Earthing system installation guide with GIM®

Installation instructions: horizontal electrode in a trench with GIM®

Installation instructions: vertical earth rod electrode in the ground with GIM®

Installation instructions: plate electrode in the ground with GIM®

Project/site name:
Installation method:
All three methods: horizontal trench, earth rod and copper earth plateHorizontal trench (horizontal electrode in a trench)Earth rod (vertical earth rod electrode in the ground)Copper earth plate (plate electrode in the ground)
Product:
GIM®
Print date:
16 November 2026

Review version: Draft 1 (awaiting technical approval), 24 September 2026. Items that need technical review are marked with an asterisk or a note in the drawings and under the tables.

GIM® installation guide

Mixing instructions and three installation methods for GIM® ground improvement material: horizontal trench, earth rod and copper earth plate. You can print each method separately.

Draft for review: This page goes through KALOT's technical approval before public release. Items that need a technical decision are marked with an asterisk under each table.

Preparing the GIM® mix

Mix each bag of GIM with 8 litres of treated water and 2 kg of cement.

  • Add nothing to the mix other than water and cement.
  • While preparing the mix, keep soil, sand, plastic and pieces of the bag out of it.
  • GIM and GIM Light are installed the same way and with the same mixing ratio. These instructions do not apply to ECO GIM, which is installed differently.

Method 1: horizontal trench with bare copper conductor or copper tape

Installation instructions: horizontal electrode in a trench with GIM®

1. Application

The earth conductor (bare copper conductor or copper tape) is laid horizontally in the trench and embedded in the GIM mix from below and above.

3. Execution drawing: final cross-section

Detailed drawing: final cross-section
Final cross-section: GIM and GIM Light in a horizontal trench Cross-section of the horizontal earthing trench, at least 10 cm wide and 75 cm deep: 5 cm GIM bed, copper conductor, 5 cm GIM cover, 15 cm of compacted screened soil and backfill. Trench width: min. 10 cm Trench depth: min. 75 cm GIM bed: min. 5 cm GIM cover: min. 5 cm Screened soil: min. 15 cm Backfill from excavated soil Screened soil, tamped and compacted GIM or GIM Light mix Bare copper conductor or copper tape Native soil Ground level KALOT Group | GIM and GIM Light installation guide | not to scale

Swipe the drawing left and right to see all dimensions.

Figure 1: Final cross-section of the horizontal trench installation with minimum dimensionsDownload drawing (SVG)

2. Installation stepsDetailed drawing

  1. Horizontal trench, step 1: excavating a trench at least 10 cm wide and 75 cm deep Excavating a trench at least 10 cm wide and 75 cm deep Width min. 10 cm Depth min.75 cm 1

    Step 1: Excavate a trench at least 10 cm wide and at least 75 cm deep. Where the local frost depth is greater, check the right depth for the site.

  2. Horizontal trench, step 2: covering the trench floor with at least 5 cm of GIM mix Covering the trench floor with at least 5 cm of GIM mix Min. 5 cm GIM mix bed 2

    Step 2: Cover the trench floor with at least 5 cm of GIM mix.

  3. Horizontal trench, step 3: laying the bare copper conductor or copper tape on the GIM bed Laying the bare copper conductor or copper tape on the GIM bed Bare copper conductoror copper tape on the GIM bed 3

    Step 3: Lay the bare copper conductor or copper tape on the GIM bed.

  4. Horizontal trench, step 4: covering the conductor with at least 5 cm of GIM mix Covering the conductor with at least 5 cm of GIM mix Min. 5 cm GIM cover over the conductor 4

    Step 4: Cover the conductor with at least 5 cm of GIM mix; the whole surface of the conductor must be in full contact with the mix.

  5. Horizontal trench, step 5: placing at least 15 cm of screened soil and tamping it Placing at least 15 cm of screened soil and tamping it Min. 15 cm Screened soil, tamped 5

    Step 5: Cover the GIM with at least 15 cm of screened soil, then tamp and compact it.

  6. Horizontal trench, step 6: filling the rest of the trench with excavated soil Filling the rest of the trench with excavated soil Excavated soil 6

    Step 6: Fill the rest of the trench completely with the excavated soil.

4. Consumption table

In each cell, the upper number is the trench length (cm), exactly as in the brochure. The lower number is the geometric volume of the same cross-section and length (width × height × length ÷ 1000), in litres; this number is calculated and does not appear in the brochure.

