩

⁦CS9-070⁩

⁦95⁩

⁦KWD 115⁩

⁦CS9-095⁩

⁦120⁩

⁦KWD 150⁩

⁦CS9-120⁩

⁦150⁩

⁦KWD 200⁩

⁦CS9-150⁩

⁦185⁩

⁦KWD 250⁩

⁦CS9-185⁩

⁦240⁩

⁦2 × KWD 150⁩

⁦CS9-240⁩

Need another size, or do your conductors not match this table? Send the conductor details or the joint drawing to our specialists and they will recommend the right mould.

KALweld® exothermic welding: copper wire to steel plate

Drag to rotate; scroll to zoom.Open full screen

Documents & Downloads

Certificates & test reports

  • Laboratory test report for KALweld® four-way conductor-to-conductor exothermic weld | Power and Water University of TechnologyPersian · 2017-03-14
  • Laboratory test report for the KALweld® conductor-to-conductor T exothermic weld | Power and Water University of TechnologyPersian

Installation & application guides

Frequently Asked Questions

What is the CS9 mould code for the smallest size?

For size 16, use mould CS9-016 with KWD 045 powder. The other sizes are in the table on this page.

How many welds can each mould make?

Our moulds are made of high-grade graphite and, used correctly and according to the instructions, last for 50 to 60 welds. Cleaning with a wire brush, knocks, moisture and opening too early all shorten mould life.

After ignition, when should the mould be opened?

Wait at least one minute for the molten metal to solidify, then open the mould carefully.

Which weld powder is right?

The powder size for each conductor size is shown in the table on this page and on the mould lid. Do not substitute powder of another size or another mould.

Have a Technical Question?

KALOT Group's technical experts are ready to answer your questions about lightning rods and earthing systems.