The key role of polarisation resistance in earthing system performance

When designing earthing systems, lowering the ohmic resistance of the soil is not enough on its own: if a ground improvement material causes polarisation and corrosion of the electrode, the performance of the whole system is called into question. That is why international standards such as IEC 62561-7 and ASTM G59-97 introduce an index called polarisation resistance (Polarization Resistance, Rp), so that besides ohmic resistance, the chemical stability and non-corrosiveness of ground improvement materials are also assessed.

Polarisation resistance expresses the ratio of the change in electrode potential to the change in current under polarisation conditions. It is inversely proportional to the corrosion rate of the metal, so a high value means greater stability and less corrosion.


Three-electrode cell and polarisation resistance measuring equipment for corrosion assessment.

The measurement is made by the potentiodynamic polarisation method using a three-electrode potentiostat in accordance with ASTM G59. The corrosion rate is then calculated with the standard formulas (ASTM G102). The diagram below shows the principles of this test:


(a) Laboratory set-up for the potentiodynamic polarisation test using a three-electrode system, in which a metal sample of the earth electrode serves as the working electrode.

(b) A simplified schematic of the three-electrode configuration.

This test method sets out a procedure for determining how corrosive ground improvement materials are. The corrosion rate is found with the potentiodynamic polarisation resistance method to ASTM G59-97, and the results are converted to a corrosion rate according to ASTM G102-89. The test matters because ground improvement materials must be physically and chemically inert towards earth electrodes, so that the earth electrode and the incoming conductor do not corrode.

Under IEC 62561-7, the minimum acceptable polarisation resistance values are given in the table below:

Minimum polarisation resistance to IEC 62561-7

Earth electrode type

Corrosive environment

Non-corrosive environment

Copper-bonded steel electrode

 Rp>8Ω.m²

 Rp>4Ω.m²

Galvanised steel electrode

 Rp>7.6Ω.m²

 Rp>3Ω.m²

Website membership required · Sign in or join
  • These values show that a ground improvement material must not only conduct well but also be inert towards the electrode and stable against corrosion.