GIM brochure table no. 1: trench length filled by one bag (cm)
Trench width (cm)GIM height (cm)
5 *10152025
1037818.90 litres18918.90 litres12618.90 litres9418.80 litres7619.00 litres
1525218.90 litres12618.90 litres8418.90 litres6318.90 litres5018.75 litres
2018918.90 litres9418.80 litres6318.90 litres4718.80 litres3819.00 litres
2515118.88 litres7619.00 litres5018.75 litres3819.00 litres3018.75 litres
3012618.90 litres6318.90 litres4218.90 litres3118.60 litres2518.75 litres
3510818.90 litres5418.90 litres3618.90 litres2718.90 litres2219.25 litres
409418.80 litres4718.80 litres3118.60 litres2419.20 litres1919.00 litres

5. Notes and technical limits

* Needs technical review: The 5 cm height column is not valid for a full installation of this method: the instructions call for at least 5 cm of GIM below the conductor and 5 cm above it. Do not use this column until a technical decision is made.

Each number is the trench length (cm) that one bag fills at the given width and height.

Geometric volume: The geometric volume is calculated only from the dimensions and the printed length of each cell. That each bag fills about 19 litres follows from the brochure figures themselves and is not a tested yield of the mortar after mixing.

Table source: GIM brochure, 15 kg bag. The figures are quoted exactly from the brochure and are not an engineering calculation of the bag count.

Website membership required · Sign in or joinBack to the mixing instructions

Method 2: earth rod

Installation instructions: vertical earth rod electrode in the ground with GIM®

1. Application

The earth rod is set vertically in a hole and the space around it is filled with GIM mix up to the top of the earth rod.

3. Execution drawing: final cross-section

Detailed drawing: final cross-section
Final cross-section: GIM and GIM Light with an earth rod Cross-section of the earth rod hole, at least 15 cm in diameter: earth rod driven 15 cm into the floor, its top about 15 cm below ground level, continuous GIM cover up to the top of the earth rod, conductor connection, backfill and optional access chamber. Hole diameter: min. 15 cm Hole depth = earth rod length About 15 cm 15 cm driven into the floor Access chamber (if the project needs it) Conductor connection:exothermic weld or suitable clamp Earth conductor / tape Continuous GIM or GIM Light coverUp to the earth rod top Earth rod Backfill Native soil Ground level KALOT Group | GIM and GIM Light installation guide | not to scale

Swipe the drawing left and right to see all dimensions.

Figure 1: Final cross-section of the earth rod installation; the access chamber is dashed and optionalDownload drawing (SVG)

2. Installation stepsDetailed drawing

  1. Earth rod, step 1: drilling a hole at least 15 cm in diameter and as deep as the earth rod is long Drilling a hole at least 15 cm in diameter and as deep as the earth rod is long Diameter min. 15 cm Depth = earth rod length 1

    Step 1: Make a hole at least 15 cm in diameter and as deep as the earth rod is long.

  2. Earth rod, step 2: driving the earth rod 15 cm into the floor and connecting the conductor to its top Driving the earth rod 15 cm into the floor and connecting the conductor to its top About 15 cm 15 cmDriven Earth rod Exothermic weldor clamp 2

    Step 2: Place the earth rod in the hole and, where possible, drive it 15 cm into the floor so that its top sits about 15 cm below ground level. At the same stage, connect the earth conductor or tape to the earth rod with exothermic welding or a suitable clamp.

  3. Earth rod, step 3: pouring and compacting GIM mix around the earth rod up to its top Pouring and compacting GIM mix around the earth rod up to its top GIM mix, compacted Up to the earth rod top 3

    Step 3: Pour the GIM mix around the earth rod and compact it until the rod is fully covered all round and up to its top.

  4. Earth rod, step 4: filling the rest of the hole with excavated soil and the optional access chamber Filling the rest of the hole with excavated soil and the optional access chamber Excavated soil Access chamber(optional) 4

    Step 4: Fill the rest of the hole with the excavated soil. Where the project needs it, use a dedicated access chamber for later access.

4. The KALOT polymer chamber

Two real photos of the chamber from outside and inside, and beside them a conceptual cutaway of the same chamber to show the approximate conductor route.

Real photoInside the KALOT polymer chamber without its lid: black body with a square opening and rounded corners, a horizontal copper busbar with four holes over the round opening, and the cylindrical neck below the body.
Figure 2: Inside view: four-hole copper busbar over the opening of the cylindrical neck. View large
Real photoOutside of the KALOT polymer chamber: black lid with raised KALOT lettering and the earth symbol on the ribbed body, and the cylindrical neck below it.
Figure 3: Outside view: KALOT lid with the earth symbol, ribbed body and cylindrical neck. View large

The photos only show what the chamber looks like; no size, hole spacing, clamp type or electrical rating should be read from them.

Conceptual cutaway
Conceptual view of the KALOT polymer chamber (cutaway, not to scale) Conceptual, undimensioned cutaway of the KALOT polymer chamber: KALOT lid, square opening, ribbed polymer shell, cylindrical neck and four-hole copper busbar. The conductor route from the top of the earth rod to the busbar and the outgoing conductor is illustrative; the terminal and clamp layout is not yet approved. Conceptual view: not to scale, no dimensions Terminal, clamp and conductor layout not yet approved KALOT lid Square opening Ribbed polymer shell Copper busbar, four holes Cylindrical neck Conductor from earth rod topIllustrative route Outgoing conductor, approximate route Earth rod top; its positionrelative to the chamber not approved GIM around the earth rod Ground level Dashed = conceptual

Swipe the picture left and right to see the drawing and its labels.

Figure 4: Conceptual view, not to scale and without dimensions. The conductor routes are dashed and approximate; the terminal layout, the clamp type and the position of the top of the earth rod relative to the chamber are not yet technically approved. View large (SVG)

5. Consumption table

In each cell, the upper number is the bag count, exactly as in the brochure. The lower number is the gross geometric volume of a cylindrical hole of the same diameter and depth (area of a circle of that diameter × depth), in litres; this number is calculated and does not appear in the brochure.

GIM brochure table no. 2: number of bags by hole diameter and depth
Hole diameter (cm)Hole depth (m)
1.21.522.534.56
10 *19.42 litres111.78 litres115.71 litres119.63 litres123.56 litres235.34 litres247.12 litres
15121.21 litres126.51 litres235.34 litres244.18 litres353.01 litres479.52 litres6106.03 litres
20237.70 litres247.12 litres362.83 litres478.54 litres594.25 litres7141.37 litres10188.50 litres
25358.90 litres473.63 litres598.17 litres6122.72 litres8147.26 litres12220.89 litres16294.52 litres
30484.82 litres6106.03 litres7141.37 litres9176.71 litres11212.06 litres17318.09 litres22424.12 litres
356115.45 litres8144.32 litres10192.42 litres13240.53 litres15288.63 litres23432.95 litres31577.27 litres
408150.80 litres10188.50 litres13251.33 litres17314.16 litres20376.99 litres30565.49 litres40753.98 litres

6. Notes and technical limits

* Needs technical review: The 10 cm diameter row is quoted from the brochure, but it is smaller than the minimum hole diameter of this method (15 cm) and is not a valid installation option.

In many cells the bag count of this table is lower than the geometric volume of the hole; for example, a hole 15 cm in diameter and 1.5 m deep holds about 26.51 litres, while the table shows one bag. These numbers are brochure estimates and are not a final order quantity until technical review.

Geometric volume: This is the gross geometric volume of the hole; it does not account for the volume of the earth rod itself, the share of backfill soil, the chamber height, the empty space above the top of the earth rod or the yield of the mortar after mixing. So the actual volume of GIM mortar or the number of bags needed cannot be derived from it, and the bag counts remain the brochure figures.

Table source: GIM brochure, 15 kg bag. The figures are quoted exactly from the brochure and are not an engineering calculation of the bag count.

Website membership required · Sign in or joinBack to the mixing instructions

Method 3: copper earth plate

Installation instructions: plate electrode in the ground with GIM®

1. Application

The copper earth plate is set vertically in a pit and covered with GIM mix below, around and above.

3. Execution drawing: final cross-section

Detailed drawing: final cross-section
Final cross-section: GIM and GIM Light with a copper earth plate Cross-section of the copper earth plate pit, 30 cm wider in diameter than the plate: 10 cm GIM bed, vertical plate with an exothermically welded connection, 10 cm GIM cover above the plate, backfill and access chamber (exact position pending technical approval). Hole diameter = plate width + 30 cm Plate width Top cover: min. 10 cm Bed: min. 10 cm Depth: to suit soil and moisture Access chamber Copper conductor / tape Backfill Exothermic weld Copper earth plate, vertical GIM or GIM Light mix:below, around and above the plate Native soil Ground level KALOT Group | GIM and GIM Light installation guide | not to scale

Swipe the drawing left and right to see all dimensions.

Figure 1: Final cross-section of the copper earth plate installation (drawn example: 60 × 60 cm plate)Download drawing (SVG)

2. Installation stepsDetailed drawing

  1. Copper earth plate, step 1: excavating a pit 30 cm wider in diameter than the plate and exothermically welding the conductor to the plate Excavating a pit 30 cm wider in diameter than the plate and exothermically welding the conductor to the plate Diameter = plate width + 30 cm Depth: to suit soil and moisture Exothermic weld 1

    Step 1: Excavate a pit whose diameter is 30 cm greater than the plate width. Set the depth to suit the soil and moisture conditions of the site. Connect the copper conductor or tape to the plate by exothermic welding at one point at least.

  2. Copper earth plate, step 2: covering the pit floor with at least 10 cm of GIM mix Covering the pit floor with at least 10 cm of GIM mix Min. 10 cm BedGIM mix 2

    Step 2: Cover the pit floor with at least 10 cm of GIM mix.

  3. Copper earth plate, step 3: setting the copper plate vertically on the GIM bed Setting the copper plate vertically on the GIM bed Copper plateVertical 3

    Step 3: Set the plate vertically in the pit. (The brochure mentions a north to south alignment for the plate; this orientation is pending technical approval before it is presented as a general requirement.)

  4. Copper earth plate, step 4: pouring GIM to at least 10 cm above the plate edge Pouring GIM to at least 10 cm above the plate edge Min. 10 cm GIM mix 4

    Step 4: Pour the GIM mix to at least 10 cm above the plate edge so that the plate is fully covered.

  5. Copper earth plate, step 5: installing the access chamber and filling the rest of the pit with soil Installing the access chamber and filling the rest of the pit with soil Access chamber Backfill 5

    Step 5: If needed, install the access chamber and fill the rest of the pit with soil. (For the chamber, the brochure gives the phrase "50 cm below ground level"; its exact position and depth are not final until technical approval and are not dimensioned in the drawing.)

4. Consumption table

In each cell, the upper number is the bag count, exactly as in the brochure. The lower number is the gross geometric volume of the cylindrical part of the hole at that column's GIM height (area of a circle of that diameter × height), in litres; this number is calculated and does not appear in the brochure.

GIM brochure table no. 3: number of bags by hole diameter and GIM height
Hole diameter (cm)Largest plate width (cm)GIM height (cm)
20 *30 *708090100120
Largest plate height (cm)-1050607080100
6030356.55 litres484.82 litres10197.92 litres12226.19 litres13254.47 litres15282.74 litres18339.29 litres
7040476.97 litres6115.45 litres14269.39 litres16307.88 litres18346.36 litres20384.85 litres24461.81 litres
80505100.53 litres8150.80 litres19351.86 litres21402.12 litres24452.39 litres27502.65 litres32603.19 litres
90607127.23 litres10190.85 litres24445.32 litres27508.94 litres30572.56 litres34636.17 litres40763.41 litres
100708157.08 litres12235.62 litres29549.78 litres33628.32 litres37706.86 litres42785.40 litres50942.48 litres
1108010190.07 litres15285.10 litres35665.23 litres40760.27 litres45855.30 litres50950.33 litres601140.40 litres
1209012226.19 litres18339.29 litres42791.68 litres48904.78 litres541017.88 litres601130.97 litres721357.17 litres

5. Notes and technical limits

* Needs technical review: No plate fits in the 20 cm column, and the 30 cm column only suits a plate up to 10 cm high; these two columns need technical review.

The bag count is not final without the actual plate dimensions: the hole diameter must be at least "plate width + 30 cm", and the GIM height must cover at least 10 cm below the plate, the plate height itself and 10 cm above it.

The "largest plate width/height" column and row are not in the brochure; they are derived only from these two brochure conditions, so that an invalid combination is easier to spot.

In some cells the bag count is estimated lower than the geometric volume of the hole; these numbers are brochure estimates and are not a final order quantity until technical review.

Geometric volume: This is the gross geometric volume of the cylindrical part; it does not account for the volume of the plate and conductor, the share of backfill soil, the chamber height or the yield of the mortar after mixing. So the actual volume of GIM mortar or the number of bags needed cannot be derived from it, and the bag counts remain the brochure figures.

Table source: GIM brochure, 15 kg bag. The figures are quoted exactly from the brochure and are not an engineering calculation of the bag count.